background image

 

0505T2D0GBEN

 

20/21 

 
 

SECTION 13. USER INSTRUCTIONS  Euro-T.. AIR HEATERS 

 

SPECIAL NOTE 

The following instructions have been written assuming 
that the Euro-T...D air heater is installed as a heating 
module independent of being installed within an air 
handling appliance. When installed within an air 
handling appliance or as part of a multi-
appliance/purpose system it will be necessary to read 
any supplementary instructions in conjunction with this 
document.

 

 
OPERATING

 

 

How the air heater works: 

 
Gas is burned by an atmospheric burner which fires into a 
heat exchanger. The gas burner is controlled by a double gas 
valve via an electronic burner control, which is actuated 
automatically via external controls i.e. a room thermostat 
and/or a time switch. The burner is ignited by a hot surface 
igniter. When the burner fires and warms the heat exchanger, 
the heat is sensed by a thermally actuated fan control which 
switches on the fan when the air temperature has reached its 
preset operating level. 
At the end of a heating cycle the burner is switched off, the 
air circulation fan will continue to run until the air heater has 
cooled to a safe condition. Thereafter the fan will remain off 
until the next cycle is initiated. 
 

Safety:

 

 
1.  Flame failure is detected by the hot surface igniter which 

is also the sensor and will immediately result in gas valve 
shut down. 

2.  Safety against overheating is assured by two overheat 

controls. The first is an automatic recycle control which 
protects against low air flow i.e. clogged air ways, fan 
failure etc. The second, which is set to a higher level than 
the first one, is a control which locks out and switches off 
the burner in the event of gross overheating for any 
reason. Manual intervention is necessary to reset this 
control device. Resetting of the automatic burner control 
may also be required. 

3.  The location of the air heater should be maintained at 

normal atmospheric pressure. Changes to the building 
after air heater installation, should have regard to the 
heating installation, i.e. structural changes causing 
excessive draught from doors, windows etc. Other air 
handlers and installation of air extraction equipment which 
may cause a negative pressure environment, can 
seriously affect the operation of this type of air heater, 
especially if combustion air supply is not ducted. 

 

To light the heater:

 

 

1.  Turn on the gas supply to the air heater. 
2.  Switch on the electricity supply to the air heater. 
3.  Ensure time switch (if fitted) is set to a 'ON' cycle. 
4. Adjust 

control/room 

thermostat to desired  

temperature. 

5.  Air heater will light automatically when the room 

thermostat calls for heat. 

 
 
6.  If the appliance does not light: 

a)

 check that the burner control does not require 

resetting. An indicator light glows at the front panel of 
the appliance and on a remote control if fitted). Reset 
by pushing light/button on appliance or the remote 
control. 

b)

 check if thermal overheat control requires resetting 

(see fig. 12 page 15 key 16). 

7.  If the thermal overheat control requires resetting and 

doing so restarts the air heater, wait until the 
appliance warms to thermal equilibrium, to ensure 
the overheat control does not lock out again. 

If it 

does and the temperature near the heater is less 
than 30

E

C, then switch off the appliance and call 

for service.

 If the temperature is over 30

E

C, take 

appropriate action to reduce the ambient temperature 
near the air heater. 

 

Air circulation:

 

 

1.  The space heating process is for air to be circulated 

through the appliance whereby it gains heat from a 
heat exchanger. The air is directly discharged into 
the space to be heated. The air is eventually re-
circulated. Therefore it is very important that an 
unobstructed path for the circulation of the air will be 
maintained. This is particularly important if the air 
heater has been installed to blow through the wall 
between two rooms. 

2.  Sometimes the air circulation fan of the appliance is 

connected to a remote over-ride switch. This enables 
cool air to be used for circulation purposes when the 
air heater is not used for heating purposes e.g. in 
summer. 
To use this feature: 

a)

 switch ON electricity 

b)

 switch ON manual override switch, this may be 

fitted as a feature on a remote composite control.  

 

Maintenance:

 

 

1.  Maintenance and service must only be carried out by 

appropriately qualified persons e.g. "Corgi" registered 
undertakings. 

2.  It is in your interest to ensure service and 

maintenance is carried out at regular intervals. 
Periods between service are dependent upon the 
local environment where the heater is installed. All 
gas appliances should be serviced at least once a 
year.  

