3 Ratings and Dimensions
3.1 Fe UL Ratings and Dimensions in Common
Description
Symbol
Unit
Data
Listing according to UL standard (UL)
–
–
UL 508 C
UL files (UL)
–
–
NMMS.E328841
Enclosure
–
–
Open type
Pollution degree (UL)
–
–
2
Ambient temperature with nominal data (UL)
T
amax
°C
40
Ambient temperature with reduced nominal data
(UL)
T
amax_red
°C
50
Minimum distance on the top of the device
1)
d
top
mm
150
Minimum distance on the bottom of the device
2)
d
bot
mm
150
Horizontal spacing on the device
3)
d
hor
mm
50
Short circuit current rating (UL)
SCCR
Arms
5,000 (0K75...90K0)
42,000 (110K...160K)
Rated input voltage, power (UL)
4)
(TN-Net)
U
LN_nenn
VAC
3P 380...480
Tolerance rated input voltage (UL)
–
–
-15...+10 %
Input frequency (UL)
f
LN
Hz
50...60
Tolerance input frequency (UL)
–
Hz
± 5
Field wiring material
(material; conductor temperature; class)
–
–
Copper, 75 °C
Output voltage (UL)
U
out
V
Corresponding to input
voltage
Output frequency range (UL)
5)
f
out
Hz
0...650
Tab. 3-1: Fe UL ratings and dimensions in common
Bosch Rexroth AG
Ratings and Dimensions
DOK-RCON01-REX*F*UL***-IN10-EN-P
15/69
Содержание EFC3600 Series
Страница 17: ...Rexroth 60 15 Bosch Rexroth AG DOK RCON01 REX F UL IN10 EN P XV...
Страница 18: ...Bosch Rexroth AG XVI DOK RCON01 REX F UL IN10 EN P...
Страница 31: ...Fig 2 2 Type code Fv Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 11 69...
Страница 32: ...Fig 2 3 Type code EFC 3600 Bosch Rexroth AG Identification 12 69 DOK RCON01 REX F UL IN10 EN P...
Страница 33: ...Fig 2 4 Type code EFC x610 Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 13 69...
Страница 62: ...Fig 5 4 FVCA Block diagram Bosch Rexroth AG Instructions for Use 42 69 DOK RCON01 REX F UL IN10 EN P...
Страница 63: ...Fig 5 5 EFC 3600 Block diagram Bosch Rexroth AG Instructions for Use DOK RCON01 REX F UL IN10 EN P 43 69...
Страница 89: ...Notes Bosch Rexroth AG...