Error codes and their meanings
Code Error description
Cause
Remedial measures
P01
Probe, storage tank bottom,
defective
Defective or short-circuited.
Plug-in contact not correct
Check probe resistance.
Replace probe
P02
Probe, storage tank top, defec-
tive
P034 Probe, collector defective
P04
Probe, ambient air defective
P05
Probe, evaporator defective
P07
Probe, suction pipe defective
E01
High pressure fault
Refrigerant pressure is too
high, pressure switch has trig-
gered
Check pressure, water temper-
ature too high
E02
Low pressure alarm
Refrigerant pressure is too low,
pressure switch has triggered
Check pressure, refrigerant
deficiency
E03
Overheating error
Water level too low
Check water level
E08
Communication fault
Communication error between
operating unit and motherboard
Cable connection, check plug-
in contacts
REMKO RBW
38