0505T2D0GBEN
3/21
(anticipated 1996)
1.11 The criteria recommended in this document regarding
airflow pressures, temperature rise, firing rates and
fitting methods must be strictly complied with, wether
or not the appliance is used as a duct heater or as
part of an multi-functional appliance, to ensure
satisfactory operation.
SECTION 2. TECHNICAL DATA
Table 1. Appliance Data Standard Efficiency Models
EURO-T Standard Model #
2025D
2030D
2035D
2045D
2055D
2075D
2095D
EURO-T Low
NO
x
#
2525D
2530D
2535D
2545D
2555D
2575D
2595D
Gas category 'Cat.'
II
2H3
Air supply and flue type
B22 - C12 - C32
Heat input (Hs) 'Qn'
kW
28,8
35,2
42,7
49,9
63,2
86,5
115,4
Heat input (Hi) 'Qn'
kW
26,0
31,7
38,5
45,0
57,0
78,0
104,0
High heat output
kW
22,8
27,8
33,7
39,4
49,9
68,3
91,0
Number of jets
4
5
7
9
12
16
natural gas
i
mm
2.4
2.2
2.4
Jet size
propane/butane
i
mm
1.35
1.25
1.35
natural gas
mbar
(GB) =
17.5
(IE) =
20.0
propane
mbar
37.0
Gas supply
pressure 'P'
1
butane
mbar
28.0
Burner pressure
2
natural gas
mbar
8.50
natural gas
3
m
3
/h
2.70
3.36
4.10
4.76
6.10
8.30
11.00
propane
kg/h
2.06
2.52
3.05
3.56
4.51
6.18
8.25
Gas consumption
butane
kg/h
2.10
2.60
3.12
3.64
4.61
6.31
8.42
Gas service connection (not supply line size)
Rc
:
Electrical supply
230/240V 1 N
-
50Hz
Electrical rating
4
180 W
Protection grade
IP20
Appliance weight net
kg
80
85
99
115
139
171
Appliance weight gross (shipping)
"
kg
88
96
109
126
152
187
1
Maximum gas pressure at inlet to appliance = 50,0 mbar
2
All casing panels fitted, service door open
3
Natural gas G20, caloric heating value 10,5 kWh/m
3
on Hs @ 15
E
C & 1013 mbar
Propane G31, caloric heating value 12,88 kWh/kg
Butane G30, caloric heating value 12,66 kWh/kg
4
Total electrical rating during the start-up period
"
30 seconds is increased by 130 W and is not included on the appliance
data plate or in the above table