ALARMS
ALARMS
Batview2-rev 01
Batview2-rev 01
UK
Set the Alarme mode
The device switches to Alarm mode when it de-
tects
4
An undervoltage fault on any one of the 4 sets
of batteries.
4
An overvoltage fault on any one of the 4 sets
of batteries.
4
A temperature fault on sets 1 or 2.
4
A low capacity fault on sets 1 or 2.
This mode is signalled by a flashing display indica-
ting the type of fault detected.
This mode results in the closure of an RCT dry loop
(terminals 1, 2, 3). The maximum switchable cur-
rent for the dry loop relay is 1A at 36V DC max.:
Return to “Normal” mode is automatic as soon as
the fault has disappeared.
Pressing “SET” allows you to momentarily return
(for 10 seconds) to “Normal” mode to allow you
to view various settings. If the fault persists, a re-
turn to “Alarm” mode is automatic.
Batteries 1 and 2
*ALARM* BAT(No.)
Vbat LO
Battery undervoltage alarm (No.)
*ALARM* BAT(No.)
Vbat HI
Battery overvoltage alarm (No.)
*ALARM* BAT(No.)
Temp HI
Battery temperature alarm (No.)
*ALARM* BAT(No.)
Capa LO
Battery low capacity alarm (No.)
*ALARM* BAT(No.)
CTN 1
T° sensor battery fault alarm (No.)
Batteries 3 and 4
*ALARM* BAT(No.)
Vbat low
Battery undervoltage alarm (No.)
*ALARM* BAT(No.)
Vbat high
Battery overvoltage alarm (No.)
BATVIEW2
Содержание BATVIEW 2
Страница 1: ...BATVIEW 2 State of charge controller D OPERATING AN USERS MANUAL 12V 24V Code REYA 399032 UK...
Страница 6: ...INSTALLATION Batview2 rev 01 Batview2 rev 01 INSTALLATION UK 1 SHUNT BATVIEW2 WIRING...
Страница 7: ...INSTALLATION Batview2 rev 01 Batview2 rev 01 INSTALLATION UK 2 SHUNTS BATVIEW2 WIRING...
Страница 10: ...USE USE Batview2 rev 01 Batview2 rev 01 UK...