Error code:
EC
Reason:
The evaporator probe T2 measures the actual value with the compressor start and takes
this as the reference value T
Start
. If, 5 minutes after the compressor start, the value T
Start
has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrig-
erant is low. The measurement is performed a total of 3 times before the display shows the
error code "EC".
Cause:
n
Refrigerant low or cooling circuit blocked
n
Evaporator probe T2 defective
n
Indoor unit control board defective
Switch off voltage, switch on again 2 minutes
later. Is the error still present?
YES
Check whether the indoor unit blows out cold
air.
JOO
Check the position and function of the evapo-
rator probe T2. Is it correctly seated and with
the correct resistance?
NO
YES
Check the cooling circuit for leaks. Leaks
found?
Exchange the control boards of the indoor unit.
JOO
Remedy leaks and put the unit back into opera-
tion.
NO
Check the cooling circuit for any blockages. Are
the shut-off valves on the outdoor unit open?
REMKO SKW series
48