Technical Data 

PWW 4000 series 
Type 

 

4030 - 3 

 

4030 - 4 

 

4050 - 3 

 

4050 - 4 

Electrical connection 

400 / 3~ N 

400 / 3~ N 

400 / 3~ N 

400 / 3~ N 

Frequency 

Hz 

50 

50 

50 

50 

Power consumption 

kW 

0.13 / 0.10 

0.13 / 0.10 

0.26 / 0.18 

0.26 / 0.18 

Rated current 

0.26 / 0.16 

0.26 / 0.16 

0.52 / 0.29 

0.52 / 0.29 

Speed 

U/min 

1340 / 1040 

1340 / 1040 

1360 / 1020 

1360 / 1020 

Air capacity 

m³/h 

2050 / 1640 

1850 / 1500 

3400 / 2870 

3150 / 2770 

Sound pressure level 

1)

 

dB(A) 

53 / 48 

55 / 49 

55 / 51 

58 / 54 

Heating medium connection 

inch 

R1" 

R1¼" 

R1" 

R1¼" 

Heating medium 

 

Pump warm water or pump hot water up to max. 130 °C 

Operating pressure 

bar 

16 

16 

16 

16 

Weight 

kg 

26 

27 

34 

36 

PWW 4000 series 
Type 

 

4080 - 3 

 

4080 - 4 

 

4100 - 3 

 

4100 - 4 

Electrical connection 

400 / 3~ N 

400 / 3~ N 

400 / 3~ N 

400 / 3~ N 

Frequency 

Hz 

50 

50 

50 

50 

Power consumption 

kW 

0.42 / 0.28 

0.42 / 0.28 

0.76 / 0.47 

0.76 / 0.47 

Rated current 

0.76 / 0.46 

0.76 / 0.46 

1.50 / 0.81 

1.50 / 0.81 

Speed 

U/min 

880 / 670 

880 / 670 

870 / 650 

870 / 650 

Air capacity 

m³/h 

5400 / 4300 

4730 / 4700 

8250 / 6620 

7670 / 6180 

Sound pressure level 

1)

 

dB(A) 

55 / 49 

55 / 49 

58 / 54 

59 / 55 

Heating medium connection 

inch 

R1¼" 

R1¼" 

R1½" 

R1½" 

Heating medium 

 

Pump warm water or pump hot water up to max. 130 °C 

Operating pressure 

bar  

16 

16 

16 

16 

Weight 

kg 

47 

51 

60 

68 

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s 

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s 

Содержание PWW 4000

Страница 1: ...REMKO powerful like a bear REMKO PWW 4000 Warm Water Heating Units Edition GB P08 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...Technical Data 9 Accessories 10 Switching Units 12 Read these instructions carefully before setting up operating the unit Our guarantee becomes null and void if the unit is used set up or maintained...

Страница 4: ...that the units are as sembled safely and effectively The units are to be placed in such a way that areas where people work and spend time are not in the di rect air current The units may only be mount...

Страница 5: ...eft The units operate on the principle of counter current The water supply line usually comes in at the bot tom The water usually goes out return line at the top Draining in case of frost It is not po...

Страница 6: ...t cause damage In cases of non compliance the guarantee becomes null and void The electrical connection may only be made by trained and authorised personnel Connecting several units If necessary sever...

Страница 7: ...the type plate in each switch phase 2 Check the control regulating function of the fan 3 Check the motor protection function of the fan 4 Check the function of the frost protection mecha nism and the...

Страница 8: ...ake and outlet openings from being blocked Check the protection grilles and the heat exchanger at regular intervals for dirt Inspect any mounted filters Clean or exchange if necessary Important precau...

Страница 9: ...ht kg 26 27 34 36 PWW 4000 series Type 4080 3 4080 4 4100 3 4100 4 Electrical connection V 400 3 N 400 3 N 400 3 N 400 3 N Frequency Hz 50 50 50 50 Power consumption kW 0 42 0 28 0 42 0 28 0 76 0 47 0...

Страница 10: ...MLK mixed air box The MLK mixed air box is designed to be mounted on the wall or the ceiling The ratio of outside air to circulation air can be set manually with the mixed air flaps in gradual stages...

Страница 11: ...ment range 25 to 95 C switching differential adjustable Maximum ambient temperature 70 C Contact 1 Opens when the temperature rises Contact 2 Closes when the temperature rises 2 1 C Technical data Adj...

Страница 12: ...2 3 4 PE L1 L2 L3 N 1 5 7 8 9 6 10 11 12 13 PE U1 V1 W1 U2 V2 W2 TK TK 14 15 RT RT 16 4 4 4 11 1 3 5 13 2 4 6 14 Room thermostat Thermal contacts in the motor Incoming power 400V 3 N PE 50HZ Grounding...

Страница 13: ...uous Operation control relay terminals for the motor output connection terminals for the thermal contacts room thermostats and frost protection thermostats Functionality The frost protection thermosta...

Страница 14: ...for the thermal contacts room thermostats frost protection thermostats mixed air adjustment motor and flap positioning switch Functionality The mixed air box can be controlled by means of a flap posit...

Страница 15: ......

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik 32791 Lage Im Seelenkamp 12 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606 260 E mail info remko de Internet www remko de...

Отзывы: