Fig. 34: Flanging the refrigerant piping
1: Flanging tool
Fig. 35: Correct flange shape
2
1
Fig. 36: Tightening the fitting
1: Tighten with the first open-ended spanner
2: Counter with the second open-ended spanner
Pipe dimension
in inches
Tightening torque
in Nm
1/4"
15-20
3/8"
33-40
1/2"
50-60
5/8"
65-75
3/4"
95-105
6.3 Additional notes on connecting
the refrigerant piping
n
When combining the outdoor unit with some
indoor units, the procedure for connecting the
refrigerant piping may differ. Install the pro-
vided reducer or expansion fittings to the
indoor unit.
n
If the basic length of the connecting line
exceeds 5m, add refrigerant when commis-
sioning the system for the first time (see
chapter "Adding refrigerant").