background image

Page 22

13. Check-Test Start (cont'd)

Startup (cont'd)

o

 Turn on the disconnect switch and re-check the slope gauge. If air

pressure differential is within the limits of -.25" to -.75" w.c., no further
adjustment is required. If the air pressure differential is not within those
limits, re-adjust the blower speed.

o

 When the differential air pressure is within the limits, check the motor

amp draw with an ammeter to be sure that the motor is not overloaded.
Amps are shown on the motor nameplate.

o

If an inlet or outlet duct system is attached to the heater, run the blower to

purge the volume of air from the duct system with at least four air
changes.

o

Turn the blower switch to OFF and damper test switch to RUN. Turn the

disconnect switch OFF. Disconnect the manometer and the slope gauge.
Replace the tubing caps.

ring will result in .233" change in pitch diameter. To increase
blower speed, decrease diameter. CAUTION: Do not adjust
sheaves in either direction to the point where moveable and
stationary flanges are in contact.
(d)
 Re-tighten the locking screws.

All Motor Sizes - Replace the belts and check belt tension. Be
sure that belts are aligned in the pulley grooves and are not
angled from pulley to pulley.

ring will result in .233" change in pitch diameter. To
decrease blower speed, increase diameter. CAUTION: Do
not adjust sheaves in either direction to the point where
moveable and stationary flanges are in contact.
(d) 
Re-tighten the locking screws.

All Motor Sizes - Replace the belts and check belt tension. Be

sure that belts are aligned in the pulley grooves and are not
angled from pulley to pulley.

DETERMINE the type of gas control system from the Model or Serial No. Suffix on the unit rating plate:

Suffix ..... Where ............ Option ................ Gas Control System
None ...... N/A ................. AG1 ..................... Single Stage with Air Controller
-2 ........... Model No. ...... AG3 ..................... Two Stage with Two-Stage Ductstat
-MV-7 .... Serial No. ....... AG30 or AG31 ..... Maxitrol Series #14 Outside Air Only (Amplifier A1014)
-MV-8 .... Serial No. ....... AG32 ................... Maxitrol Series #14A Outside Air Only (Amplifier A1014)
-MV-9 .... Serial No. ....... AG33 ................... Maxitrol Series #44 Outside Air Only (Amplifier A1044)
-MV-B ... Serial No. ....... AG36 ................... Paint Spray Booth System (Maxitrol 94)
-MV-C ... Serial No. ....... AG37 ................... Maxitrol Series #DDC for Outside Air Only (Signal Conditioner A200)
-MV-D ... Serial No. ....... AG47 ................... Maxitrol Series #14 Outside Air and Recirculation (Amplifier ADFM14)
-MV-E .... Serial No. ....... AG48 ................... Maxitrol Series #44 Outside Air and Recirculation (Amplifier ADFM44)
-M .......... Model No. ...... AG49 ................... Mechanical Modulation, 40-160°F
-M .......... Model No. ...... AG50 ................... Mechanical Modulation, 40-120°F
-MV-F .... Serial No. ....... AG51 ................... Maxitrol Series DDC for Outside Air and Recirculation

For units with Maxitrol Series 14 or 14A, remove and individually tape wires from Terminals #4 and #8 on the amplifier
For units with Maxitrol Series 44, remove and individually tape wires from Terminals #2, #4 and #8 on the amplifier

For units with Maxitrol Series DDC, the customer provided input signal must be 4-20 milliamps (conditioner
dip switch "on") or 0-10 volt DC (conditioner dip switch "off").

3.  Check pilot and burner ignition and pilot operation (hot surface ignition)

o

Turn the disconnect switch ON. Turn blower service switch and burner

service switch to TEST position.

o

Observe for ignition through the viewport.

 

Check for lights - Lights listed in prior Steps should be energized. After

15-20 seconds, the "Pilot Valve" light will light to signal the pilot igni-
tion, followed by the "Main  Valve" light signaling main burner operation.

o

With both the burner and blower operating, measure the gas pressure at

the burner. Gas pressure should match the required manifold pressure
listed on the rating plate. (If pressure does not match the required pres-
sure, further testing is required in Step 5.) Remove the manometer.

o

Leak test all connections in the pilot and main burner supply lines.

WARNING: DO NOT TEST WITH OPEN FLAME.

Содержание RDF 1-20-3

Страница 1: ...tem provides tempered makeup air Makeup air is defined as air that enters a building or area due to negative pressure created by an air exhaust load in excess of the volume of entering air This system...

Страница 2: ...account through standard engineering methods the structure s designed infiltration rate by providing properly sized relief openings by interlocking a powered exhaust system or by a combination of thes...

Страница 3: ...e Sensor Option AR32 Toggle Switch Option AR36 Photohelic Pressure Sensor Option AR37 Photohelic Pressure Sensor If an optional remote console is ordered these controls are mounted on the console The...

Страница 4: ...al to the width of the unit Top View Control Side Front View Rear View A Full Length of Outside of Curb Cap D Inside of Curb Cap Z Y B Cabinet Height 2 5 8 67 Control Compartment Blower Compartment Su...

Страница 5: ...88 37 1 8 44 3 16 84 13 16 45 1 2 24 1 2 10 1 2 5 7 16 14 9 32 15 5 8 21 29 32 19 1 8 2 80 3 2 120 3 88 48 11 16 68 1 4 84 13 16 69 1 2 52 16 1 4 5 5 16 10 15 16 15 1 2 27 9 32 27 7 32 3 180 3 3 260...

Страница 6: ...placed directly on a surface cross supports should be placed underneath the rails at the ends and at the cabinet joint Refer to FIGURE 4 IMPORTANT NOTE Mount an outdoor unit with a minimum of 14 clear...

Страница 7: ...8 1 7 8 48 1 7 8 48 Roof Curb Ductwork for Bottom Discharge Option AQ1 or AQ3 Roof Curb Ductwork for Optional Return Air Airflow See IMPORTANT NOTE on the left Roof Curb Dimensions for Model RDF Serie...

Страница 8: ...tolerance of 1 8 5 Level the roof curb To ensure a good weatherproof seal between the unit curb cap and the roof curb the roof curb must be leveled in both direc tions with no twist end to end Shim as...

Страница 9: ...system is automatically controlled to maintain a set building pressure the en tering air will travel naturally toward the relief areas at the perimeter walls using the building structure as the distr...

Страница 10: ...the type of construction of the roof wood joist steelbar joist steel truss pre cast concrete etc and the ceiling hung flush etc o Rectangular ducts should be constructed of not lighter than No 26 U S...

Страница 11: ...er Light and Potentiometer If ordered the optional remote console is shipped separately Re mote consoles include terminal blocks for wiring Depending on what gas control or inlet air options were orde...

Страница 12: ...normally open differential pressure switch that senses air pressure across the filter bank There are field installation procedures that must be done for the proper operation of the dirty filter indic...

Страница 13: ...valve will not open If the actual temperature of the outside air is above the setpoint on the outside air control the burner will not ignite may modulate to satisfy discharge setting would shutdown co...

Страница 14: ...t this switch The pressure null switch is Dwyer 1460 0 with a range of 01 12 w c The pressure null switch is a diaphragm operated differential pressure switch used in makeup air applications to contro...

Страница 15: ...n AR33 or AR34 and or with Gas Control Option AG37 or AG51 If the system includes Air Control Option AR33 the discharge damper is con trolled by a field supplied 0 10VDC or 4 20 milliamp signal If the...

Страница 16: ...dance with the requirements of the National Fuel Gas Code ANSI Z223 1 latest edition or CAN1 B149 1 and B149 2 Gas supply piping installation must conform with good practice and with all local codes R...

Страница 17: ...te on a natural gas pilot supply pressure of 3 5 w c or propane gas of 6 0 w c Measure both operating pressure and pilot supply pressure with the blower in operation Manifold pressure is defined as th...

Страница 18: ...ocedure in Paragraph 13 Motor Loads Use an ammeter to check motor amps Amps may be adjusted downward by reducing blower RPM or by increasing duct system static pres sure For accurate amps read the mot...

Страница 19: ...k Test Start FIGURE 26 Control Locations in the Electrical Compartment RDF Series 3 Direct Fired Systems NOTE Locations may not be identical but controls should be smilar Check Test Startup Procedures...

Страница 20: ...oIf equipped with any manually reset devices such as an optional firestat limit switch a high limit switch and or optional high gas pressure switch reset devices Check setpoint on the high ambient bu...

Страница 21: ...oosen the setscrew on the side of the pulley away from the motor c Turn adjustable half of the pulley inward to increase blower speed One turn of the pulley will change speed 8 to 10 d Tighten the set...

Страница 22: ...er 2 Model No AG3 Two Stage with Two Stage Ductstat MV 7 Serial No AG30 orAG31 Maxitrol Series 14 Outside Air Only Amplifier A1014 MV 8 Serial No AG32 Maxitrol Series 14A Outside Air Only Amplifier A1...

Страница 23: ...k the main burner inlet gas pressure If the main inlet gas pressure is lower than stated on the rating plate full burner firing rate will not be achieved Check main gas supply service regulator for ad...

Страница 24: ...irements in the installation codes and operating instructions The amount of air over the burner must be within the specified range The burner profile plates are set at the factory to match CFM require...

Страница 25: ...ate N A 2 91584 2 98764 Filter Block Off Sections N A 6 95335 6 96335 Permanent Filters 12 N A 1 87251 2 94383 Sheetmetal Screws 10 x 1 2 long Screws 1 4 20 x 5 8 long bolt type Hex Nuts 1 4 20 Keps S...

Страница 26: ...inet Post Bottom Filter Channel with Blockoff Plate assembled in 1B P N 91578 Intermediate Cabinet Post Center Channel Assy Step 1C Assemble Outer Side of Filter Rack Options AS6 and AS7 only Parts Re...

Страница 27: ...tach Assembled Cabinet Section 4 Assemble Air Inlet Hood Section P N 91569 Right Side of Hood P N 91568 Left Side of Hood Step 4A Attach Hood Sides Attach the sides to the interme diate posts and bott...

Страница 28: ...er Louver Supports Step 4E Install Louvers Parts Required Two factory assembled louver sec tions 19 screws 1 2 long and five Tinnerman clips Position one louver section in the left side of the hood at...

Отзывы: