background image

0603RHC4-JLGBEN 

17

/

21 

Consequently, 2.06m³/s (7413 m³/h) flows through the 

heat exchanger enclosure and the remaining 1.55m³/s 

(=5587m³/h) (= 3.61m³/s – 2.06m³/s) flows through 
the by-pass channel. 
From section 4.1.2 the maximum allowable airflow 
through the heating module enclosure is 23979 m³/h 
(for this example). 
We notice the 7413m³/h is still below this maximum 
allowable figure.  Consequently there is no probability 
of condensation forming within the tubes. 

 

Pressure drop : 

The total pressure drop can be derived from figure 12.  
Use the air flow through the heat exhanger  enclosure 
to determine the total pressure drop. (@7413 m³/h) 

 

Result : 70Pa (approx) 

 

 
Figure 13a 

 

 

Figure 13b 

 

12.0  Installation of RHC  

units in series 

    

12.1 General 

 

12.1.1  Two RHC 4000(M) units can be installed in 

series.  Units can be bolted together using the 
pre-punched holes in the duct flanges (see fig. 
3 for dimensions B and C).  Apply a sealant 
between two units in order to avoid air leakage. 

 
12.1.2 Each individual unit requires its own 

combustion circuit as described in sections 8.0 
& 9.0. 

 
12.1.3 Instructions 

concerning the burner and controls 

section (see section 5.0) must be followed.  
The controls sections of the 2 units in series 
can be combined, resulting in one enclosure. 
The recommendations as described in section 
4.1.2 are applicable for RHC units when 
installed in series.  Checking the possibility of 
condensation forming within the tubes must be 
done (heating section by heating section), 
taking into account the expected minimum inlet 
temperature and the heat output conditions for 
each individual heating section. 

 

12.2 

Limitations for use 

 

12.2.1  Minimum airflow requirement through heat 

exchanger enclosure : 
For RHC units, installed in series, the minimum 
airflow duty through the heat exchanger 
enclosure (see fig. 4 – table 1) must be 
observed as indicated in table 7. 

 

12.2.2  Maximum airflow through heat exchanger 

enclosure : 

 

12.3 

Pressure loss through multiple heating 
modules

 

The charts below (figures 14) indicates the 
pressure loss over the heating module versus 
the total air volume through the heat exchanger 
enclosure (see figure 4 and table 1).  The 

temperature rise (

T) as shown is for 100% 

heat output. 

 

Table 7 :Minimum airflow requirements for 2 RHC 
units in series : 

 

Model

V (m

³

/h)

Model

V (m

³

/h)

2x 4050-06

5950 2x 4110M,13

13600

2x 4060-07

7150 2x 4125M,15

15600

2x 4075-09

8800 2x 4150M,18

17500

2x 4100-12

11700 2x 4175M,21

20600

2x4200M,24

23300

V = min. airflow required through heat exchanger 
enclosure

Содержание RHC 4000 DJL Series

Страница 1: ...n air handler or as part of an air handling system These appliances meet the following EC Directives Dir CE 90 396 EEC GAD Dir CE 89 336 EEC EMC Dir CE 73 23 EEC LVD Dir CE 89 392 EEC MD annex ll sub...

Страница 2: ...e destined to be incorporated in other machines air handlers and are for this reason not entirely in compliance with the machinery directive 89 392 EEC as amended 91 368 EEC 93 444 EEC 93 68 EEC Prope...

Страница 3: ...rs via a duct terminating from the appliance vertically 1 9 Dew point The condition when the temperature is such that the water vapour in the combustion products condenses out 2 0 BASIC INFORMATION 2...

Страница 4: ...441 224 268 118 85 516 291 268 118 4075 09 741 800 613 187 160 581 224 268 118 85 656 291 268 118 4100 12 950 800 613 187 160 790 224 268 118 85 865 291 268 118 4110M 13 1132 930 778 152 190 942 361...

Страница 5: ...Table 1 Dimensions E min dimension Figure 5 Installation possibilities for RHC 4000 air heater modules 4 0 LIMITATIONS FOR USE 4 1 Heat exchanger compartment 4 1 1 Minimum airflow requirement through...

Страница 6: ...rt of the tubes Figure 6 indicates the probability of condensation forming within the tubes reference the temperature rise of the air through the enclosure around the tubes see table 1 fig 4 the inlet...

Страница 7: ...ectrical services shall not be larger than to permit a ball of 16 mm diameter to pass with a pressure of 5N 5 1 5 Dimensions mm of control cabinet with reference to figure 4 the dimensions of the cont...

Страница 8: ...installation has been completed and earth continuity test must be carried out 7 1 3 The electrical equipment of the module complies with the requirements of EN 60335 1 EN60730 1 and EN61058 1 or to re...

Страница 9: ...e the combustion inlet grill at the control door panel is completely sealed to prevent ingress of water It is forbidden to use the combustion inlet grill as passage for cables or gas supplies Ensure t...

Страница 10: ...sealed ring type Connections between the burner module controls compartment must be effectively sealed from the appliance air stream so the pressure within the compartment remains neutral 9 0 COMBUST...

Страница 11: ...the mounting flange of the heating module see figure 9 9 1 8 A gas service inlet PVC sealing ring is also provided for the appliance for size Rc or Rc 1 for the M models The hole size required for thi...

Страница 12: ...ithin the combustion circuit Hole dia 142mm required to receive seal ring PN 06 22786 134 Hole dia 142mm required to receive seal ring PN 06 22786 134 Hole dia 50 or 70mm required to receive gas passa...

Страница 13: ...9000 23000 27000 Airflow m h through the heat xchanger enclosure Pressure loss Pa RHC4100 12 RHC4075 09 RHC4060 07 RHC4050 06 38 34 30 27 24 22 20 18 17 16 15 14 13 12 11 11 12 13 14 38 34 32 30 28 26...

Страница 14: ...rder to ensure that the airflow through the heat exchanger enclosure always meets the minimum airflow requirements as mentioned in table 6 Table 6 V1 minimum airflow required through heat exchanger en...

Страница 15: ...n for heat output H2 Result dimension B 670 50mm dimension X 800mm R1 138 20 R2 334 60 dimension C 136 20 x 3 61 334 60 4C 164 30mm Note In this case 2 44m s 8800m h flows through the heat exchanger e...

Страница 16: ...xchanger enclosure 2 44 m s 8800 m h Total pressure drop 90 Pa approx 11 3 Calculation of alternative by pass dimension Due to space restrictions it may not be possible to use the above mentioned maxi...

Страница 17: ...lowed The controls sections of the 2 units in series can be combined resulting in one enclosure The recommendations as described in section 4 1 2 are applicable for RHC units when installed in series...

Страница 18: ...38 41 44 47 50 T 2x RHC4060 07 Pressure losses through 2 RHC 4000M heating modules in series 300 350 400 450 500 550 600 650 700 750 800 12000 14000 16000 18000 20000 22000 24000 airflow m h Pressure...

Страница 19: ...pass dimension Due to space restrictions it may not be possible to use the above mentioned maximum dimension by pass In this case a smaller by pass can be applied Obviously this smaller by pass will...

Страница 20: ...r the RHC heating coil it is stronly recommen ded to follow the installation method as described in figure 15 Figure 15 Installation of air fan With A min distance fan heating coil D width of duct sec...

Страница 21: ...4100 12 120 00 108 40 100 00 11 40 8 80 8 60 0 15 47 00 28 00 4110M 13 136 60 123 00 112 30 13 00 9 60 0 28 51 20 24 80 4125M 15 153 50 138 30 126 30 14 60 10 80 0 28 51 00 25 30 4150M 18 182 90 164...

Отзывы: