DCN: 141-00930-07 09/06/04
5
display will come on when the manual fan is ON. Changes in the fan mode will be sent to the HVAC Control
Unit.
Setup Mode
The TR16 has a new setup mode to allow the user to set the following functions from the WDU:
•
Serial Network Address
•
F/C mode
•
Sensor Calibration
Entering into the setup mode.
Enter the setup mode by the following procedure:
1. First press and hold the Mode button
2. Simultaneously press the Fan button.
3. The display will change to show “SU”.
4. Release all buttons.
5. The display will change to show the setup menu, starting with “Ad” (address)
6. Select what setup function you want to change or view by pressing the Mode button to cycle
through the menu options:
“Ad” Serial Network address
“FC” Fahrenheit or Celsius mode
“C1” Calibrate Internal Sensor (or Remote Sensor address 1 if attached)
and if additional external sensors are attached they will appear also:
“C2” (if Remote Sensor address 2 attached)
“C4” (if Remote Sensor address 4 attached)
Setting the Address
When you first enter the setup mode, the first menu selection displayed on the LCD display is “Ad”. To view
the current address setting, press the UP or DOWN button once. With the current address displayed, you
can either change the setting or exit by pressing the mode button or wait for the screen to time out. If you
want to change the address, while the current address is being displayed, use the UP/Down buttons to
select the serial address desired, 1 to 99. (default set to 1)
Setting the Fahrenheit or Celsius mode
In the setup mode, press the mode button to select “FC” mode. Press the UP/DOWN buttons to select F or
C mode desired. To exit press mode again to move another setup mode or wait for the screen to time out and
return to thermostat mode.
Setting the Sensor Calibration
In the setup mode, press the mode button to display the sensor calibration address, “C1”, to be calibrated.
”C1” is the internal sensor and normally that is all that will be available to calibrate unless external remote
sensors are attached. These will show up as “C2”, and “C4” in the menu selection, if present. With the
desired sensor address displayed, press the UP/DOWN buttons to change the sensor calibration to the
desired temperature. See calibration explanation below.
Exit setup mode
When you are done making changes and no button is pressed for 3 seconds, the display will automatically
exit setup mode and return to the thermostat mode and current temperature display.
Temperature Display Calibration