Unit Assembly

 

 

Brackets

 

Brackets for wall and ceiling assembly (2 per unit) are 
inserted into the openings at the back of the unit and at-
tached with the supplied screws. 
Components that are attached directly to the units, 
such as mixed-air boxes or filter boxes, are equipped 
with a bracket adapter.  
When using customer-installed bracket constructions, 
the minimum distance to the wall (dimension "e") must 
be observed! 

KO bracket

 

For wall and ceiling assembly 

Cu / Al heat-exchangers 

The heat-exchangers are made of copper pipes with alu-
minium plate fins pressed onto the outside. The plate fin 
package is surrounded by a galvanized, zinc-plated steel 
frame. 
The collector and the distributor are made of steel. 
Please observe the following for the heat-exchangers:

 

◊ 

The heating medium connection is made via 
threaded connectors. 

◊ 

The maximum operating temperature is 130 °C. 

◊ 

The maximum operating pressure is 16 bar.

 

◊ 

The heat-exchangers are not suitable for operation 
with steam or thermal oil. 

Connection to the heating system 

◊ 

The REMKO PWW is to be connected by the cus-
tomer via the shut-off valve, automatic air bleeder 
and screws in the supply and return lines. 

 

Use compensators if necessary.

 

◊ 

It does not matter which side is connected. 

 

Right or left.

 

◊ 

The units operate on the principle of counter-current. 

◊ 

The water (supply line) usually 

comes in 

at the bot-

tom. The water usually 

goes out 

(return line) at the 

top. 

Draining in case of frost 

It is not possible to statically drain the heat-exchanger 
completely. The heat-exchanger can only be com-
pletely drained when compressed air is used. 

Drainage 

Ventilation 

Frost protection thermostat 

Screws 

Incoming air 

Outgoing air 

Incoming water 

Outgoing water 

PWW 

Dimension 

4030-3 / 4 

560 

430 

510 

155 

270 

4050-3 / 4 

640 

505 

590 

192 

270 

4080-3 / 4 

800 

620 

750 

250 

270 

4100-3 / 4 

880 

730 

830 

305 

340 

The brackets must be current-free and screwed on 
to the unit and the wall/ceiling. 

 

◊ 

After assembly, the heat-exchanger must be care-
fully ventilated.   

Air pockets in the register reduce the unit perform-
ance.

 

◊ 

You can find the thread sizes of the heat register in 
the technical data. 

When the fan is idle, the heating medium supply 
must be interrupted. 

 

Important information about frost protection! 

To prevent frost damage, a frost protection mechanism 
must be attached for temperatures below 0 °C. 
There may not be any water in the heat-exchanger for 
systems taken out of operation in rooms susceptible to 
frost. The remaining water must be blown out with com-
pressed air. 
If this is not possible, the heating medium (water) must 
be mixed with a suitable anti-freeze.  

No guarantee claims can be made for frost damage 
on the heat-exchanger! 

 

KO 

Ø

12.5 

Содержание PWW 4000

Страница 1: ...REMKO powerful like a bear REMKO PWW 4000 Warm Water Heating Units Edition GB P08 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...Technical Data 9 Accessories 10 Switching Units 12 Read these instructions carefully before setting up operating the unit Our guarantee becomes null and void if the unit is used set up or maintained...

Страница 4: ...that the units are as sembled safely and effectively The units are to be placed in such a way that areas where people work and spend time are not in the di rect air current The units may only be mount...

Страница 5: ...eft The units operate on the principle of counter current The water supply line usually comes in at the bot tom The water usually goes out return line at the top Draining in case of frost It is not po...

Страница 6: ...t cause damage In cases of non compliance the guarantee becomes null and void The electrical connection may only be made by trained and authorised personnel Connecting several units If necessary sever...

Страница 7: ...the type plate in each switch phase 2 Check the control regulating function of the fan 3 Check the motor protection function of the fan 4 Check the function of the frost protection mecha nism and the...

Страница 8: ...ake and outlet openings from being blocked Check the protection grilles and the heat exchanger at regular intervals for dirt Inspect any mounted filters Clean or exchange if necessary Important precau...

Страница 9: ...ht kg 26 27 34 36 PWW 4000 series Type 4080 3 4080 4 4100 3 4100 4 Electrical connection V 400 3 N 400 3 N 400 3 N 400 3 N Frequency Hz 50 50 50 50 Power consumption kW 0 42 0 28 0 42 0 28 0 76 0 47 0...

Страница 10: ...MLK mixed air box The MLK mixed air box is designed to be mounted on the wall or the ceiling The ratio of outside air to circulation air can be set manually with the mixed air flaps in gradual stages...

Страница 11: ...ment range 25 to 95 C switching differential adjustable Maximum ambient temperature 70 C Contact 1 Opens when the temperature rises Contact 2 Closes when the temperature rises 2 1 C Technical data Adj...

Страница 12: ...2 3 4 PE L1 L2 L3 N 1 5 7 8 9 6 10 11 12 13 PE U1 V1 W1 U2 V2 W2 TK TK 14 15 RT RT 16 4 4 4 11 1 3 5 13 2 4 6 14 Room thermostat Thermal contacts in the motor Incoming power 400V 3 N PE 50HZ Grounding...

Страница 13: ...uous Operation control relay terminals for the motor output connection terminals for the thermal contacts room thermostats and frost protection thermostats Functionality The frost protection thermosta...

Страница 14: ...for the thermal contacts room thermostats frost protection thermostats mixed air adjustment motor and flap positioning switch Functionality The mixed air box can be controlled by means of a flap posit...

Страница 15: ......

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik 32791 Lage Im Seelenkamp 12 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606 260 E mail info remko de Internet www remko de...

Отзывы: