5.4 Installation
Perform the installation as follows:
1.
Cut the required holes out of the mounting
template.
2.
Fasten the mounting template to the wall.
Ensure that this is level.
3.
Mark the required core holes, the fastening
points for the mounting rails and the holes for
the condensate drain and the lift protection
bracket.
A
A: Inside
4.
Remove the mounting template.
5.
Using a corresponding core drill machine,
drill two 162 mm diameter holes in the wall
for the air supply and exhaust air (the pilot
hole should be 5-10 mm. Use an incline of
approx. 3% to prevent the penetration of
water from outside.
A
A: Inside
6.
Drill the remaining holes for the condensate
drain (min. 18 mm), the wall bracket and the
lift protection bracket. The condensate drain
must have an incline of at least 3 %.
7.
Insert the supplied plastic sheets into the drill
holes and cut off the excess material so that
the plastic sheets on the outside are 5 mm
shorter than the wall thickness. Ensure that
the junction line points upwards. Then insert
the condensate hose into the hole provided.
NOTICE!
If heating mode must be used, it is recom-
mended to insulate the plastic sheets
from outside to prevent condensation in
the wall.
5 mm
A
A: Inside
REMKO series KWT