Fault indicated by code
Code Fault type
Re-set
Intake type
Cut-off
Intake value
Automatic
Manual
Digital
Analog
Compr
essors
Condenser fan
Cir
culation pump
A1
Antifreeze alarm medium cycle
B2
P05
OWT 13/11
x
x
AHt
Excess temperature at start
B1 / P16
x
IWT
10
x
x
ALt
Insufficient/or excess temperature at start C/H
B1 / P19
x
IWT
10
x
x
CP1
Compressor 1
x
x
E1
Temperature sensor medium intake defective
B1
x
IWT
10
x
x
x
E2
Temperature sensor medium output defective
B2
x
OWT 13/11
x
x
x
E3
Temperature sensor condenser defective
B3
x
PT
14/12
x
x
x
E4
Pressure tranceducer cooling cycle defective
Bn/V+
x
PS
Bn/V+
EHS
High supply voltage controller
x
x
x
x
ELS
Low supply voltage controller
Tr
x
x
x
x
EP1
EEPROM driver defective
x
x
x
x
EPb
EEPROM fault at start
Config.
x
x
x
x
EPr
EEPROM fault during operation
Config.
x
x
x
x
FL
Flow monitor has responded
ID1
x
FS
6/9
x
x
x
Hc1
Maintenance interval compressor 1
C14
x
Ht
Excessive temperature medium cycle
B1 / P16
x
IWT
10
HP1
Pressure switch HD cooling cycle
ID3
<3/hrs <3/hrs HP
2
x
on 1 min.
HP1
Tranceducer cooling cycle excess pressure
Bn/V+
x
PS
Bn/V+
x
x
x
LP1
Pressure switch ND cooling cycle
ID4
<3/hrs <3/hrs LP
3
x
x
tC1
Overload cycle 1
P08-13
x
x
x
tEr
Communication cabled remote control
x
x
x
x
tP
General overload
P08-13
x
x
x
x
Reports
LA
General reports
P08
x
D1
Report defrosting
x
dF1-2 Defrost cycle exceeded
Defrosting
period
x
x
x
Reset
1. Faults with automatic reset:
The reset is carried out automatically.
2. Faults with manual reset:
The reset can only be carried out by a specialist after the fault has been corrected.
3. Faults with semi-manual reset: The reset is first carried out automatically, afterwards only a manual reset is possible
by a specialist, after the fault has been corrected.
Fault
Code
Possible cause
check
Remedial measures
The unit
does not
start or
switches
itself
off.
ELS/EHS
Low/High supply voltage
controller
Initial voltage transformer, or mains
inlet voltage
Have checked by a
specialist.
EP1
EEprom controller error
Does the controller operate properly?
Have specialist check regulation or
parameters.
EPr
EEprom controller error
Does the controller operate properly?
Have specialist check regulation or
parameters.