Initial Operation

 

 

Prior to initial operation 

Prior to initial operation, the following must be com-
pleted: 

1.  Check that assembly is mechanically sound. 
2.  Check that the connection to the customer-installed 

heating system is correct. 

3.  Check that the frost protection mechanism is work-

ing properly 

 

If assembled.

 

4.  Make sure that hot surfaces, e.g. the supply lines, 

are protected against unintentional contact. 

5. Ensure that the unit’s electrical wiring has been 

made in accordance with the relevant guidelines and 
standards and complies with the enclosed wiring 
diagrams. 

6.  Check the fan area as well as the air intake and out-

let area for foreign objects. 

7.  Make sure that all air outlet openings are opened. 
8.  Ensure that the distance between the fan wheel and 

housing is the same all the way around. 

9.  Activate the power supply to the switching unit and 

switch the unit on via the control switch. 

10. Check to make sure that the fan is rotating in the di-

rection of the arrow.   

The rotational direction can be changed by reversing 
the 2 phases.

 

11. Remember that when using speed control, the ca-

pacity of the regulating unit must be adjusted to the 
capacity of the motor. 

12. Initial operation is prohibited until it is ensured that 

the proper assembly and electrical installation corre-
sponds to the provisions of the EU guidelines 
89/392/EWG and 73/23/EWG. 

During initial operation 

All regulating, control and safety mechanisms must be 
checked to ensure that they are functioning properly 
and set correctly during initial operation. 

1. Measure the power consumption of the fan. 

The rated current may not exceed the value speci-
fied on the type plate in each switch phase.

 

2.  Check the control/regulating function of the fan. 
3.  Check the motor protection function of the fan. 
4.  Check the function of the frost protection mecha-

nism and the room thermostat 

 

If mounted.

 

5.  Check that the fan is running quietly. 
6.  Check the entire system for any vibrations. 
7.  Check that the heating medium supply lines have 

been properly connected and are impermeable. 

The control switch must always be reset to “0” to 
restart the unit after the switching unit is sepa-
rated from the power supply, following a power 
outage or a malfunction.  

 

Shutting Down the Unit

 

 

Prior to longer periods of non-operation

 

◊ 

Switch all poles of the electrical connections off. 

◊ 

If there is a danger of frost, drain the system if the 
heating medium (water) has not been mixed with a 
suitable anti-freeze. 

It is only possible to completely drain the heat-
exchanger with compressed air. 

 

Proper use 

The units are designed exclusively for industrial and com-
mercial heating and insulation purposes on the basis of 
their design and equipment. 
The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are 
made to the units. 

 

Operation/handling which does not comply with 
these instructions is prohibited!  
In cases of non-compliance, we assume no liability 
and the guarantee becomes null and void.

 

Customer Service and 
Guarantee

 

 

For the guarantee to be valid, the purchaser or his cus-
tomer must completely fill out the "

guarantee certificate

enclosed with all units and send it back to REMKO GmbH 
& Co. KG

The units are repeatedly tested at the production site to 
ensure that they are working properly. If a malfunction 
occurs that cannot be eliminated by the operating per-
sonnel, please contact your dealer or contract partner. 

Содержание PWW 4000

Страница 1: ...REMKO powerful like a bear REMKO PWW 4000 Warm Water Heating Units Edition GB P08 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...Technical Data 9 Accessories 10 Switching Units 12 Read these instructions carefully before setting up operating the unit Our guarantee becomes null and void if the unit is used set up or maintained...

Страница 4: ...that the units are as sembled safely and effectively The units are to be placed in such a way that areas where people work and spend time are not in the di rect air current The units may only be mount...

Страница 5: ...eft The units operate on the principle of counter current The water supply line usually comes in at the bot tom The water usually goes out return line at the top Draining in case of frost It is not po...

Страница 6: ...t cause damage In cases of non compliance the guarantee becomes null and void The electrical connection may only be made by trained and authorised personnel Connecting several units If necessary sever...

Страница 7: ...the type plate in each switch phase 2 Check the control regulating function of the fan 3 Check the motor protection function of the fan 4 Check the function of the frost protection mecha nism and the...

Страница 8: ...ake and outlet openings from being blocked Check the protection grilles and the heat exchanger at regular intervals for dirt Inspect any mounted filters Clean or exchange if necessary Important precau...

Страница 9: ...ht kg 26 27 34 36 PWW 4000 series Type 4080 3 4080 4 4100 3 4100 4 Electrical connection V 400 3 N 400 3 N 400 3 N 400 3 N Frequency Hz 50 50 50 50 Power consumption kW 0 42 0 28 0 42 0 28 0 76 0 47 0...

Страница 10: ...MLK mixed air box The MLK mixed air box is designed to be mounted on the wall or the ceiling The ratio of outside air to circulation air can be set manually with the mixed air flaps in gradual stages...

Страница 11: ...ment range 25 to 95 C switching differential adjustable Maximum ambient temperature 70 C Contact 1 Opens when the temperature rises Contact 2 Closes when the temperature rises 2 1 C Technical data Adj...

Страница 12: ...2 3 4 PE L1 L2 L3 N 1 5 7 8 9 6 10 11 12 13 PE U1 V1 W1 U2 V2 W2 TK TK 14 15 RT RT 16 4 4 4 11 1 3 5 13 2 4 6 14 Room thermostat Thermal contacts in the motor Incoming power 400V 3 N PE 50HZ Grounding...

Страница 13: ...uous Operation control relay terminals for the motor output connection terminals for the thermal contacts room thermostats and frost protection thermostats Functionality The frost protection thermosta...

Страница 14: ...for the thermal contacts room thermostats frost protection thermostats mixed air adjustment motor and flap positioning switch Functionality The mixed air box can be controlled by means of a flap posit...

Страница 15: ......

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik 32791 Lage Im Seelenkamp 12 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606 260 E mail info remko de Internet www remko de...

Отзывы: