Weights (kg)
4050 06
4060 07
4075 09
4100 12
4110M.13
4125M.15
4150M.18
4175M.21
4200M.24
unit
90
100
120
149
200
220
250
279
313
packaging
29
29
29
29
58
58
58
58
58
total
119
129
149
178
258
278
308
337
371
2.8 Weights
3.0
PRACTICAL APPLICATION
Heat exchanger compartment size.The duct section or air
handler compartment must be sized in accordance with the
dimensions given in table 1 with reference to figure 4.
Mounting flanges on the modules RHC 4000(M)RJL &
DJL allow easy installation.
The heating module may only be fitted as shown in
figure 5.
Alternative orientation is
not
allowed.
Figure 4. : Compartment dimensions
Table 1 : Dimensions
E = min. dimension
Figure 5 : Installation possibilities for RHC 4000 air heater
modules
4.0 LIMITATIONS FOR USE
4.1
Heat exchanger compartment
4.1.1
Minimum airflow requirement
through heat
exchanger enclosure :
RHC 4000(M) RJL & DJL air heaters may be
used for either push or pull through air heaters.
The minimum airflow duty through the heat
exchanger enclosure (see fig. 4 – table 1)
must be observed as indicated in table 2.
H
H1
Y
Y2
W
W1
E
4050 06
531
461
1049
975
800
800
400
4060 07
601
531
1049
975
800
800
400
4075 09
741
671
1049
975
800
800
400
4100 12
950
880
1049
975
800
800
400
4110M.13
1132
1062
1049
975
930
930
420
4125M.15
1272
1202
1049
975
930
930
420
4150M.18
1481
1411
1049
975
930
930
420
4175M.21
1691
1621
1049
975
930
930
420
4200M.24
1900
1830
1049
975
930
930
470
Model
Duct channel & controls compartment