Troubleshooting  

 
Repairs of the cooling and electrical systems may only be performed by an authorised service centre! Always remove 
the power plug from the plug socket when working on the unit!

 

This unit has been designed based on state of the art manufacturing methods and it has been tested repeatedly to 
ensure that it is working properly. However, should problems occur, refer to the following list. 
Should the unit still not work after performing these functional checks, please contact an authorised service centre.

 

Problem

 

Possible cause

 

Remedy 

The unit does not start  

Power failure. 

Check voltage and wait for the unit to start 

again. 

Defective power fuse / main switch is off 

Replace power fuse. Switch on main switch. 

Power supply line damaged. 

Maintenance by authorised personnel. 

Water tank is full. 
“DRAIN WATER” LED lit up. 

Empty container above the water drainage 
tube.

 

Unit is switched on with the timer function. 

Press the On / Off button again. 

The unit is either not cooling  
at all or only cooling a little 
bit.
 

Dirty dust filter, input and/or output opening 
blocked by foreign matter. 

Clean the filter. Make sure that the input 

and/or output opening are not blocked. 

Temperature setting too high. 

Lower temperature. 

Windows and doors open. 
Thermal load increased. 

Close windows and doors. 

Reduce thermal load. 

Condensation water leaks 
out of the unit.
 

The unit is not standing upright. 

Place upright and make sure it is firmly in 

place. 

Sealing cap is not in place. 

Reseal the water drainage tube tightly. 

Technical Data 

 

1) Room temperature of DB 27 °C /  WB 19 °C, outdoo r temperature of DB 35 °C / WB 24 °C 
2) Distance 1m freefield conditions 

Model 

 

RKL 460  

RKL 480 

RKL 480 S-Line 

Nominal Cooling capacity 

1)

 

kW 

4,18 

4,84  

Energy efficiency class 

1)

 

 

 

Energy efficiency ratio EER 

1)

 

 

3,05 

3,01  

Working range (indoor unit) 

°C 

+16 to +35 

+16 to +35 

Working range (outdoor unit) 

°C 

+15 to +45 

Refrigerant 

 

R 407C 

Air performance max. indoor unit 

m³/h  

450 / 520 / 600 

480 / 550 / 630 

Air performance max. outdoor unit 

m³/h  

640 

680 

Sound pressure level indoor unit  

2)

 

dB(A) 

48 / 50 / 52 

Sound pressure level outdoor unit  

2)

 

dB(A) 

51 

Electrical connection 

V / Hz 

230 / 1~/ 50 

Protection class indoor / outdoor unit 

IP 

24 / X4 

Nominal power consumption 

kW 

1,37 

1,61  

Nominal current 

1)

 

6,05 

7,56  

Refrigerant charge 

kg 

0,89 

1,03 

Connecting line, usable length 

2.300, not extended  

Dimensions indoor unit  

 width  

mm 

695 

 

  

 

height 

mm 

470  

 

  

 

depth 

mm 

335 

Dimensions outdoor unit  

 width  

mm 

490  

 

  

 

height 

mm 

510 

 

  

 

depth 

mm 

230 

Weight indoor unit 

kg 

35,0 

35,5 

Weight outdoor unit 

kg 

13,0 

13,0 

Color 

 

white 

white 

silver 

Serial number 

 

506... 

507... 

508... 

Ref. No. 

 

1613460 

1613480 

1613481 

Содержание RKL 460

Страница 1: ...Operation Technology Spare Parts REMKO powerful like a bear REMKO RKL 460 RKL 480 RKL 480 S Line Portable Air Conditioner Edition GB T01...

Страница 2: ......

Страница 3: ...al Data 12 Wiring Diagram 13 Exploded View 14 Spare Part List 15 Service and Guarantee 15 Environment and Recycling 15 Portable Air Conditioner REMKO RKL 460 REMKO RKL 480 S Line Make sure to read the...

Страница 4: ...off by pressing the ON OFF but ton Do not switch the unit off by unplugging the power cable When unplugging the unit always pull the power plug Never pull the cable Do not set up or operate the unit...

Страница 5: ...ndoor unit or via the infrared remote control that comes with it The unit is particularly suited for flexible use The de tachable connecting line lets it be installed as a station ary unit Outdoor uni...

Страница 6: ...t temperature can be set as de scribed above 2 Unit switches off automatically When the device is on using the SET button the user can enter the number of hours after which the device is to be switche...

Страница 7: ...does not overflow This may cause water damage 10 Operating mode and fan setting display This display provides information about the operat ing mode and the fan setting which have been se lected 11 DRA...

Страница 8: ...to the outside air To perform this function the outdoor unit can either be placed on the floor or hung on an outside wall Floor installation To set up the outdoor unit on a terrace or balcony it is no...

Страница 9: ...to a wall or to a parapet in the outer area is to use straps 1 Hook the wall holders onto the outdoor unit and se cure them with the M4 safety screws Here the wall holders maintain the proper distance...

Страница 10: ...er pressure on the upper coupling with the second wrench SW 21 Fig 15 Never turn the inflexible upper part 12 Keep turning until the connection is detached Should refrigerant leak out with a slight hi...

Страница 11: ...lly in warm water 4 Then let the filter air dry 5 Reinsert the filter into the unit In case of extreme dirt the dust filter is to be replace Never use the unit without installed dust filter Without a...

Страница 12: ...gh Lower temperature Windows and doors open Thermal load increased Close windows and doors Reduce thermal load Condensation water leaks out of the unit The unit is not standing upright Place upright a...

Страница 13: ...FM1 Fan motor indoor unit FM2 Fan motor outdoor unit WM Water pump CM Compressor motor OLP Overload protection compressor CX1 Capacitor fan motor indoor unit CX2 Capacitor fan motor outdoor unit CX3...

Страница 14: ...oor unit 35 Indoor unit 1 42 11 32 12 10 13 2 13 14 37 34 27 26 25 17 19 18 36 22 23 20 21 39 38 24 7 9 8 35 33 31 28 30 6 3 4 41 40 16 5 15 29 We reserve the right to make modifications in dimensions...

Страница 15: ...122 8 Dust filter 1106067 Dust filter RKL 480 S Line 1106123 9 Cover connecting line 1106068 Cover connecting line RKL 480 S Line 1106124 10 Cover bottom 1106069 11 Base plate cpl 1106070 12 Transport...

Страница 16: ...REMKO GmbH Co KG Air Conditioning and Heating Technology D 32791 Lage Im Seelenkamp 12 D 32777 Lage P O Box 1827 Phone 49 52 32 606 0 Fax 49 52 32 606 260 E mail export remko de Internet www remko de...

Отзывы: