RFL C37.94FSU
RFL Electronics Inc.
May 20, 2013
11
(973) 334-3100
Table 4. Controls and indicators, Fiber Service Unit (107460-1 to 107460-4, 107460-1-1,107460-1-2, 107460-2-2,
107460-3-1)
Location
Reference
Designation
Function
Front Panel U8
Fiber optic detector
SW1
8-position DIP switch used to set FSU operating parameters as follows:
SW1-1 through SW1-4: Selects Data Rate in accordance with Table 6.
SW1-5: For 107460-1, -2 and -4,
Selects NORMAL or INVERTED Xmit Data Clock as follows:
Down = Normal Clock
Up = Inverted Clock
For 107460-3, SW1-5 must be UP
SW1-6: For 107460-1, -2 and -4 selects NORMAL or INVERTED
Receive Data Clock as follows:
Down = Normal Clock
Up = Inverted Clock
For 107460-3, SW1-6 must be DOWN
SW1-7: On 107460-1, -2 and –4 selects normal or inverted data as follows
Down = Inverted Data
Up = Normal Data
SW1-8: (This switch applies to G.703 only and is ignored by all other FSU
modules) Selects octet timing as follows:
Up = Octet Timing Enabled
Down = Octet Timing Disabled
DS4
Fiber optic emitter
DS5
DATA LED (green), illuminated when data is present on the electrical interface.
DS1
SYNC LED (green), illuminated when the optical signal is in sync.
DS2
YEL LED (yellow), Yellow Alarm Indication, illuminated when the remote fiber
receiver has failed and the remote transmitter is sending a yellow code by
the
local fiber receive channel.
DS3
PWR LED (green), illuminated when power is ON.
P1 or P2
Connector
Rear Panel
TB1
Power connector
Ground Lug
Ground lug
On ECB
No. 107463
Board A
F1
FSU power supply fuse (see note below)
Note:
F1 is a 0.25 Amp, 250 Volt SLO-BLO, 5x20 mm fuse.
Littlefuse part number is:
239.250
BUS part number is:
GMD-.25A