Existing Fireplace Preparation
A few points must be considered before inserting the RF24 into an existing
fi
replace cavity. Generally, modi
fi
cations
to the existing
fi
replace that will compromise its integrity are NOT allowed. Components that are bolted or screwed
on, such as dampers or baf
fl
es, may be removed to accommodate the installation of the RF24 engine.
Cutting
away any sheet metal parts off the existing
fi
replace to accommodate the installation of the RF24 is
prohibited
. Check with local authorities if in doubt.
Clean Fireplace and Chimney
Have the chimney swept and the
fi
replace cavity cleaned before installing the RF24 heater and vent liners. Any
creosote or soot residue remaining in the
fi
replace cavity or chimney may cause odors once the RF24 insert is
installed. Consult with chimney sweep for information on how best to clean.
Existing Dampers
Factory-built, zero clearance
fi
replaces will require the damper to be removed in order to install the vent liners.
These dampers are usually bolted into place. Dampers in masonry
fi
replaces must be
fi
xed open and may remain
in place.
Ash Retaining Curbs
Some
fi
replaces (particularly factory-built) have a raised curb at the front edge to retain ashes. Check the dimensions
carefully to ensure the RF24 engine will
fi
t behind any raised curb (some curbs may be removed separately from
the refractory base). The fret retainers allow for some vertical adjustment of the cast iron fret should the fret need
to sit on top of the curb, otherwise the fret will need to be eliminated or adequate room provided behind the curb.
Gas Line Routing
Plan the routing of the gas line before proceeding. Utilize the existing hole for the gas line. If the factory-built
fi
replace has no access hole, carefully drill an access hole of 1-1/2 inch (38 mm) or less through the lower sides
or bottom of the
fi
rebox. The access hole must be plugged with non-combustible insulation after the gas supply
line has been installed. See illustration in
Dimensions
section for detailed location of gas inlet. Also, take into
consideration whether or not a fan or shut-off valve will interfere when planning the routing of the gas line.
Existing Glass Doors and Wire Screens
Existing glass doors must be permanently removed
prior to installing the RF24 insert. Existing wire
fi
re screens
may remain in place or new ones may be added. The RF24 has been tested and approved to operate with wire
fi
re screens in the
closed
or
open
positions.
Combustible Mantels
Combustible mantel clearances must conform to those required for the original solid-fuel
fi
replace into which the
RF24 is being installed.
Paint Existing Refractory Liners
It may be desirable, for visual reasons, to paint the existing refractory liners in black to blend in with the RF24
insert once installed.
Attach Warning Label to Existing Fireplace
(label supplied loose with RF24 heater)
Attach the label “This
fi
replace has been converted...”
to the existing
fi
replace
using screws or other mechanical
means and store any removed parts in the back of the existing
fi
replace for future use.