TROUBLESHOOTING
9.2 TEST END DEVICES
The
Test End Devices
allows you to manually control outputs for testing. The unit must be off
for this feature to be enabled. An alarm will occur in one hour (default) if you forget to take the
device out of test mode.
Once done. Make sure you cycle power to end test mode and put all values back to zero.
9.2.1 Supply or Exhaust Fan Alarm Troubleshooting
These alarms, 10 and 11, mean that either the fan did not start or that the current switch did
not detect that the fan is running. To troubleshoot this:
u
Turn the unit off through the keypad.
u
In the password protected menus, go to the
Test End Devices
and enable. As shown, an alarm
will sound if you leave the unit in device test mode for more than an hour (default).
u
Open both dampers.
u
Enable both fans.