© RESOL 11294 flo
wsol_d_d_he
.monen.ind
d
FlowSol D / D HE
| 12
11.2 Menu structure
The controller is operated and controlled via the menu.
During normal operation, the status is displayed.
1,8 bar
Pressure
500 l/h
Flow rate
18,4 kW
Power
System OK
P
V
Display
Description
Adjustment range
Factory setting
Balance/adjust. values
Max. pressure
maximum system pressure
Min. pressure
minimum system pressure
Max. s3
maximum temperature
store, top
Max. power
maximum power
heat
heat quantity
oper. hours R1
operating hours relay 1
oper. days
operating days
--adjust values:--
Date
Time
Tstmax
maximum store temperature
0 ... 90 °C
60 °C
D
Ton
switch-on difference
1,0 ... 25,0 K
5,0 K
D
Toff
switch-off difference
0,0 ... 24,0 K
3,0 K
D
Tset
set difference
2 ... 50 K
10 K
Relay mode
Off, Auto, Min., Max.
Auto
--expert:--
D
Tstmax
maximum store hysteresis
1,0 ... 10,0 K
2,0 K
Tstsec
store emergency shutdown tem-
perature
0 ... 95 °C
90 °C
D
Tstsec
store emergency shutdown
hysteresis
1,0 ... 10,0 K
2,0 K
Tcolsec
collector emergency shutdown
temperature
20 ... 180 °C
130 °C
D
Tcolsec
collector emergency shutdown
hysteresis
10 ... 50 K
10 K
collector cooling
Yes, No
Yes
Tcolmax
maximum collector temperature 10 ... 130 °C
110 °C
D
Tcolmax
maximum collector hysteresis
5,0 ... 20,0 K
5,0 K
collector minimal.
minimum collector function
Yes, No
No
Tcolmin
minimum collector temperature 0 ... 90 °C
10 °C
D
Tcolmin
minimum collector hysteresis
0,3 ... 10,0 K
2,0 K
Note:
The displayed values and options depend on the
functions and only appear if these are available
for the adjusted system parameters.