REOVIB MFS 268
Operating Instructions
EtherNet/IP - Programming
5
2.0 Interface operation (EtherNet-IP )
Bus Power Supply
24 V, DC, 250 mA
Bus connector
2 x RJ-45
Internal interface
CAN-Bus
Supported baud rates
1000 kBaud
Communication
Data consistency required
Protocol
EtherNet-IP
3.0 Activate interface
For the interface version parameter “CAN” is set to “I”. Then communication through the interface is pos-
sible. If manual control of the unit should be required e.g. for testing, this parameter must firstly be set
back to "0” again.
Important: The parameter “Ad.” must be set to “1” and the baud rate must be set to “b 1000”.
Code 017
0 = interface off
I = interface on
P
P
running mode
P
P
P
P
P
P
4.0 EDS-File
Following EDS-File is required for the operation with the EtherNet-IP interface:
EDS File Name:
UNIGATE IC-EI 2Port.eds
The EDS-file is supplied on a CD with each new unit or alternatively, visit
www.reo.de
to download
the file from the website.
5.0 Bus operating modes
Two fundamental operating modes can be chosen for bus communication.
Normal Operation:
Control of the frequency controller in production, in which case the Set point and
ON/OFF control signals are transmitted
Parameter Operation:
Adjustment of the frequency controller for the desired operation mode and limits.
In a special mode the parameter and parameter addresses are transmitted and
acknowledged.
In parameter operation, the unit’s specific values, such as frequency, soft start
time, timers and switching etc., are set.