High Temperature Limit Troubleshooting
•
The high temperature limit cycles whenever internal temperature exceeds the non-adjustable limit setpoint: 145°F
for unit size 095 or 160°F for unit sizes 140 and 190.
•
The cause must be found and corrected for heater to function safely/properly. Refer to the flowchart shown in
for troubleshooting steps.
•
If the fan and limit controls require replacement, see
•
If the heat exchanger and fan require cleaning, refer to
Clean Combustion Chamber/Heat Exchanger and Flue
and
Clean Exterior Surfaces of Combustion Chamber/Heat Exchanger and Clean Fan Assembly
sections.
Figure 24. High Temperature Limit Troubleshooting Flowchart
Does the fan
operate?
Are the heat
exchanger surfaces
and/or the fan blades
covered with
dirt?
Clean the heat
exchanger and fan.
Remove ducts or
deflector from heater.
Check for 115
volts across fan leads.
Is voltage
read?
Replace fan
motor.
Check for 115 volts
across Terminals 1 & 2.
Is voltage
read?
Replace fan and limit
controls assembly.
Check wiring.
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Have ducts or
air deflectors
been added ?
Replace fan and limit
controls assembly.