Assembly Instructions for 
Service Personnel 

 

Important instructions prior to installation 

Prior to actual assembly, the following items have to be 
checked and complied with: 

à

Ensure that the contents of the package are com-
plete and that the units have no visible damage re-
sulting from transport. 

Any problems must be communicated directly to 
your contract partner and the shipping company.

 

à

Place the unit in its original packaging as close as 
possible to the location where it will be assembled to 
prevent damage from transport. 

à

Select a location to set up the unit where air can flow 
freely in and out of the device, where the unit is not 
in direct sunlight and is not close to other sources of 
heat. 

à

Air should be distributed optimally throughout all ar-
eas of the room to be cooled and no drafts should be 
created. 

à

Prior to installation, check that the electrical connec-
tion values and the data on the type plate are consis-
tent. 

à

Make sure that all electrical connections meet the 
DIN-VDE requirements. 

à

Lift the cassette on the corners and not with the re-
frigerant or condensation connections.  

à

Prior to unit assembly, the connection adaptors for 
the adjacent room connection and the fresh air con-
nection must be attached. 

à

Carefully plan where the condensation line will be 
laid. 

à

Make sure that, if laid horizontally, there is an ade-
quate incline.      
At least

 2 %.

 

à

The integrated pump can bridge a maximum height 
difference of 250 mm on top of the unit. 

But only if the condensation line flows immediately in 
a vertical direction after leaving the unit and then 
continues at an incline. 

à

Remove the protective caps of the unit connections 
just before connecting the refrigerant lines. 

à

The power supply is only connected to the outdoor 
part. The control lines to the indoor unit should be 
placed together with the refrigerant lines. 

Common installation mistakes 

When performing the installation, make sure to observe 
the following to ensure smooth operation: 

à

Do not install the unit in the direct vicinity of objects 
that emit intense heat (e.g. lights). Install it in the 
middle of the room instead. 

Wall lead-throughs 

Wall lead-throughs are necessary to establish the con-
nection between the indoor unit and the outdoor part. 
Please observe the following: 

à

For the connection line to the outdoor part, a lead-
through of at least 70 mm in diameter must be cre-
ated. 

à

The lead-through must be placed at an incline of at 
least 2% from the inside to the outside. 

à

Make sure that there are no supply lines located in 
the vicinity of the wall lead-through. 

à

The air intake and outlet openings may not be 
blocked by furniture, curtains, etc. 

à

Prevent unnecessary bends in the refrigeration lines  
to minimise the pressure loss and ensure that the 
compressor oil can recirculate properly.  

à

If the outdoor part is mounted above the indoor unit, 
take steps to recirculate the oil. 

à

If this line is connected to the drainage line, an odour 
seal must be installed the upper edge of which may 
not extend beyond the lower edge of the indoor unit. 

à

The refrigerant lines may not be bent or pressed. 

à

Protect open refrigerant lines from moisture with 
suitable caps or adhesive. 

à

Make sure that all refrigerant lines including all con-
nectors and valves are adequately insulated against 
heat. 

à

Mount the outdoor part in such a way that the differ-
ence height to the indoor unit is not more than 10 m. 

à

Make sure that the maximum length of 15 m for the 
basic length of the refrigerant line is not exceeded. 

à

Use a balance to position the unit precisely which will 
prevent condensation from leaking out. 

à

Equip the ventilation lines for adjacent room cooling 
and/or the fresh air connection including the connec-
tor piece with diffusion-sealed heat insulation. 

à

Make sure that the electrical connections have been 
properly attached to the terminals. 

Control line 

Refrigerant 
intake line 

Condensation line 

Refrigerant 
injection line 

à

We recommend cushioning the inside of the hole or 
lining it to prevent the lines from being damaged. 

Suitable materials are, for example, PVC pipes with 
an inner diameter of 70 mm.

 

à

After assembly is complete, the wall lead-through 
must be sealed with a suitable sealing compound. 

Do not use any materials containing cement or lime!

 

Содержание RKV 13 C

Страница 1: ...REMKO powerful like a bear REMKO RKV 13 C 18 C 24 C Ceiling Cassettes Edition GB P05 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...sonnel 16 Installation 17 Condensation Connection 19 Electrical Connection 19 Two Room and Fresh Air Connection 21 Prior to Initial Operation 22 Initial Operation 22 Certification for Initial Operatio...

Страница 4: ...indoor unit and the remote control from moisture Protect all electric cables and connection lines from being damaged for example by animals Protect the air conditioning unit and the remote con trol fr...

Страница 5: ...at the polarity is correct when inserting the batteries Use the labelling in the slot Close the battery slot again Once the reset button 20 see page 12 is pressed the remote control is ready for opera...

Страница 6: ...sor of the fan is defective or outside of its regu lation range Blinks 4 times The frost protection mechanism has been activated Blinks 10 times EEPROM defective Green light ON OFF signal It lights up...

Страница 7: ...he unit does not switch off this process must be re peated Switching the unit on Button 7 If the air conditioning unit is to be switched on only the clock may be visible on the remote control display...

Страница 8: ...mbol appears on the display M Cooling mode In this operating mode the room in the air is cooled and slightly dehumidified The following section Temperature selection buttons describes how to set the d...

Страница 9: ...late fins can be set to The air outlet plate fins are set for oscillat ing air distribution Symbols on the display The positions and settings of the air outlet plate fins are represented by the follow...

Страница 10: ...orresponding symbol disappears from the dis play 3 Remember if the unit is already switched on it is only possible to program another start up time The current settings of the unit are transferred for...

Страница 11: ...s 5 Press the button 6 repeatedly until UCFG ap pears on the display 6 Press either the button 8 or 9 to change the preset from heating pump HP to air conditioning unit AC 7 Press the button 13 to tra...

Страница 12: ...and then press the 7 button to quit the configuration menu G If no button is pressed for 30 seconds the configu ration menu is automatically exited and program ming must be started from the beginning...

Страница 13: ...e to the bottom Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all units and send it back...

Страница 14: ...ia control line outdoor part Power consumption W 75 80 105 Current consumption A 0 4 0 4 0 5 Fan capacity W 63 68 93 Fan speeds 3 automatic 3 automatic 3 automatic Air volume current per speed m h 550...

Страница 15: ...hade Electromagnetic fields are disrupt ing transmission Does the unit work when devices in the vicinity are switched off No signal transmission when sources of disruption are operated simultaneously...

Страница 16: ...bjects that emit intense heat e g lights Install it in the middle of the room instead Wall lead throughs Wall lead throughs are necessary to establish the con nection between the indoor unit and the o...

Страница 17: ...on mount and the bottom of the intermedi ate ceiling see figure above Connect the refrigerant control and condensation lines to the indoor unit as described below and check again hat the unit is posit...

Страница 18: ...t is conducted using dry nitrogen The connections that have been established are sprayed with a leak locator spray to test for imperme ability If bubbles appear the connection was not made properly Ti...

Страница 19: ...door unit the system must be cur rent free The electrical connections of the indoor unit and the ter minals of the control line to the outdoor part are located on the regulating panel The regulating p...

Страница 20: ...utral conduct External conduct No function Protection conduct Wiring diagram RKV 13 C Main board Fan motor Micro float regulator Condensation pump LED IR connection Plate fin motor and micro plate fin...

Страница 21: ...nit To do this use a black strip with ad hesive on one side which is stuck to the opening s to be sealed The strip must be able to withstand the strain from the air pressure permanently The flanged co...

Страница 22: ...indicate operation 3 Connect the unit to the power supply and switch the power on 4 Press down the buttons 9 and 13 of the re mote control for five seconds The display is deleted The letters Src for a...

Страница 23: ...re The following must be performed measured validated during initial operation Test Visible check setup assembly of outdoor part and indoor unit s OK problem Visible check of the heat exchanger OK pro...

Страница 24: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Отзывы: