background image

19 

Condensation Connection

 

 

Condensation forms on the evaporator during cooling 
operation because temperatures below the dew point 
are reached. The collection tray of the indoor unit is 
equipped with a condensation hose. The transport 
height of the condensation pump is a max. of 250 mm 
above the upper edge of the unit. 
The condensation pump switches on after a brief delay 
following the start of the unit. During cooling mode, it is 
in continuous operation. After the unit is switched off, 
the pump continues to run for approx. 7 minutes. 
To ensure that the condensation can flow freely, the 
condensation hose must be laid at an incline of at least 
2 % to a drain or to the outside. 

à

Hose extensions can be purchased as accessories. 

à

If the condensation is being guided to a drainage 
line, please install a siphon-like hose guideway which 
acts as an odour seal. 

à

To keep water from dripping, the condensation line 
should be equipped with heat insulation. 

à

If the unit is being operated at outside temperatures 
below 0°C, the lines must be placed in such a way 
that they are protected from frost. 

à

If the drains or the collection trays are more than 250 
mm from the mounted cassette, a second condensa-
tion pump purchased as an accessory should be 
used. 

à

After the hose has been laid, check to make sure 
that condensation can drain freely. 

Electric Connection

 

 
The electrical connections may only be made by author-
ised service personnel. Prior to installing the electrical 
connections on the indoor unit, the system must be cur-
rent-free. 
The electrical connections of the indoor unit and the ter-
minals of the control line to the outdoor part are located 
on the regulating panel. The regulating panel is hidden 
behind the grating on the indoor unit. 
The complete unit control is located in the regulating 
panel. The power supply is only connected to the out-
door part. The indoor unit is supplied with power from 
the outdoor part via the control line. 

1.  Open the cover of the regulating panel by removing 

the 3 screws and taking off the cover.  

2.  Guide the line through the edge protection rings on 

the fresh air connections sides into the unit and lock 
into place in the line clamp. 

3.  Begin wiring by connecting the protective conductor 

and connect the contacts of the control, neutral and 
external conductors. 

Connecting the RKV 13 C indoor unit 

L     = External conductor power supply indoor unit 
N    = Neutral conductor power supply indoor unit 
Y     = Control conductor to outdoor part (compr. on / off) 
0     = NO connection 
W2 = NO connection planned

 

Connecting the RKV 18 C and RKV 24 C indoor units

 

R    = External conductor power supply indoor unit 
C    = Neutral conductor power supply indoor unit 
Y     = Control conductor to outdoor part (compr. on / off) 
0     = NO connection 
W2 = NO connection planned 
S     = NO connection planned

 

4.   Attach the connection plugs C

LR

 and C

A

 to their 

counterparts.      

It is not possible to switch them.

 

Cable clamp 

Connection plug 
C

LR

 and C

A

 from 

the frame 

Frame mounting screws 

Connection plug 
C

LR

 and C

A

 from 

the unit 

Indoor unit 

Outdoor part 

P

ow

er connecti

on 

230V

~

 50 H

Connecting all indoor units to the RKS outdoor part 

R    = A 
C    = N 
Y     = 2 

Indoor unit 

Outdoor part 

P

ow

er connecti

on 

230V

~

 50 H

Содержание RKV 13 C

Страница 1: ...REMKO powerful like a bear REMKO RKV 13 C 18 C 24 C Ceiling Cassettes Edition GB P05 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...sonnel 16 Installation 17 Condensation Connection 19 Electrical Connection 19 Two Room and Fresh Air Connection 21 Prior to Initial Operation 22 Initial Operation 22 Certification for Initial Operatio...

Страница 4: ...indoor unit and the remote control from moisture Protect all electric cables and connection lines from being damaged for example by animals Protect the air conditioning unit and the remote con trol fr...

Страница 5: ...at the polarity is correct when inserting the batteries Use the labelling in the slot Close the battery slot again Once the reset button 20 see page 12 is pressed the remote control is ready for opera...

Страница 6: ...sor of the fan is defective or outside of its regu lation range Blinks 4 times The frost protection mechanism has been activated Blinks 10 times EEPROM defective Green light ON OFF signal It lights up...

Страница 7: ...he unit does not switch off this process must be re peated Switching the unit on Button 7 If the air conditioning unit is to be switched on only the clock may be visible on the remote control display...

Страница 8: ...mbol appears on the display M Cooling mode In this operating mode the room in the air is cooled and slightly dehumidified The following section Temperature selection buttons describes how to set the d...

Страница 9: ...late fins can be set to The air outlet plate fins are set for oscillat ing air distribution Symbols on the display The positions and settings of the air outlet plate fins are represented by the follow...

Страница 10: ...orresponding symbol disappears from the dis play 3 Remember if the unit is already switched on it is only possible to program another start up time The current settings of the unit are transferred for...

Страница 11: ...s 5 Press the button 6 repeatedly until UCFG ap pears on the display 6 Press either the button 8 or 9 to change the preset from heating pump HP to air conditioning unit AC 7 Press the button 13 to tra...

Страница 12: ...and then press the 7 button to quit the configuration menu G If no button is pressed for 30 seconds the configu ration menu is automatically exited and program ming must be started from the beginning...

Страница 13: ...e to the bottom Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all units and send it back...

Страница 14: ...ia control line outdoor part Power consumption W 75 80 105 Current consumption A 0 4 0 4 0 5 Fan capacity W 63 68 93 Fan speeds 3 automatic 3 automatic 3 automatic Air volume current per speed m h 550...

Страница 15: ...hade Electromagnetic fields are disrupt ing transmission Does the unit work when devices in the vicinity are switched off No signal transmission when sources of disruption are operated simultaneously...

Страница 16: ...bjects that emit intense heat e g lights Install it in the middle of the room instead Wall lead throughs Wall lead throughs are necessary to establish the con nection between the indoor unit and the o...

Страница 17: ...on mount and the bottom of the intermedi ate ceiling see figure above Connect the refrigerant control and condensation lines to the indoor unit as described below and check again hat the unit is posit...

Страница 18: ...t is conducted using dry nitrogen The connections that have been established are sprayed with a leak locator spray to test for imperme ability If bubbles appear the connection was not made properly Ti...

Страница 19: ...door unit the system must be cur rent free The electrical connections of the indoor unit and the ter minals of the control line to the outdoor part are located on the regulating panel The regulating p...

Страница 20: ...utral conduct External conduct No function Protection conduct Wiring diagram RKV 13 C Main board Fan motor Micro float regulator Condensation pump LED IR connection Plate fin motor and micro plate fin...

Страница 21: ...nit To do this use a black strip with ad hesive on one side which is stuck to the opening s to be sealed The strip must be able to withstand the strain from the air pressure permanently The flanged co...

Страница 22: ...indicate operation 3 Connect the unit to the power supply and switch the power on 4 Press down the buttons 9 and 13 of the re mote control for five seconds The display is deleted The letters Src for a...

Страница 23: ...re The following must be performed measured validated during initial operation Test Visible check setup assembly of outdoor part and indoor unit s OK problem Visible check of the heat exchanger OK pro...

Страница 24: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Отзывы: