5.6 Oil return measures
If the outdoor unit is installed at a higher level than
the indoor unit, suitable oil return measures must
be taken. Usually, an oil pump bend is installed for
every 7 metres of height difference.
1
A
B
2
Fig. 28: Oil return measures
A: Outdoor unit
B: Indoor unit
1: 1 x oil pump bend in suction pipe to outdoor
unit every 7 metres of height difference, radius:
50 mm
2: Max. 10/(20) m (SKW 521 DC)
5.7 Wall bracket for the indoor unit
A
B
D
G
C
E
F
H
Fig. 29: Mounting points for the wall bracket SKW 261-521 DC (rear view, all dimensions in mm)
Unit type/
dimensions
A
B
C
D
E
F
G
H
SKW 261-351 DC
415
390
44
47
115
245
580
225
SKW 521 DC
463
494
40
47
105
242
675
282
The diameter of the pipe break-through is 65 mm for all unit types.
The wall bracket for the units must be attached with suitable screws and anchors.