14
REMKO ATR-5
Installation
function as expected, begin by
verifying that it is correctly connected
and that there is a power supply
■
Use probe lines in accordance with
the requirements and note the
maximum line lengths and requisite
minimum cross sections
Maximum line
length
Line cross section
30 m
0.50 mm²
45 m
0.75 mm²
60 m
1.00 mm²
90 m
1.50 mm²
■
De-energise all live lines before
working on the unit
■
Connections must be made in
accordance with the circuit diagram
on page 18
■
The unit is only approved for
connection to fixed lines
■
When installing the unit, it must be
ensured that lines carrying mains
electricity, such as the mains supply
and relay connection lines, cannot
come into contact with low-voltage
lines such as probe lines (minimum
clearance 4 mm for lines with basic
insulation)
■
The requirements of EN 60730
Part 1 must be adhered to to
ensure adequate protection against
connecting conductors self-loosening.
This may be achieved by securing the
lines with suitable cable ties
■
VDE 0100, EN 60730 Part 1 and the
regulations of the local EVU must also
be observed
■
In the event that the unit does not
Errors on connection can cause
damage to the unit! No liability
will be assumed for damage caused
by incorrect connection and/or
improper operation!
CAUTION
CAUTION
For the avoidance of malfunctions,
the external probe lines must not
be routed together with other live
lines. Observe a minimum clearance
of 4 mm when using conductors
with basic insulation.