DCN: 141-00930-07 09/06/04
6
The TS16 WDU has the capability for the user to adjust the temperature display calibration of the internal
sensor as well as all attached remote sensors from the WDU in the setup mode.
Normally the TS16, with no attached remote sensors, will only show the internal sensor as “C1” in the
calibration setup menu. The TS16 can have additional remote sensors attached. These are addressed as
remote sensors 1 to 4. If they are detected by the TS16, they will show up in the calibration menu as
additional sensors to calibrate as C2, C3 and C4. Note that if remote sensor with address 1 is attached it
replaces the internal sensor and is becomes the “C1” sensor. See the remote sensor section for more
details.
When the desired sensor is selected in the setup menu, you can adjust its displayed temperature calibration
up or down 7 degrees by pressing the UP/DOWN buttons.
The calibration menu selections are:
C1 = calibrate internal sensor or remote sensor address 1 if attached
C2 = calibrate remote sensor address 2 (only shows up in menu if attached)
C4 = calibrate remote sensor address 4 (only shows up in menu if attached)
Remote Sensors
The TS16 Wall Display Unit has a remote sensor terminal block, J2, on the base for connection of a remote
temperature sensor. Remote sensors have an address that can be set to 1, 2, or 4. Without any remote
sensor attached, the WDU uses the internal sensor for the current temperature information. When a remote
sensor is attached, the WDU will detect it
automatically
and will use the remote sensor(s) according to its
address selection. Modes of operation are as follows:
Address 1: Use this remote sensor instead of the internal sensor. (becomes C1 in the calibration setup).
Address 2: Average remote sensor 2 with internal sensor or sensor address 1 if attached. (C2)
Address 3: Not used on TS16 wall display units
Address 4: This remote sensor address is only for an
outside
temperature sensor. (C4)
Table of Remote Sensor Functions and Sensor Addresses
Function
Remote Addr 1
Remote Addr 2
Remote Addr 3
Remote Adrr 4
Use internal sensor only
No
Yes
Not used
*
Used as remote sensor only
Yes
No
Not used
*
Average internal and one remote
No
Yes
Not used
*
Average two remotes (only 2)
Optional with A2
Yes with A1
Not used
*
Outside temp display on WDU
NA
NA
NA
Yes
* optional outside temp sensor can be used with any other sensor address.
When averaging sensors are used, the
average
temperature is displayed on the WDU and reported to the
HVAC control unit. You cannot view an individual remote averaging sensor temperatures as the main
thermostat display or report individual sensor temperatures on the communication port. However, you can
check the individual sensor temperatures by going to the calibration setup menu and selecting the sensor
address. You can view the outside temperature by pressing both the UP/DOWN buttons simultaneously.
Display Lock
The TR16 WDU control buttons can be locked to prevent unauthorized changes in system operation from
the WDU. The display lock/unlock state can only be set by the “DL” network command. See the Serial
Protocol Manual.