background image

Page 12

FIGURE 11 - Dirty Filter
Pressure Switch

Set screw (on
front of switch)
must be
manually
adjusted after
system is in
operation.

Negative pressure connection is

toward the "back or bottom"

of the switch (senses blower side

of filters)

Positive pressure connection is

toward the "front or top" of the

switch (senses air inlet side of filters)

FIGURE 10 - Remote Console Dimensions

Dirty Filter Light

2-3/8

(60)

6 (152)

5-15/32 (139)

1-5/16 (33)

1-3/32 (28)

4-7/16

(113)

1-3/32 (28)

FIGURE 10 - Technical Data of the Remote Console (Variations depend on options selected; consult custom wiring diagram for 

controls and to determine wiring required.)  

Control  Qty of  Temperature  Potentiometer 

Dimensions - inches (mm)

Switch Lights*

Selector**

*** L****

H****

D

Yes

3

Yes

No

10-3/4 (273) 7-5/8 (194) 2-5/8 (67)

Yes

3

No

No

10-3/4 (273) 7-5/8 (194) 2-5/8 (67)

Yes

3

Yes

Yes

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

3

No

Yes

10-3/4 (273) 7-5/8 (194) 2-5/8 (67)

Yes

4

Yes

No

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

4

No

Yes

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

4

Yes

Yes

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

4

No

No

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

* 3 - Blower On, Burner On, and Safety Lockout on both RC13 and RC14; 
   4th light is Dirty Filter Indicator on Option RC14 only
** On the console with Gas Control Options AG 31, 32, 33, 35, 47, or 48
*** On the console with Air Control Options AR19 or AR22
**** Subtract 1" (25mm) when recessing

Locations of Knockout

Holes (dimensions to

centerlines)

When a console with a dirty filter indicator is selected, the remote console
includes a fourth light (dirty filter indicator light). The light is activated by an
adjustable, single-pole/normally open differential pressure switch that senses
air pressure across the filter bank. There are field-installation procedures that
must be done for the proper operation of the dirty filter indicator light.

10. Electrical Supply, Connections and Controls (cont'd)

Dirty Filter Light
Installation Instructions

o

Before the system is operating, connect the sensing tubes from the
switch to their sensing locations in the field-installed filter cabinet. (Cabi-
net installation instructions are in Paragraph 15.)

1) Run the tubes through the holes in the cabinet wall. Pull gently to

extend the tubing to its entire length without stress.

2) Position the tubing approximately at the center of the height of the filter

rack.

3) Identify the tube connected to the positive connection on the switch

(FIGURE 11) as the positive pressure tube. Determine the length of
tubing required to attach the positive pressure tube so that it will sense
pressure at the inlet side
 of the filter rack.

Identify the tube connected to the negative connection on the switch (FIG-
URE 11
) as the negative pressure tube. Determine the length of tubing
required to attach the negative pressure tube so that it will sense the
pressure at the blower side
 of the filter rack.

(NOTE: Tubing shipped is the same length for all sizes of systems; cut to
the appropriate length for the smaller systems.)

4) If required, cut the tubing to the proper lengths. Using the clamps

provided, attach the ends of the tubing to the filter rack at about center
height being careful not to kink or compress the tubing.

o

After the system is operating, the filter switch must be manually set.
With clean filters in place, blower doors closed, and blower in operation,
increase the pressure setting by adjusting the set screw on the switch

Содержание RDF 1-20-3

Страница 1: ...tem provides tempered makeup air Makeup air is defined as air that enters a building or area due to negative pressure created by an air exhaust load in excess of the volume of entering air This system...

Страница 2: ...account through standard engineering methods the structure s designed infiltration rate by providing properly sized relief openings by interlocking a powered exhaust system or by a combination of thes...

Страница 3: ...e Sensor Option AR32 Toggle Switch Option AR36 Photohelic Pressure Sensor Option AR37 Photohelic Pressure Sensor If an optional remote console is ordered these controls are mounted on the console The...

Страница 4: ...al to the width of the unit Top View Control Side Front View Rear View A Full Length of Outside of Curb Cap D Inside of Curb Cap Z Y B Cabinet Height 2 5 8 67 Control Compartment Blower Compartment Su...

Страница 5: ...88 37 1 8 44 3 16 84 13 16 45 1 2 24 1 2 10 1 2 5 7 16 14 9 32 15 5 8 21 29 32 19 1 8 2 80 3 2 120 3 88 48 11 16 68 1 4 84 13 16 69 1 2 52 16 1 4 5 5 16 10 15 16 15 1 2 27 9 32 27 7 32 3 180 3 3 260...

Страница 6: ...placed directly on a surface cross supports should be placed underneath the rails at the ends and at the cabinet joint Refer to FIGURE 4 IMPORTANT NOTE Mount an outdoor unit with a minimum of 14 clear...

Страница 7: ...8 1 7 8 48 1 7 8 48 Roof Curb Ductwork for Bottom Discharge Option AQ1 or AQ3 Roof Curb Ductwork for Optional Return Air Airflow See IMPORTANT NOTE on the left Roof Curb Dimensions for Model RDF Serie...

Страница 8: ...tolerance of 1 8 5 Level the roof curb To ensure a good weatherproof seal between the unit curb cap and the roof curb the roof curb must be leveled in both direc tions with no twist end to end Shim as...

Страница 9: ...system is automatically controlled to maintain a set building pressure the en tering air will travel naturally toward the relief areas at the perimeter walls using the building structure as the distr...

Страница 10: ...the type of construction of the roof wood joist steelbar joist steel truss pre cast concrete etc and the ceiling hung flush etc o Rectangular ducts should be constructed of not lighter than No 26 U S...

Страница 11: ...er Light and Potentiometer If ordered the optional remote console is shipped separately Re mote consoles include terminal blocks for wiring Depending on what gas control or inlet air options were orde...

Страница 12: ...normally open differential pressure switch that senses air pressure across the filter bank There are field installation procedures that must be done for the proper operation of the dirty filter indic...

Страница 13: ...valve will not open If the actual temperature of the outside air is above the setpoint on the outside air control the burner will not ignite may modulate to satisfy discharge setting would shutdown co...

Страница 14: ...t this switch The pressure null switch is Dwyer 1460 0 with a range of 01 12 w c The pressure null switch is a diaphragm operated differential pressure switch used in makeup air applications to contro...

Страница 15: ...n AR33 or AR34 and or with Gas Control Option AG37 or AG51 If the system includes Air Control Option AR33 the discharge damper is con trolled by a field supplied 0 10VDC or 4 20 milliamp signal If the...

Страница 16: ...dance with the requirements of the National Fuel Gas Code ANSI Z223 1 latest edition or CAN1 B149 1 and B149 2 Gas supply piping installation must conform with good practice and with all local codes R...

Страница 17: ...te on a natural gas pilot supply pressure of 3 5 w c or propane gas of 6 0 w c Measure both operating pressure and pilot supply pressure with the blower in operation Manifold pressure is defined as th...

Страница 18: ...ocedure in Paragraph 13 Motor Loads Use an ammeter to check motor amps Amps may be adjusted downward by reducing blower RPM or by increasing duct system static pres sure For accurate amps read the mot...

Страница 19: ...k Test Start FIGURE 26 Control Locations in the Electrical Compartment RDF Series 3 Direct Fired Systems NOTE Locations may not be identical but controls should be smilar Check Test Startup Procedures...

Страница 20: ...oIf equipped with any manually reset devices such as an optional firestat limit switch a high limit switch and or optional high gas pressure switch reset devices Check setpoint on the high ambient bu...

Страница 21: ...oosen the setscrew on the side of the pulley away from the motor c Turn adjustable half of the pulley inward to increase blower speed One turn of the pulley will change speed 8 to 10 d Tighten the set...

Страница 22: ...er 2 Model No AG3 Two Stage with Two Stage Ductstat MV 7 Serial No AG30 orAG31 Maxitrol Series 14 Outside Air Only Amplifier A1014 MV 8 Serial No AG32 Maxitrol Series 14A Outside Air Only Amplifier A1...

Страница 23: ...k the main burner inlet gas pressure If the main inlet gas pressure is lower than stated on the rating plate full burner firing rate will not be achieved Check main gas supply service regulator for ad...

Страница 24: ...irements in the installation codes and operating instructions The amount of air over the burner must be within the specified range The burner profile plates are set at the factory to match CFM require...

Страница 25: ...ate N A 2 91584 2 98764 Filter Block Off Sections N A 6 95335 6 96335 Permanent Filters 12 N A 1 87251 2 94383 Sheetmetal Screws 10 x 1 2 long Screws 1 4 20 x 5 8 long bolt type Hex Nuts 1 4 20 Keps S...

Страница 26: ...inet Post Bottom Filter Channel with Blockoff Plate assembled in 1B P N 91578 Intermediate Cabinet Post Center Channel Assy Step 1C Assemble Outer Side of Filter Rack Options AS6 and AS7 only Parts Re...

Страница 27: ...tach Assembled Cabinet Section 4 Assemble Air Inlet Hood Section P N 91569 Right Side of Hood P N 91568 Left Side of Hood Step 4A Attach Hood Sides Attach the sides to the interme diate posts and bott...

Страница 28: ...er Louver Supports Step 4E Install Louvers Parts Required Two factory assembled louver sec tions 19 screws 1 2 long and five Tinnerman clips Position one louver section in the left side of the hood at...

Отзывы: