GB
MU1H-1239GE23 R0420
3
5.2 Maintenance
Do not use any cleansers that contain solvents and/or
alcohol for cleaning the plastic parts, because this can
cause damage to the plastic components - water
damage could result.
Detergents must not be allowed to enter the
environment or the sewerage system!
5.2.1 Cartridge insert
1.
Close shut-off valve on inlet
• Pressure in backflow preventer relieves
2.
Unscrew the plug
• Dismount punched plate in the outlet if necessary
3.
Remove strainer and clean it
4.
Remove cartridge insert and clean or exchange it
Exchange lip seal and filter
• push down the cartridge insert till it snaps in
CAUTION!
Don’t disassemble cartridge insert to individual
parts!
5.
Reinsert cartridge insert
6.
Reassemble in reverse order
7.
Test function (see 5.1 Inspection)
5.2.2 Check valve
1.
Close shut-off valve on inlet
• Pressure in backflow preventer relieves
2.
Exchange check valve
3.
Test function (see 5.1 Inspection)
6
Disposal
Observe the local requirements regarding correct waste
recycling/disposal!
7
Troubleshooting
8
Spare Parts
For Spare Parts visit homecomfort.resideo.com/europe
9
Accessories
For Accessories visit homecomfort.resideo.com/europe
Problem
Cause
Remedy
Discharge valve opens without apparent
reason
Pressure strokes in water supply system Install a pressure reducing valve
upstream the backflow preventer
Fluctuating inlet pressure
Install a pressure reducing valve
upstream the backflow preventer
Cartridge insert is contaminated
Remove cartridge insert and exchange it
Discharge valve don’t close
Deposits on valve seat
Remove cartridge insert and clean or
exchange it
Damaged ’o’ring
Remove cartridge insert and exchange it
Leaky discharge valve
Remove cartridge insert and clean or
exchange it
Flow is too low
Inlet strainer is blocked
Remove strainer and clean it