0505T2D0GBEN
4/21
Table 2
Appliance Data
Higher Efficiency Models
EURO-T Standard Model #
2026D
2031D
2036D
2046D
2056D
2076D
2096D
EURO-T Low NO
x
Model #
2526D
2531D
2536D
2546D
2556D
2576D
2596D
High fire heat output
kW
23.7
28.9
35.1
41.0
51.9
71.0
94.7
Note: All other data as standard model
Table 3 Minimum air volumes for maximum temperature rise. Standard Appliance
Standard model Euro-T...
2025D
2030D
2035D
2045D
2055D
2075D
2095D
High efficiency model Euro-T...
2026D
2031D
2036D
2046D
2056D
2076D
2096D
Minimum air volume
m
3
/h
1800
2200
2660
3110
3940
5400
7190
Maximum temperature rise
_T
K
37
Table 4 Minimum air flows for maximum temperature rise. Low NO
x
Models
Standard model Euro-T...
2525D
2530D
23535D
2545D
2555D
2575D
2595D
High efficiency model Euro-T...
2526D
2531D
2536D
2546D
2556D
2576D
2596D
Maximum air volume
m
3
/h
2080
2540
3080
3600
4555
6240
8300
Maximum temperature rise
_T
K
32
N.B. The maximum static pressure that may be applied to the Euto-T...D series is 800 Pa
Figure 1 Pressure loss for air flow passing
Euro-T... D series air heaters
Figure 2. Combustion circuit Dew-point occurrence