91
1.800.627.4499
Premium Commercial Controls
ERV
CONTROLLER UPDATES
6. Restore the parameters using the
General Save and Restore
method. Make sure you choose
IMPORT! Use the Export_XX number you chose in step 1.
7. Cycle power.
10.4.2 Upgrade Type: Connect with a USB Thumb Drive
Connect with a USB thumb drive to the micro USB connection.
1. Save the parameters using the
General Save and Restore
method. Make sure you choose
EXPORT! Remember the Export_XX number you chose.
2. Put the autorun.ap1 file in a folder in the root of the thumb drive called “UPGRADE.”
3. Carefully connect the micro USB drive to the front connection of the controller (long side to
the bottom).
4. You will be prompted to press “ENTER” to proceed.
5. Once it is done you will be prompted to press “ENTER” to restart the controller.
6. Restore the parameters using the
General Save and Restore
method. Make sure you choose
IMPORT! Use the Export_XX number you chose in step 1.
7. Cycle power.
10.4.3 Upgrade Type: Connect via Ethernet
This requires a PC and the ability to connect to the embedded web pages inside the controller.
1. Save the parameters using the
General Save and Restore
method. Make sure you choose
EXPORT! Remember the Export_XX number you chose.
2. Go to the Upgrade Tab in the web pages.