3.  In case of any damage to the appliance, it must be 

shut down completely and checked by an 
appropriately qualified person. 4.In the event of 
difficulties in resolving any of these matters, please 
do not hesitate to contact Reznor or their official 
distributor. 

Содержание Euro-T 2025D

Страница 1: ... B22 C12 C32 INSTALLATION COMMISSIONING SERVICING USER INSTRUCTIONS These appliances meet the following EC Directives Dir CE 90 396 EEC GAD Dir CE 89 336 EEC EMC Dir CE 73 23 EEC LVD PLEASE READ THIS DOCUMENT CAREFULLY BEFORE COMMENCING INSTALLATION AND LEAVE IT WITH THE USER OR ATTACHED TO THE APPLIANCE OR GAS SERVICE METER AFTER INSTALLATION ...

Страница 2: ...nd recommendations of British Standard BS 6230 1991 Installation of Gas Fired Forced Convection Air Heaters for Commercial and Industrial Space Heating The Installation must also be in accordance with the relevant requirements of The Gas Safety Installation and Use regulations and Amendment Regulations 1990 and The Building and Electrical Regulations in GB the IEE Regulations The requirements of t...

Страница 3: ...2 4 Jet size propane butane i mm 1 35 1 25 1 35 natural gas mbar GB 17 5 IE 20 0 propane mbar 37 0 Gas supply pressure P 1 butane mbar 28 0 Burner pressure 2 natural gas mbar 8 50 natural gas 3 m3 h 2 70 3 36 4 10 4 76 6 10 8 30 11 00 propane kg h 2 06 2 52 3 05 3 56 4 51 6 18 8 25 Gas consumption butane kg h 2 10 2 60 3 12 3 64 4 61 6 31 8 42 Gas service connection not supply line size Rc Electri...

Страница 4: ...del Euro T 2026D 2031D 2036D 2046D 2056D 2076D 2096D Minimum air volume m 3 h 1800 2200 2660 3110 3940 5400 7190 Maximum temperature rise _T K 37 Table 4 Minimum air flows for maximum temperature rise Low NOx Models Standard model Euro T 2525D 2530D 23535D 2545D 2555D 2575D 2595D High efficiency model Euro T 2526D 2531D 2536D 2546D 2556D 2576D 2596D Maximum air volume m 3 h 2080 2540 3080 3600 455...

Страница 5: ... Rear Table 5 Dimensions reference figure 3 Model 2 25 2 26 2 30 2 31 2 35 2 36 2 45 2 46 2 55 2 56 2 75 2 76 2 95 2 96 Dimensions A1 Width overall 520 590 730 870 1080 1360 i Flue combustion air intake socket internal i 102 132 X Flue combustion air intake socket centres 140 225 Y Duct flange width front and back 360 620 570 710 920 1200 ...

Страница 6: ...ses are met taking into account the pressure resistance of the air heater as indicated in figure 2 When designing by pass ducts ensure that the requirements for service access flue and controls connections are maintained An adjustable damper should be included within by pass ducts to enable air flow pressure and volume to be adjusted after installation When fitting Euro T air heaters in a side by ...

Страница 7: ...0505T2D0GBEN 7 21 Figure 4 Arrangements for applying multi heater combinations ...

Страница 8: ...ng through all members 5 4 Checking alignment and joint worthiness 5 5 Applying gasket seals to prevent air leakage 5 6 Sectional view of completed joint Legend figure 5 6 1 Cut and assemble flange into frame to suit opening 6 2 Check dimensions and position on duct spigot 6 3 Ensuring flange is mated correctly before fastening 6 4 Checking location after positioning 6 5 Applying sealing gasket 6 ...

Страница 9: ...purposes The flue system must therefore be supported independently Where flue systems are taken through elements of air handling appliances then provision must be made to allow servicing of the flue gas fan assembly this will entail fitting a special detachable transfer section from the appliance flue and combustion air connection sockets to the outside of the appliance The main flue should then r...

Страница 10: ...m Flue terminal 3 0 m 4 7 3 To ensure that the allowable resistance is not exceeded in the case of horizontal runs of flues a positive rise from the air heater of 1E i e 17 mm per metre is recommended 4 7 4 If condensation is to be avoided flues should not pass through cold areas or not be installed externally 4 7 5 When mechanical ventilation is used it shall be by mechanical inlet with either me...

Страница 11: ...cal specification is in accordance with the specified data on the air heater A unique appliance wiring diagram is supplied as a separate document attached to this one plus a copy attached to the air heater 6 3 These appliances must be earthed 6 4 A separate electrical isolator for each heater must be provided adjacent to the appliance The isolator must have a contact separation of at least 3 0 mm ...

Страница 12: ...e the gas valve s will open and the burner will be lit 7 4 4 If the burner has not lit within 5 seconds the electronic flame relay will switch off and lockout will occur This will cause the signal lamp to glow within the reset push button on the appliance and or on a remote control if fitted After 10 seconds the reset button on the appliance or the remote control can be activated in order to reset...

Страница 13: ...nclude a service access section adjacent to the connection socket allowing access to the top of the flue fan In the event that the fan housing assembly requires removal i e for replacement then it is necessary to remove that section to access the 4 securing screws that fasten the fan housing through the top of the appliance All controls electrical and flue gas components are now accessible 8 5 2 F...

Страница 14: ...on the appliance in accordance with the step procedure described in section 7 7 2 of this document Fig 9 SERVICE ACCESS KEYS Fig 10 IGNITER ASSEMBLY Fig 11 REMOVAL OF COMBUSTION AIR FAN VENTER MOTOR FAN IMPELLER ASSEMBLY CRITICAL DIMENSIONS 8 15 TO REMOVE COMBUSTION AIR FAN 1 Disconnect electrical connections to fan motor 2 Remove motor and venter wheel 3 screws 3 Withdraw motor impeller assembly ...

Страница 15: ...d 1 Cable entry all electrical connections 2 Gas connection not supply line size 3 Combustion air fan with motor 4 Terminals for all electrical connections 5 Fuse 6 Double gas valve with pressure regulator 7 Hot surface igniter 8 Burner tray with burner ribbons 9 Manifold with injectors and pressure nipple 10 Reset button with indicator for burner lock out 11 Fan thermostat FCR 12 Not used for UK ...

Страница 16: ...02 mbar OFF 0 94 mbar except type 25 26 ON 0 76 mbar OFF 0 68 mbar No differential pressure in flue gas system check flue and air inlet Faulty combustion air fan or capacitor 9 5 Appliance does not provide sufficient warm air Check gas inlet pressure Check burner pressure Gas filter if fitted dirty or blocked Limit control LC1 switches burner off see 9 6 Differential pressure switches relay off se...

Страница 17: ... Honeywell C6065 FH1144 Models 2 25 26 Combustion circuit pressure switch 30 60607 94 Honeywell C6065 FH1194 Models except 2 25 26 Automatic burner control 03 25317 Honeywell S4570LS All Hot surface ignition assembly 05 25217 Norton 240V All Two pole relay K1 2 30 61742 240V Finder All two stage burners Wiring harness for burner control 06 41633 HGC Waak All Wiring connector for igniter device 06 ...

Страница 18: ...n of the gas burner must be carried out 11 2 A Reznor approved conversion kit to suit the appropriate gas type must be used 11 3 In addition to changing the burner injectors and adjusting the gas pressure sealing a governor or fitting a blanking plate it is necessary to fix over stickers as supplied with the conversion kit of parts 11 4 After conversion re commission appliance according to section...

Страница 19: ... Some people can suffer reddening and itching of the skin Fibre entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling People with a history of skin complaints may be susceptible to irritation Dust levels are only likely when the material is abraded In general normal handling and use for this...

Страница 20: ...t the heater 1 Turn on the gas supply to the air heater 2 Switch on the electricity supply to the air heater 3 Ensure time switch if fitted is set to a ON cycle 4 Adjust control room thermostat to desired temperature 5 Air heater will light automatically when the room thermostat calls for heat 6 If the appliance does not light a check that the burner control does not require resetting An indicator...

Страница 21: ... OPTIONAL ELECTRONIC CONTROL PANELS SAVE ENERGY AND OPTIMISE THERMAL COMFORT Reznor 7 Europe N V J M Sabbestraat 130 B8930 Menen Belgium Tel 32 0 56 52 95 11 Fax 32 0 56 52 95 33 e mail reznor_europe tnb com Reznor UK Limited Park Farm road Folkestone Kent CT19 5DR U K Tel 44 0 303 259141 Fax 44 0 303 850002 e mail sales reznor co uk ...

Отзывы: