MFS_268_EtherNetIP_appendix_rev03.en
02.08.2016
REOVIB
Control Equipment for the Vibratory Feeder Industry
MFS 268
Frequency Converter for Vibratory Feeders
Appendix: EtherNet-IP - Programming
Страница 1: ...MFS_268_EtherNetIP_appendix_rev03 en 02 08 2016 REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders Appendix EtherNet IP Programming ...
Страница 2: ...uctions are provided for the personal safety of operators and also for the protection of the described product and connected equipment Warning Hazardous Voltage Failure to observe can kill cause serious injury or damage Isolate from mains before installation or dismantling work as well as for fuse changes or post installa tion modifications Observe the prescribed accident prevention and safety rul...
Страница 3: ...2 Reply from Controller 6 5 2 Parameter Operation 7 5 2 1 Creating parameter addresses and values 7 5 2 2 Send Write Enable 7 5 2 3 Receive Acknowledge Write Enable 8 5 2 4 Send Parameter 8 5 2 5 Close write enable 9 5 2 6 Parameter read send 9 6 0 Parameter Table 10 7 0 Example of bus communication with Frequency controller 12 7 1 Normal mode 12 7 2 Parameter mode 12 7 3 RESET Controller 14 8 0 M...
Страница 4: ...livery 24V DC switch reset IP input EIP output EIP LED I blinks during active internal communication green LED EtherNet ok yellow LED Bus error green LED EtherNet ok yellow LED status LED The interface enables communication with the frequency converter using 4 data words i e 16 Bits The four 16 Bit words are transmitted and acknowledged every bus cycle Important Data consistence is required to ope...
Страница 5: ...interface on P P running mode P P P P P P 4 0 EDS File Following EDS File is required for the operation with the EtherNet IP interface EDS File Name UNIGATE IC EI 2Port eds The EDS file is supplied on a CD with each new unit or alternatively visit www reo de to download the file from the website 5 0 Bus operating modes Two fundamental operating modes can be chosen for bus communication Normal Oper...
Страница 6: ... MUST be set to 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Mode bit 0 0 0 0 0 0 0 0 0 0 0 0 0 Enable 0 0 Control information unit specific 5 1 2 Reply from Controller H Byte L Byte Word 1 xxxx H undefined 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 H Byte L Byte Word 2 only in regulation mode Feed back actual acceleration 16 Bit 100 8000H 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 H Byte L Byte Word 3 Feed ba...
Страница 7: ...rite and 0 read this should be accompanied by the corresponding parameter address The mode bit msb in Word 3 is used to select normal or parameter operation 0 Normal or 1 pa rameter operation Word 1 reserved 0000 H Word 2 R W Bit Address e g 8000 H 1009 H 9009 H Word 3 Value of the parameters e g 7FFF H Word 4 Mode bit 1 Control bit s e g 8000 H 0004 H 9004 H 5 2 2 Send Write Enable H Byte L Byte ...
Страница 8: ...t 0 FFFF H 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 R W Parameter address H Byte L Byte Word 3 Parameter value 16 Bit 0 FFFF H XX XX H Byte L Byte Word 4 Control Word 8000H Mode must be set to 1 All unused bits must be set to 0 Bit 1 Function ON 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 Mode bit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Control Information unit specific Received acknowledge H Byte L Byte Word 1 xxxx...
Страница 9: ... 0 0 0 0 0 0 0 Control Information unit specific 5 2 6 Parameter read send H Byte L Byte Wort d xxxx H undefined 00 00 H Byte L Byte Word 2 Parameter address R W Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 R W Parameter address H Byte L Byte Word 3 Read Enable Value 0000 00 00 H Byte L Byte Word 4 Mode bit 1 Control bits 80 00 Received parameter H Byte L Byte Word 1 xxxx H undefined 00 00 H Byte L B...
Страница 10: ...y relay 0 I r b 0 003 0x583D 0x0000 0x FFFF Regulation with sensor Switch to regulation 0 I ACC 0 008 0x5808 0x0000 0x FFFF P characteristic 0 100 P A 40 008 0x100F 0x0000 0xFFFF I characteristic 0 100 I A 100 008 0x1014 0x0000 0xFFFF Automatic frequency control 0 I A F C 0 008 0x5809 0x0000 0x FFFF Start automatic frequency search start A F S 008 0x1400 0x0AF5 Track control Switch on time delay 0...
Страница 11: ...ent limit 0 100 I 100 040 0x1016 0x0000 0x8000 H Stop at current limit 0 I E F u 0 040 0x5850 0x0000 0x FFFF Current regulator P part 1 100 I P 20 040 0x100D 0x0000 0xFFFF Current regulator I part 1 100 I I 40 040 0x1032 0x0000 0xFFFF Min frequency limit 5 150 Hz F L 35 040 0x1020 01F4 7530 H 500 30000 dec Max frequency limit 5 150 Hz F H 140 040 0x1021 01F4 7530 H 500 30000 dec Start level AFC 0 ...
Страница 12: ... 0000 H 2 C0DE H Write enable Address C0DE H Acknowledge 3 B5E7 H Write enable value B5E7 H Acknowledge 4 8000 H Control bits Set mode bit 1 C0DE H Acknowledge Write parameter 1 0000 H 0000 H 2 9005 H Parameter address Vibrating frequency R W Bit 9005 H Acknowledge 3 1388H Frequency 50 Hz 1388 H Acknowledge 50 Hz 4 8000 H Control bits Set mode bit 1 C0DE H Acknowledge Write parameter 1 0000 H 0000...
Страница 13: ...811 H Acknowledge 3 FFFF H new Parameter FFFF H Acknowledge 4 8000 H Control bits Set mode bit 1 C0DE H Acknowledge Close Write enable Word Code send Code Received 1 0000 H 0000 H 2 C0DE H Write Enable Address C0DE H Acknowledge 3 0000 H Write Enable Value 0000 H Acknowledge 4 8000 H Control bits Set mode bit 1 C0DE H Acknowledge Read only the parameter Read Word Code send Code Received 1 0000 H 0...
Страница 14: ...H 2 C0DE H Write Enable Address C0DE H Acknowledge 3 B5C9 H Write Enable Value B5C9 H Acknowledge 4 8000 H Control bits Set mode bit 1 C0DE H Acknowledge Write Parameter 1 0000 H 0000 H 2 9400 H Parameter address Reset R W Bit 0000 H Acknowledge 3 C009 H RESET 0000 H 4 8000 H Control bits Set mode bit 1 C0DE H Allow approximately 0 5 sec for RESET ...
Страница 15: ...is switch longer than five seconds the device is set into the original state IP address 0 0 0 0 and DHCP is set on 8 1 Web server You can call up an HTML page with the help of our web server There are shown system parameters of the device on this page If the subnet mask of your PC doesn t correspond with the subnet mask of the device you proceed in the following way 1 You open the control panel 2 ...
Страница 16: ... you double click on Internet Protocol Version 4 TCP IPv4 6 Then you set the subnet mask at 255 255 240 0 7 You click on OK 8 Then you open the web browser e g the Internet Explorer 9 You enter the following IP address 192 168 11 182 as address 10 Then you click on IP Set ...
Страница 17: ... choose Network Settings in the menu Tools 4 You enter the subnet mask 5 The Gateway address Primary and or Secondary DNS address and Domain Name are optional 6 Choose the appropriate module 7 Click on Add to Relation List The New Entry dialog box appears 8 Enter an IP address host name and description for the module 9 Click on OK 10 You wait until the module appears in the Relation List Then you ...
Страница 18: ...REOVIB MFS 268 Operating Instructions EtherNet IP Programming 18 ...
Страница 19: ...REOVIB MFS 268 Operating Instructions EtherNet IP Programming 19 ...
Страница 20: ... 703 Warszawa Tel 48 0 22 812 3066 Fax 48 0 22 815 6906 E Mail croma croma com pl Internet www croma com pl Spain REO ESPAÑA 2002 S A C Manuel Ventura i Campeny 21B local 9 E 08339 Vilassar de Dalt Barcelona Tel 34 937 509 994 Fax 34 937 509 995 E Mail info reospain com Internet www reospain com Switzerland REO ELEKTRONIK AG Im Halbiacker 5a CH 8352 Elsau Tel 41 0 52 363 2820 Fax 41 0 52 363 1241 ...