Remeha Quinta 30
22
With the ‘
code’
- display showing
A
- the
t
-display will indicate the method of boiler
control in the first segment
x[
and the option to turn the HTG and DHW on or off
in the second segment
[y
. By using codes from the table below a series of control
options are available
Example:
xy
11
- Boiler enabled internal modulation with booster on *
- HTG and DHW on (as default)
42
- Analog signal 0 -10V on temperature - HTG on and DHW off
23
- Boiler high/low - HTG off and DHW on
t
-display
Description
First segment
x[
Boiler control option
1
Boiler enabled internal modulation with booster on *
2
Boiler high/low
3
Boiler enabled internal modulation with booster off *
4
Analog signal 0-10V on temperature
5
Analog signal 0-10V on output %
t
-display
Description
Second segment
[y
Operation mode
0
HTG and DHW off
1
HTG and DHW on
2
HTG on and DHW off
3
HTG off and DHW on
Table 08 Boiler control option
* NOTE:
Booster function n/a in UK
6.6 Setting mode service level (
X00
)
(only for the qualified service engineer)
To prevent accidental, unauthorised access by non-qualified persons the control
system requires an input code to gain access to the second level of boiler control.
- Press the ‘
m
’ - and ‘
s
’-keys simultaneously and hold. The
‘code’
-display now
shows a letter
c
with a random number in the
t
-display.