10
SSCBL-RPBL-IOM (10-22) 149159-C
INSTALLATION—CONTINUED
Mounting Support Structure—Continued
NOTES:
• Prior to installation, ensure that the method of support is in agreement with all local building
codes and, for outdoor installations, is suited to the climate.
• If the area within the curb is left open, higher radiated sound levels may result.
• The system can have a variety of configurations that affect installation. If the system does not
have a downturn plenum, the discharge is horizontal.
Curb Cap Base
•
Units are equipped with a load bearing curb cap that forms an integral part of the unit . The curb cap is welded at
all joints .
• Model SSCBL:
The curb cap has suspension holes at each corner and hanger brackets on the sides . Each
suspension location requires a 1/2-inch threaded rod (refer to
section) .
• Model RPBL:
The curb cap has a skirt that fits over a roof curb to provide a weatherproof installation . Four holes
are provided at the curb cap corners for lifting the unit . These holes do not interfere with unit weatherproofing . The
curb cap is not designed to be placed directly on the roof surface . The system may be mounted on an optional roof
curb purchased with the unit, a field-supplied roof curb, or field-supplied supports . If the system has a downturn
plenum and/or a bottom return air opening, a roof curb is recommended to provide a weatherproof installation
as well as more workable clearances for ductwork (refer to
Bottom Duct Connections (Model RPBL)
section) .
Optional Curb (Option CJ1, CJ2, CJ4, or CJ5) Assembly (Model RPBL)
NOTES:
• Curbs are shipped unassembled. Field-assembly and mounting on the roof are the responsibility
of the installer. All required hardware necessary to complete the assembly is provided.
• The system can have a variety of configurations that affect installation. Option CJ1 is for a
standard RPBL unit. Option CJ2 is for a unit with a factory-installed downturn plenum (option
AQ5 or AQ8). Option CJ4 is for a unit with a field-installed cooling coil cabinet (option AU2 or
AU3). Option CJ5 is for a unit with a field-installed cooling coil cabinet with a downturn plenum
(option AU11, AU12, AU13, or AU14).
shows a unit with an option AQ5 or AQ8 downturn
plenum. If the system does not have a downturn plenum, the discharge is horizontal.
• Field installed means that the cooling coil cabinet, with or without the downturn, is factory-
assembled and shipped separately. The roof curb is sized to accommodate the complete length
of the system. The shipped-separate cooling coil cabinet, with or without a downturn, must be
lifted to the roof separately from the packaged system, set on the roof curb, and connected to
the furnace section.