Parameter list (expert level) - continued
No.
Description
Code Para-
meter Value
Range
61
Ambient temperature
t
t01
Measured
value
-9~99°C
62
Storage tank temperature, lower
t02
Measured
value
-9~99°C
63
Storage tank temperature, upper
t03
Measured
value
-9~99°C
64
Evaporator temperature
t04
Measured
value
-9~99°C
65
Suction gas temperature
t05
Measured
value
-9~99°C
66
Collector temperature
t06
Measured
value
-9~99°C
67
Compressor status
O
O01
Status
On/Off
68
Electric heating coil status
O02
Status
On/Off
69
Solenoid valve defrost
O03
Status
On/Off
70
Fan speed low
O04
Status
On/Off
71
Fan speed high/ circulation pump/ solar pump
O05
Status
On/Off
72
Operation circulation pump/solar pump
O06
Status
On/Off
73
EEV position
O07
Status
0~500
Parameter list (operator level)
No.
Description
Para-
meter Value
Range
1
Start defrost temperature (evaporator)
d01
-3°C
-30°C~0°C
2
End defrost temperature (evaporator)
d02
13°C
2~30°C
3
Time between defrosts
d03
45 min
30~90 min
4
Max. defrosting period
d04
8 min
1~12 min
5
Duration of legionella function
g02
0 min
0~90 min
6
Time start of legionella function
g03
0 h
0~23 h
7
Time interval (day) of legionella function
g04
7D
7~99 days
8
Max. storage tank temperature solar pump stop
n10
84°C
50~90°C
9
Switch-on delay electr. heating coil
r06
200 min
0~450 min
REMKO RBW
34