background image

1.800.627.4499

Premium Commercial Controls

ERV

104

SYSTEM MONITORING

12.5.2 Alarms
Individual alarms are mapped to Binary Inputs 500 and above. Two general alarms are available: 

u

  Serious Alarm: Located at Binary Input 17, “Alarm_Out.val” indicates whether there is a  

    serious alarm that stops the unit. 

u

  Any Alarm: Located at Binary Input 72, “Any_Alarm_Out.val” indicates whether there is any  

    alarm present.
To reset the User Reset type alarms, set Binary Value 12 “AlarmMng.AlrmResByBMS” to true. 
The program will set it back to false. You can view the status change through Binary Input 14 
“AlarmMng.AlrmRes.”  

12.5.3 Temperature and Humidity Around the ERV
The following are available: 

u

  Analog Input 0 “OA_Temp.Val” 

u

  Analog Input 1 “OA_Hum.Val” 

u

  Analog Input 2 “RA_Temp.Val” 

u

  Analog Input 3 “RA_Hum.Val” 

u

  Analog Input 4 “EA_Temp.Val” 

u

  Analog Input 5 “SA_Temp.Val”

EA

OA

RA

SA

CA

UNITSTATUS_BN: MULTISTATE INPUT 7

VALUE

STATUS

MEANING

1

Unit on

The unit is on and running.

2

Unit switched off due to 
alarm  

The unit is off by a serious alarm.

3

Unit switched off by BMS

The unit is off by command from the BMS.

4

Unit switched off by time 
band

The unit is off by the scheduler.

5

Unit switched off by digital 
input

The unit is off due to contacts across 17 and 18 open.

6

Unit switched off from the 
local keypad

The unit is off by the setting on the menu screen.

8

Exhaust Fan Only Mode

The unit is in single fan mode with exhaust fan 
running.

9

Supply Fan Only Mode

The unit is in single fan mode with supply fan running.

11

Cool Locked Out by BMS

A BMS command has the cooling locked out.

12

Heat Locked Out by BMS

A BMS command has the heating locked out.

13

Device Test

The system is in device test mode for more than an 
hour.

14

Sens Ovrd Active

The system has a sensor overwritten for more than  
24 hours.

15

Off by CO2 Level

Off by CO2 Level.

16

Frost Control On

Frost Control Mode Active.

Содержание EV450

Страница 1: ...Carel c pCO Mini Carel c pCOe Expansion Board PREMIUM COMMERCIAL CONTROLS Installation Operation and Maintenance Manual FOR EV450 HE Series LE Series and RD Series Units...

Страница 2: ...rgy recovery ventilator ERV units with Premium controls version 3 xx xx For previous versions refer to the older manual The version number can be seen on the splash screen when the unit power is cycle...

Страница 3: ...of the controller and all connected devices IMPORTANT This controller is only for use in protected environments It is not to be exposed to the weather or exposed to extremes in temperature IMPORTANT...

Страница 4: ...rnal memory a backup file should be created on an external memory device and stored in some convenient place READ AND SAVE THIS MANUAL LIRE ET CONSERVER CE MANUEL NOTE This page is to be completed by...

Страница 5: ...low Control Codes for Bypass Face damper also acts as Isolation Damper in EA or RA Airstream Restrictions 1 Orientation Code C not available with models EV450 HE 6X HE 8X HE1 5 2 Voltage Codes 1 9 onl...

Страница 6: ...n 33 5 2 6 CO2 Flow Control Option 34 5 3 OPTIONS FOR EXHAUST FAN CONTROL 34 5 3 1 Constant Fan Speed Option 34 5 3 2 EA Flow Control Option 35 5 3 3 Supply Fan Command Tracking Control Option 35 5 3...

Страница 7: ...Restore 83 9 3 4 Can Not See Device via IP Connection 83 9 4 TESTING FUNCTIONS IN GENERAL 84 9 5 RESTORE PARAMETERS SETTING 84 9 5 1 User Commissioning Settings Service 84 TABLE OF CONTENTS 9 5 2 Rest...

Страница 8: ...RY WRITES 118 13 4 ALARM INITIALIZATION 118 13 5 MEMORY WIPE 119 13 6 COMMUNICATION TO EXPANSION MODULE 119 14 0 MAINTENANCE RECORDS 120 14 1 UNIT START UP CONDITIONS 120 14 1 1 Setpoints 120 14 1 2 O...

Страница 9: ...2 3 Pressure Differential Transmitter typ 25 Figure 4 2 4 Electrical Pressure Differential Transmitter 25 Figure 5 1 0 Smoke Detector 28 Figure 5 1 1 Motion Sensor Ceiling Mount 28 Figure 5 1 2 Motion...

Страница 10: ...dded u Single fan operation with digital input or BMS command 4 Supply and Exhaust Fan status via current sensors 5 Monitoring of these values u Outdoor Air OA Temperature u Outdoor Air OA Relative Hu...

Страница 11: ...is used in this manual The airstreams are defined as u Outside Air OA Air taken from the external atmosphere and therefore not previously circulated through the system Each ERV unit has an OA air inl...

Страница 12: ...One at the entering RA duct of the unit If a unit has heating and or cooling there is also a fifth CA sensor that is included but needs to be installed down the duct past the heating and cooling Humi...

Страница 13: ...and Motion Detector These items are all accessories and are field installed EA FAN AND SA FAN CURRENT SWITCHES MERV 13 FILTER OPTIONAL CORE AIRFLOW PRESSURE SENSORS TEMPERATURE AND HUMIDITY SENSORS T...

Страница 14: ...UT remote display 4 Remote display or BMS connection 5 Relay digital outputs 6 5V power supply 7 FBUS connection to expansion module 8 Analog outputs 9 Digital inputs 10 Ethernet port 11 Micro USB por...

Страница 15: ...ddress Ext Baud Prot 1 2 3 4 5 FIGURE 2 0 2 EXPANSION MODULE DETAIL 1 24VAC Power 2 Universal inputs outputs 3 Relay digital outputs 4 Serial connector to main controller 5 Dip switches NOTE Expansion...

Страница 16: ...screens of alarms Pressing and holding the Alarm button for three seconds resets the alarms When a menu or menu item has been highlighted press the ENTER hard button to enter the highlighted selection...

Страница 17: ...an RUT is also desired contact the factory for further information 2 1 2 Connecting Using Internal Web Pages The controller has embedded web pages and when they are accessed an interactive screen app...

Страница 18: ...screens click on RUT on the Menu Bar 2 1 3 Setting the PC IP Address For those that are not familiar with changing their PC adapter settings go into Network Setting in the Control Panel and Change Ad...

Страница 19: ...et to system menus CONTROLLER OVERVIEW NOTE When you are finished viewing the controller on your computer remember to restore the original settings 2 2 CONTROLLER MENU STRUCTURE Any screen will have t...

Страница 20: ...ed for troubleshooting u Advanced Service Advanced Service Information and Settings 2 2 3 Password Entry To access the password protected service screens press the program bullseye button to get to th...

Страница 21: ...the display to the current controller time and date u Change the Time ad Date accordingly Day is automatically generated 4 1 2 Setting the Unit of Measure The controller supports the following settin...

Страница 22: ...al Days 4 2 VERIFY UNIT CONFIGURATION 4 2 1 Main Unit Configuration It is important to verify the configuration as the settings on these screens will also determine which screens show up in the user s...

Страница 23: ...d with the unit but will have to be placed in the duct The sensor may also be included with heating units purchased from RenewAire 4 2 3 Field Installed Sensors and General Wiring All sensors are wire...

Страница 24: ...the level of CO2 in the space or duct These sensors provide a 0 10VDC signal scaled as specified in the CO2 scaling screen FIGURE 4 2 1 CO2 SENSOR DUCT MOUNT SIDE VIEW FIGURE 4 2 2 CO2 SENSOR WALL MOU...

Страница 25: ...essure These sensors provide a 0 10VDC signal scaled as specified in the Duct Pressure scaling screen FIGURE 4 2 3 PRESSURE DIFFERENTIAL TRANSMITTER TYP FIGURE 4 2 4 ELECTRICAL PRESSURE DIFFERENTIAL T...

Страница 26: ...oling The sensor uses a special curve and cannot be swapped with standard T2 or T3 NTC sensors UNIT CONFIGURATION NOTE When wiring sensor do not wire directly to the expansion module wire to the X3 te...

Страница 27: ...within the scheduler ON time if scheduler enabled u The BMS has written the unit on signal if BMS control is enabled Upon starting the isolation dampers will open The end switches of these dampers wi...

Страница 28: ...mand has the heating locked out Device Test The system is in device test mode for more than an hour Sens Ovrd Active The system has a sensor overwritten for more than 24 hours Off by CO2 Level The CO2...

Страница 29: ...n consult the unit specific IOM 5 1 3 Fans The variable speed fans may be driven by VFDs or may be ECM fans The VFD fans get an enable signal and both types of fans get a 0 10VDC signal which is propo...

Страница 30: ...starts this screen will show when the fans are enabled There is a slight delay of a few seconds and then the second line supply or exhaust fan on shows the status of the current sensor The current se...

Страница 31: ...re control CO2 control VOC control or CO2 Flow control Available modes may depend on the sensors added 5 2 1 Constant Fan Speed Option The analog voltage command to the supply fan VFD or ECM can be se...

Страница 32: ...etpoint This option requires a field installed duct pressure transmitter and setup for the transmitter in the I O configuration The SA duct static pressure setpoint is entered and adjusted from the un...

Страница 33: ...cent area or outdoors 5 2 5 CO2 VOC Control Option The controller will adjust the supply fan VFD or ECM command to maintain the room or RA CO2 or VOC level at a setpoint This option requires a field i...

Страница 34: ...aled If the measured CO2 level exceeds 1000 ppm adjustable for more than 60 seconds adjustable a CO2 alarm will be set to true This supply fan operation mode can be used to provide demand controlled v...

Страница 35: ...y or provided by the BMS The minimum and maximum values for EA flow rate setpoint are unit dependent An adjustable PI loop will compare the measured EA flow to the airflow rate setpoint and adjust the...

Страница 36: ...VFD or ECM command to track the supply fan air flow rate The offset from the SA flow rate is adjustable from 25 to 25 An adjustable PI loop will compare the measured EA flow to the airflow rate setpo...

Страница 37: ...from running when the Outdoor Air temperature is above the Lockout Above setpoint This causes the ERV unit to use energy recovery from the RA for heating instead of firing the heat module The Lockout...

Страница 38: ...etpoint type and a control type Setpoint types available u Adjust If you choose this it will allow you to set a heating setpoint u OA Reset You are prompted to set a reset schedule In the screen shown...

Страница 39: ...e mode is determined by the outdoor temperature and the heating lockout temperature settings This type of heating will modulate gas or electric heat using PI control The KP and Ti can be adjusted to f...

Страница 40: ...can be adjusted to fine tune the control The setpoint is also set here if set for Adjust The NO1 heating enable contact is engaged whenever the heating output is at 99 or lower NOTE The valve control...

Страница 41: ...ut temperature settings This type of heating cycles one stage of heating to maintain the heating setpoint You must set a hysteresis value whereby the stage will turn on at the setpoint hysteresis and...

Страница 42: ...than the OA temperature Unit OFF Unit is off 6 2 3 4 Two Stage Heater The mode is determined by the outdoor temperature and the heating lockout temperature settings This type of heating cycles two sta...

Страница 43: ...default settings stage 1 turns on at 75 2 1 74 2 Stage 2 turns on at 75 2 3 72 2 The heating status can be monitored in the Unit Status The screen shows u Heating Control Variable which will be as se...

Страница 44: ...h down the duct to prevent over cycling u RA If you are only feeding one space this is a useful control method 6 3 3 Cooling Types The following cooling types are supported u On Off one stage DX or he...

Страница 45: ...PERING CONTROL This type of cooling cycles one stage of cooling to maintain the cooling setpoint You must set a hysteresis value whereby the stage will turn on at the setpoint hysteresis and turn at s...

Страница 46: ...ed by the outdoor temperature and the cooling lockout temperature settings This type of cooling turns cycles two stages of cooling to maintain the cooling setpoint You must set a prop band value This...

Страница 47: ...ON u Cooling demand expressed as a percentage of proportional band u Cooling Status Stage 1 turns on a 25 and Stage 2 at 75 of prop band Stage 2 turns off at 25 and Stage 1 at 0 of prop band Proportio...

Страница 48: ...t is at 1 or higher The cooling status can be monitored in the Unit Status The screen shows u Cooling Control Variable which will be supply or return air as selected u Cooling setpoint u Whether cooli...

Страница 49: ...s type requires cooling type On Off and heating type On Off These type settings are made in the Control Settings 6 4 1 1 Heat Pump 1 Stage Mode The mode is determined by the outdoor temperature and th...

Страница 50: ...to use axillary heat when the OA is below a certain temperature You must set a hysteresis value whereby the stage will turn on at the setpoint hysteresis and turn at setpoint There is also a minimum o...

Страница 51: ...r the PI loop if necessary 6 4 1 5 Heat Pump 1 Stage Reversing Valve The reversing valve controls which direction the refrigerant flows On change of mode i e cool to heat there will be a delay before...

Страница 52: ...may be true 6 4 2 Heat Pump 2 Stage with or without 0 10VDC Aux Heat This type requires cooling type 2 stage and heating type HP 2 Stage 6 4 2 1 Heat Pump 2 Stage Mode The mode is determined by the ou...

Страница 53: ...4 2 3 Heat Pump 2 Stage Heating Operation This type of cooling cycles two stages of heating to maintain the heating setpoint You must set a prop band value This value represents 100 the wider the pro...

Страница 54: ...ol to heat there will be a delay before the compressor turns on to allow the valve to come into position Reversing valve settings u Delay This is the delay between the heating and cooling changeover w...

Страница 55: ...OA The heating OA lockout is higher than the OA temperature Lockout Overlap The OA lockouts for heating and cooling overlap No vent mode The heating takes preference Econ Only If economizer is open le...

Страница 56: ...4 cooling enable contact is engaged whenever the cooling demand is at 1 or higher 6 4 3 3 VRF Heating Operation This type of heating modulates a 0 10VDC output using PI control to maintain the heating...

Страница 57: ...dual temperature coil is a coil which provides heating in the winter and cooling in the summer by changing the temperature of the fluid in the coil To do this the coil needs to know what type of fluid...

Страница 58: ...int The KP and Ti can be adjusted to fine tune the control The NO4 cooling enable contact is engaged whenever the cooling demand is at 1 or higher 6 4 4 3 Dual Temperature Coil Heating Operation This...

Страница 59: ...at BMS is setting the mode to heat No cooling is allowed BMS Mode set to Cool BMS is setting the mode to cool No heating is allowed IN HEAT MODE Valve is positioned for heat mode IN COOL MODE Valve is...

Страница 60: ...ust air temperature is below the EA Below set point For variable speed fans an additional setting is required for the exhaust fan operation While the supply fan is off a variable speed exhaust fan ECM...

Страница 61: ...External Temp and Humidity Sensor from OA to RA 4 5 5 2020 austine Added Any Alarm Output 5 5 8 2020 austine Updated Ground Locations 6 4 4 2022 shreyat Updated controller gnd connections 3 DN 2 3 Jxx...

Страница 62: ...at the same percentage that the first turned on and the first turns off at setpoint If you set Specify Off Values to YES it will turn them off at the values specified 7 5 ADJUSTMENTS FOR TWO STAGE CO...

Страница 63: ...ion screen You can also set whether the fans will run to a specified or CFM 7 7 FLUSH FEATURE Depending upon the last setting you will se either one of these screens to allow you to define how the fan...

Страница 64: ...CALIBRATING I O For a temperature sensor that may have run a long distance or a humidity sensor with a reading that may have drifted over time a calibration may be necessary There is a screen such as...

Страница 65: ...n EA Temperature CAREL NTC Red or White U6 Main Red or White GND Main OA Filter Pressure 0 10VDC Vin Red 24VAC TS1 GND Black GND TS2 Vo White U7 Main RA Filter Pressure 0 10VDC Vin Red 24VAC TS1 GND B...

Страница 66: ...ALS CONTROLLER TERMINALS Smoke Detector Dry Contact X2 15 C1 2 X2 16 24VDC ID1 Unit Enable Dry Contact X2 17 ID1 X2 18 Sensor COM ID2 Single Fan Mode Dry Contact X2 19 ID2 X2 18 Sensor COM SF Current...

Страница 67: ...Dry Contact X1 10 NO2 EXP X1 08 C1 2 EXP Tempering Mode Dry Contact X4 32 NO3 EXP X4 35 C3 4 5 Cooling Enable 1 Dry Contact X4 33 NO4 EXP X4 35 C3 4 5 Cooling Enable 2 Dry Contact X4 34 NO5 EXP X4 35...

Страница 68: ...NALS CONTROLLER TERMINALS SF Signal 0 10VDC 01 6 D Y1 Main 01 2 D GND EF Signal 0 10VDC 01 4 D Y2 Main 01 2 D GND Cooling Command 0 10VDC X3 29 Black U9 EXP X4 31 Sensor COM Heating Command 0 10VDC Se...

Страница 69: ...ase 460 VAC 3 Phase Transformer COM 24V F1 Contactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Supply Contactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Exhaust Transformer COM 24...

Страница 70: ...Current Red SF Current Red EF Current Red EF Current Red Not Used NO3 4 5 Blk X1 3 NO3 4 5 Wht X1 5 ID1 2 GND Red ID1 2 GND Wht X2 17 X2 19 X2 18 NO1 2 C Blk X2 15 NO1 2 C Wht X2 11 NO1 2 C Red X2 13...

Страница 71: ...6 7 8 9 10 11 12 13 X3 21 X3 24 X3 23 X3 22 X3 30 X3 29 X3 28 X3 27 X3 26 X3 25 Sensor 24 VAC NO 4 Accy COM Accy COM Accy 24 VAC X1 4 X1 3 X1 2 X1 1 EFEN1 UE1 SD1 Factory Jumper NO 3 Accy COM X1 7 X1...

Страница 72: ...est End Device feature in the service level See the following Test End Devices section for this In other cases problems may be caused by the air handler trying to overcome a pre set or operating param...

Страница 73: ...the User Reset alarms The auto reset alarms reset themselves 9 1 4 Alarm Digital Outputs The controller includes a digital output for remote indication of an alarm condition The first is AlarmOut val...

Страница 74: ...s Failure to correct this could result in damage to the controller Alarm Number 1 Error in retain memory writings This usually means indicates that the BMS is writing to a retained setpoint too often...

Страница 75: ...r this alarm is set here The setting is shared with the exhaust fan Whether the unit shuts down if this alarm occurs is also set here Alarm Number 11 Exhaust Fan Alarm This indicates that either the e...

Страница 76: ...Shutdown 20 Al_VOC User Reset VOC Alarm 21 Al_EA_StaticPress Auto reset EA Static Pressure Level Alarm Alarm Number 12 Supply Airflow Alarm This alarm occurs when the supply is set to control on supp...

Страница 77: ...sure or the exhaust fan is set to control on return static pressure It indicates that the pressure measured is out of tolerance set here for more than the alarm delay set here If the sensor is reading...

Страница 78: ...t First view the sensor value in Unit Status If it seems OK then check the alarm levels set here Only one will show depending upon whether you have a Unit Supply Temp Sensor The difference in the two...

Страница 79: ...Pressure Transducer Alarm 38 Al_OA_Flow_Rate_ Prb Auto reset OA Flow Rate Sensor Error 39 Al_EA_Flow_Rate_ Prb Auto reset EA Flow Rate Sensor Error 40 Al_CO2_Level_Prb Auto reset CO2 Sensor Error 41 A...

Страница 80: ...active verify that the reading is as expected in the Unit Status If not check that someone has not changed the pressure transducer range in the I O Configuration Also check the offset or override for...

Страница 81: ...re you cycle power to end test mode and put all values back to zero 9 2 1 Supply or Exhaust Fan Alarm Troubleshooting These alarms 10 and 11 mean that either the fan did not start or that the current...

Страница 82: ...can try to adjust it below Adjusting the Current Switch With the dampers open and the fans enabled as described in the Test End Devices mode above set the fan for which you want to calibrate to the m...

Страница 83: ...rent mode is heat u BMS Heat Lockout This means that BMS Heat Cool Mode Is set to Yes in General Settings and the current mode is cool u In Device Test Mode in Test End Devices is enabled Cycle power...

Страница 84: ...vels of settings in the controller Some are set by the factory and some are set be users These parameters include all configuration settings fan settings heat cool settings and BMS settings 9 5 1 User...

Страница 85: ...t These are somewhat specific settings but going back to these settings will require you to perform start up and commissioning again To return to factory defaults u Choose internal u Set Confirm to YE...

Страница 86: ...onnection was interrupted Input parameter value is not valid The file may not be compatible with the program If the unit does not confirm that the operation was done the controller may have been older...

Страница 87: ...thods at the same time If you are viewing the web pages and then connect with USB the web page will go blank until you disconnect The controller has a built in USB port where an external memory device...

Страница 88: ...11 45 00 00 3 Al_BMS_Offline Active Start 2022 01 24T08 10 59 00 00 39 Al_EA_Flow_Rate_Prb Active Start 2022 01 24T08 10 59 00 00 38 Al_OA_Flow_Rate_Prb Active Start 2022 01 24T08 10 55 00 00 42 Al_S...

Страница 89: ...tore Parameters Settings You can also share them between controllers An excerpt of a file is shown below Ver 1 0 cpCO Family Exported Configuration file 10 3 VIEWING PARAMETER FILES VARIABLE DESCRIPTI...

Страница 90: ...connect to the embedded web pages inside the controller 10 4 1 Upgrade Type Connect via USB 1 Save the parameters using the General Save and Restore method Make sure you choose EXPORT Remember the Exp...

Страница 91: ...thumb drive called UPGRADE 3 Carefully connect the micro USB drive to the front connection of the controller long side to the bottom 4 You will be prompted to press ENTER to proceed 5 Once it is done...

Страница 92: ...l system monitoring It is here only to provide a general sense of how to monitor the system Specific screens and information appear depending upon the features you have selected Refer to the documenta...

Страница 93: ...due to alarm The unit is off by a serious alarm Unit switched off by BMS The unit is off by command from the BMS Unit switched off by time band The unit is off by the scheduler Unit switched off by di...

Страница 94: ...OA The heating OA lockout is higher than the OA temperature Unit OFF Unit is off 11 5 2 Cooling Screens If in dehumidification this screen will reflect the cooling used for dehumidification Each scre...

Страница 95: ...u The economizer damper command u Cooling status This screen contains all frost control information 11 6 FROST CONTROL INFORMATION This screen is described in Verifying all I O through Unit Status Sc...

Страница 96: ...ital Input for start stop terminals 17 and 18 are closed u The unit is turned on at the keypad u The time is within the scheduler ON time if scheduler enabled u The BMS has written the unit on signal...

Страница 97: ...pping If upgrading from an older version and you want to keep that mapping change the setting below to Pri Array legacy The mapping is quite different and is supported in the older documentation Also...

Страница 98: ...Address Baud rate Max Master and Max Info frames as needed If you need to set the timing values you can do that here 12 3 4 BACnet MSTP Wiring The BACnet MSTP network is wired into the four pin conne...

Страница 99: ...mand Val Exhaust Fan Command actual Read_NoWrite Analog Input 28 CO2_Level Val CO2 Level PPM Read_NoWrite Analog Input 29 VOC_Level Val VOC Level PPM Read_NoWrite Analog Input 30 Space_Pressure Val Sp...

Страница 100: ...or PPM Read_Writeable Analog Value 54 BMS_Space_Press_ Reading Coil LAT Setpoint for dehumidification F Read_Writeable X Analog Value 55 Occ_HTG_Setp Val Occupied Heating Setpoint F Read_Writeable X A...

Страница 101: ...K Alarm Read_NoWrite Binary Input 501 Al_Err_retain_write Active Too Many Writes to Retained Memory OK Alarm Read_NoWrite Binary Input 502 Al_Device_Test Active Unit Was Left In Device Test Mode OK Al...

Страница 102: ..._Flow_Rate_Prb Active OA Flow Rate Pressure Transmitter Out of Range OK Alarm Read_NoWrite Binary Input 539 Al_EA_Flow_Rate_Prb Active EA Flow Rate Pressure Transmitter Out of Range OK Alarm Read_NoWr...

Страница 103: ...ControlType_BN See Notes Read_NoWrite MultiState Input 5 CLG_ControlType_BN CLG_ControlType_BN See Notes Read_NoWrite MultiState Input 6 Heating_SetPtType_BN Heating_SetPtType_BN See Notes Read_NoWrit...

Страница 104: ...SA_Temp Val EA OA RA SA CA UNITSTATUS_BN MULTISTATE INPUT 7 VALUE STATUS MEANING 1 Unit on The unit is on and running 2 Unit switched off due to alarm The unit is off by a serious alarm 3 Unit switch...

Страница 105: ...read at Binary Input 15 SF_Status Val The actual flow rate is viewed at Analog input 6 OA_Flow_Rate Val The exhaust fan control type method can be viewed at Multistate Input 3 EF_ControlType_BN The va...

Страница 106: ...if adjustable setpoint is chosen Otherwise the setpoint is based on an outdoor temperature schedule The type is Multistate Input 6 Heating_SetPtType_ BN where 1 Adjust and 2 OA Reset The acting setpoi...

Страница 107: ...Val minus Analog Value 78 Defrost_OA_SetP DBright and turns off again when the OA exceeds the AV77 During this time the supply fan is OFF and the OA damper is closed 12 5 7 Filter Monitoring Filter p...

Страница 108: ...troller itself or on the RUT page of the web pages 5 Once the upgrade is finished the controller will ask you to reboot You can then verify that the license is installed by going to the RUT page 12 6...

Страница 109: ...to the bottom 2 You should see a folder called UPGRADE in the controller Put the file in that folder 3 Once finished you will be prompted to press ENTER again You should now see the license is instal...

Страница 110: ...iring The Modbus RTU network is wired into the four pin connector named J3 Disp In the upper left hand corner of the controller This is also used for a RUT display so the two cannot be used at the sam...

Страница 111: ...empering Mode Heat Cool Read_NoWrite DiscreteInput 2 AlarmMng AlrmRes Alarm Reset Status No Yes Read_NoWrite DiscreteInput 3 SF_Status Val SF Status from Current Sensor Off On Read_NoWrite DiscreteInp...

Страница 112: ...g BMS CO2 Reading in lieu of attached sensor PPM Read_Writeable HoldingRegister 36 BMS_SpacePressPress_ Reading BMS Space Pressure iwc Read_Writeable X HoldingRegister 38 Occ_HTG_Setp Val Occupied Hea...

Страница 113: ...trolType_BN See Notes Read_NoWrite InputRegister 43 EF_ControlType_BN EF_ControlType_BN See Notes Read_NoWrite InputRegister 44 HTG_ControlType_BN HTG_ControlType_BN See Notes Read_NoWrite InputRegist...

Страница 114: ...SA CA UNITSTATUS_BN INPUT REGISTER 50 VALUE STATUS MEANING 1 Unit on The unit is on and running 2 Unit switched off due to alarm The unit is off by a serious alarm 3 Unit switched off by BMS The unit...

Страница 115: ...ponding settings are as follows u Constant Speed setpoint is Holding Register 16 EF_ConstantSpeedSetP Val u Exhaust Airflow setpoint is Holding Register 18 EF_FlowControlSetP Val u Exhaust Fan Trackin...

Страница 116: ...Val for stage two u Input Register 36 Heating_Command Val shows a percentage for the 0 10V output It is also possible for the BMS to take over total control of the 10 0V hot water valve signal out to...

Страница 117: ...izer Econ_Low_RA_Temp_Limit 12 9 6 Frost Control The frost control function is enabled when the OA is lower than Holding Register 64 Defrost_ OA_SetP Val minus Holding Register 66 Defrost_OA_SetP DBri...

Страница 118: ...old for alarm to alert that service is required and the ability to reset those numbers once service is performed 13 1 RUN HOURS AND STARTS This screen gives information on the last time the unit was p...

Страница 119: ...lues most setpoints and or NVRAM clock and IP settings You should only use this screen if directed to do so by TSS 13 5 MEMORY WIPE This screen allows you to see the status of the communication to the...

Страница 120: ...1 3 IP Addresses UNIT ID OR TAG 14 1 UNIT START UP CONDITIONS 14 0 MAINTENANCE RECORDS NAME OF SETPOINT VALUE NAME OF OFFSET VALUE NAME OF COMPONENT IP ADDRESS Controller This page is to be used to r...

Страница 121: ...sets UNIT ID OR TAG 14 2 CHANGES MADE TO UNIT AFTER START UP NAME OF SETPOINT NEW VALUE NAME OF OFFSET NEW VALUE This page is to be used to record all user changes made to controller settings and indi...

Страница 122: ...ime an updated controller program is provided by the factory and installed by the user it should be recorded here 14 4 SETTINGS BACKUP FILE Use this space to record whether or not a backup has been pe...

Страница 123: ...rror is 10 F which requires very little heat from the heater The controller sees there is an error and immediately sends a call for heat that starts at 0 1 strength and ramps up as needed but the rate...

Страница 124: ...mple the default Ti value is 30 If the value were changed to 15 sampling would occur twice as often If the value were changed from 30 to 60 sampling would occur only half as often If Ti were changed t...

Страница 125: ...ing too slowly increase the KP value and run the trial again The Command percentage should reach 100 or very nearly within 2 4 minutes Repeat the process but move the heating setpoint 20 F lower than...

Страница 126: ...ND PERCENTAGE ELAPSED TIME 0 KP Adjustment Trial 2 KP SETTING HEATING SETPOINT TEMPERATURE COMMAND PERCENTAGE ELAPSED TIME 0 KP Adjustment Trial 3 KP SETTING HEATING SETPOINT TEMPERATURE COMMAND PERCE...

Страница 127: ...ELAPSED TIME 0 Ti Adjustment Trial 2 Ti SETTING HEATING SETPOINT TEMPERATURE COMMAND PERCENTAGE ELAPSED TIME 0 Ti Adjustment Trial 3 Ti SETTING HEATING SETPOINT TEMPERATURE COMMAND PERCENTAGE ELAPSED...

Страница 128: ...0 68 0 12 09 21 0 69 8 11 63 22 0 71 6 11 20 23 0 73 4 10 78 24 0 75 2 10 38 25 0 77 0 10 00 26 0 78 0 9 63 27 0 80 6 9 28 28 0 82 4 8 94 29 0 84 2 8 62 30 0 86 0 8 31 31 0 87 8 8 01 C F K 32 0 89 6...

Страница 129: ...129 1 800 627 4499 Premium Commercial Controls ERV REFERENCE THIS PAGE I S I NTENTI ONALLY LEFT BLANK...

Страница 130: ...or Impellers Digit 13 Voltage see Restrictions 2 3 4 5 6 19 1 120V Digit 20 Disconnect 4 460V N Non Fused Standard 5 208 230V F Fused 8 575V 9 277V Digit 21 Unit Control Enhancements see Restrictions...

Страница 131: ...1XRTC 9 Unit Control Code G Terminal Strip only available in EV450 HE 1X HE1 5 with Motor Codes E and EE EC Motors 10 Unit Control Code D only available in HE 1X HE1 5 11 Dampers and Bypass not availa...

Страница 132: ...Controls Digit 11 Wall Type 2 Premium Controls S Single 3 Enhanced Controls with BACnet License D Double 4 Premium Controls with BACnet License Digit 12 Phase See Restriction 2 Digit 22 Filter Options...

Страница 133: ...1 Voltage Codes 4 8 only available with Phase Code 3 Three Phase 2 Phase Code 1 only available in Motor Codes D F G 3 Motor Code P 7 5 HP High Speed not available in LE 6X 4 Motor Codes Q and R all 10...

Страница 134: ...se None 1 Single Phase W White Paint 3 Three Phase C Custom Paint X Custom Unit Digit 13 Voltage see Restriction 3 4 460V Digit 25 Safety Listing see Restriction 6 5 208 230V L Listed 8 575V N Non Lis...

Страница 135: ...d Interlaced 2 Circuits Coil Fins Per Inch answer for each coil 6 7 8 9 10 11 12 13 14 Coil Coating answer for each coil None Electrofin UV Restrictions 1 Interlaced 2 Circuits Coil Style only availab...

Страница 136: ...VFDs in rooftop units FIGURE 15 5 0 MODEL ACS320 SHOWN FIGURE 15 5 1 VFD KEYPADS IN EBOX 15 6 1 1 ABB VFD Parameters VFD Parameters are instructions that the Variable Frequency Drives follow They are...

Страница 137: ...ED 1 Select Parameter 1603 PASS CODE press EDIT softkey 2 Use the UP DOWN buttons to scroll to 358 press SAVE softkey the entry will automatically revert back to 0 press EXIT softkey 3 Scroll up to Pa...

Страница 138: ...E 90 0 LE units 120 0 DN units 2101 START FUNCTION 1 AUTO 6 SCAN START ACS320 arrives with P2101 default at e6 SCAN START but ACS320 manual says default is 1 AUTO 2607 SWITCHING FREQUENCY 2 ON LOAD 1...

Страница 139: ...COMMENTS 9902 APPLIC MACRO 1 HVAC DEFAULT or ABB STANDARD 1 USER S1 SAVE This will save the settings above that can be restored by pressing SAVE when USER S1 LOAD is selected in parameter 9902 CHANGE...

Страница 140: ...7 5 25 0 98 136492 136458 3 136355_002 106355_000 Baldor 208 25 4 1770 10 0 31 7 98 136490 136456 3 135543_002 Dayton 208 14 0 1760 5 0 17 5 98 136491 136457 3 134314_002 Dayton 208 20 5 1770 7 5 25 6...

Страница 141: ...nameplate FLA parameter 9909 motor 1 nameplate HP plus motor 2 nameplate HP Parameter 3007 Motor Load Curve is typically 125 127 98 for motors with 1 15 Service Factor SF 115 127 90 for motors with 1...

Страница 142: ...F4 U1 V1 W1 U2 V2 W2 PE SHLD AI1 GND 10 VDC OUT AIN 2 GND 2 3 4 5 6 8 9 10 11 12 13 14 15 AO 24 VDC DIN2 DIN1 DCOM 1 7 16 GND GND DIN3 DIN4 DIN5 Exhaust VFD Input Power 208 230 VAC 3 Phase 460 VAC 3...

Страница 143: ...IN EBOX 15 6 2 1 Lenze VFD Parameters VFD Parameters are instructions that the Variable Frequency Drives follow They can be adjusted by using the keypads on the VFDs Do not change these parameters fro...

Страница 144: ...ry or ABB defaults To return to RenewAire s defaults select parameter 9902 APPLIC MACRO and press EDIT softkey Scroll down to USER 1 LOAD Not USER 1 SAVE as this will overwrite the factory settings sa...

Страница 145: ...um operating speed Hz for the motor P108 Motor Overload Set per Motor Table Critical Safety Parameter P108 Motor FLA VFD Output Rating X 100 P160 Speed at Minimum Signal 15 When analog input is used t...

Страница 146: ...2 85 460 136513 136296_000 Marathon 5 5 6 6 1 90 575 136509 136356_000 106356_000 Baldor 1 5 1 8 2 7 67 575 136509 136356_001 WEG S 1 5 1 62 2 7 60 575 136509 136357_000 106357_000 Baldor 2 2 3 2 7 8...

Страница 147: ...2 5 AT F4 L1 L2 L3 U V W PE Start Stop ACOM AIN 0 10 VDC 10 VDC OUT AIN 4 20 mA DCOM 2 5 6 25 4 11 13A 13B 13C 14 30 16 17 12 VDC OUT DIN DIN DIN DOUT AOUT RELAY 1 Exhaust VFD Input Power 575 VAC 3 Ph...

Страница 148: ...ocess by a digital device computer The controller accepts digital or analog inputs from a variety of sensors and then follows all of its programmed instructions to produce action instructions to valve...

Страница 149: ...supervisory computer with a remote terminal unit RTU in supervisory control and data acquisition systems Modbus RTU see Modbus above Modbus RTP see Modbus above NAND Memory NAND flash memory is a type...

Страница 150: ...rive A very small portable solid state hard drive that can be inserted into a USB port for storage and retrieval of data UI User Interface commonly called UI A user interface is the means by which a p...

Страница 151: ...151 1 800 627 4499 Premium Commercial Controls ERV NOTES...

Страница 152: ...y the industry s best warranty with the lowest claims due to long term reliability derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of st...

Отзывы: