Parameter description
Para-
meter
Designation
Description
d01
Start defrost temperature (evaporator)
If the evaporator temperature is < d01 then the
defrosting process starts
d02
End defrost temperature (evaporator)
If the evaporator temperature is > d02 then the
defrosting process ends
d03
Time between defrosts
This is the min. run-time of the heat pump
between 2 defrosting processes
d04
Max. defrosting period
Once the set time d04 lapses, defrosting ends
g02
Duration of legionella function
Time of the legionella function
g03
Time start of legionella function
The legionella function starts at this time
g04
Time interval (day) of legionella function
The legionella function is activated at this
interval (number of days)
n10
Max. storage tank temperature solar pump stop
If the storage tank temperature is higher than
n10, the solar pump r06 stops: Switch-on delay
electrical heating coil. Upon exceeding the set
run-time r06, the electrical heating coil is
switched on