0603RHC4-JLGBEN
21
/
21
14.0 TECHNICAL DATA
Table 8 - Model RHC 4000 Specifications
Notes to table 1:
1. GCV (Hs)
2. NCV (Hi)
3. Heat output depends on airflow (see table 3a)
4. Natural gas G20 gross calorific value 10.48 kWh/m
3
@ 15 °C, 1013.25 mbar
Butane gas G30 gross calorific value 13.7 kWh/kg
Propane gas G31 gross calorific value 14.0 kWh/kg
Table 9 :
Injector size and burner pressure
G20 natural gas - inlet pressure =17.5 mbar for UK / 20.0 mbar for IE
Table 10 :
Injector size and burner pressure
G30/G31 butane/propane - inlet pressure G30 = 28mbar - inlet pressure G31 = 37mbar
(1) with open service door
Heat output
H2
Heat output
50%
100%
3
G20
G30
G31
2 stage
3
kW gros
1
KW net
2
kW
m³/h
kg/h
kg/h
kW
kW
kW
4050 06
62.00
55.90
50.80
5.90
4.50
4.40
0.15
24.00
14.40
4060 07
74.60
67.20
61.20
7,10
5.40
5,20
0.15
28.60
17.10
4075 09
91.50
82.40
75.00
8,70
6.70
6,60
0.15
36.00
21.20
4100 12
120.00
108.40
100.00
11,40
8.80
8,60
0.15
47.00
28.00
4110M.13
136.60
123.00
112.30
13.00
--
9.60
0.28
51.20
24.80
4125M.15
153.50
138.30
126.30
14.60
--
10.80
0.28
51.00
25.30
4150M.18
182.90
164.80
151.30
17.40
--
12.80
0.28
75.80
36.70
4175M.21
211.80
190.80
175.00
20.20
--
14.90
0.28
99.40
49.00
4200M.24
240.60
216.80
198.70
22.90
--
16.90
0.65
99.40
48.20
Minimum
modulating
output
Model
Heat input
Gas rate
4
Power
Consumption
mm
marking
4050 06
6
3.00
300
7.00
4060 07
7
3.00
300
7.50
4075 09
9
3.00
300
7.50
4100 12
12
3.00
300
7.50
4110M.13
13
3.00
300
7.70
4125M.15
15
3.00
300
7.40
4150M.18
18
3.00
300
7.50
4175M.21
21
3.00
300
7.70
4200M.24
24
3.00
300
7.70
Model
Quantity
Injector size
Burner
pressure
(mbar) (1)
mm
marking
Butane
Propane
4050 06
6
1.55
155
26.40
35.50
4060 07
7
1.55
155
27.20
35.50
4075 09
9
1.55
155
24.90
33.90
4100 12
12
1.55
155
25.00
33.60
4110M.13
13
1.55
155
--
35.20
4125M.15
15
1.55
155
--
34.80
4150M.18
18
1.55
155
--
34.90
4175M.21
21
1.55
155
--
35.30
4200M.24
24
1.55
155
--
34.40
Model
Quantity
Injector size
Burner pressure
(mbar)