11
Pre-setting
Limit
0.0 K
±3.0 K
SEnS
(sensor calibration display)
Stabilised temperature values must be
available for sensor calibration. In addition,
sensor calibration must be performed at a
usual room temperature of approx. 20°C.
In order to perform correct temperature
calibration, the actual temperature
displayed on the unit and the temperature
at the sensor (to be measured with
a suitable temperature measuring
instrument) must be known.
The difference between these two values
can be set within ±3.0 K limits under the
SEnS
menu item.
Example:
20.7°C
is shown on the unit display.
The temperature measuring instrument
shows
19.9°C
as the temperature at the
sensor.
– 0.8
must therefore be set under the SEnS
menu item.
NOTE
The accuracy of temperature
recording is dependent on the
length and cross-section of the lines
(see table on page 14).
s
s
s
H C
(internal changeover
"
HE
" heating/cooling display)
In "Heat" mode, the activated relay is
displayed on the left-hand side of the
display with an upwards pointing arrow
(
) and in "Cooling" mode, with a
downwards pointing arrow (
)
.
Pre-setting
Alternatives
H E
(Heating)
C o
(Cooling)
MO DI MI DO FR SA SO