21
6.5.2 Pump run on time HTG (
@
)
Pump run on time can be adjusted (Please refer to installation contractor)
- Press the ‘
m
’ -key until the digit
!
(with dot) appears in the
‘code’
-display.
- Press the ‘
s
’-key until the digit
@
(with dot) appears in the
‘code’
-display.
- Set the required value, using the [
+
] and [
-
]-keys.
- Press the ‘
e
’-key to store the new value (value will flash twice).
- Press the ‘
reset’
-key to return to operating mode.
NOTE:
For continuous pump operation use manual override,
see Par. 6.1.3.
Code
t
Description
@
00
Pump runs on for 10 seconds
@
Xx
Pump runs on for 1 to 15 minutes (
xx
=
01
to
15
)
Table 07 Pump run on time HTG
6.5.3 DHW temperature set point (
3
)
The DHW temperature is adjustable from 20 to 75°C (factory default 55°C). Only with
Broag DHW priority sensor.
- Press the ‘
m
’ -key until the digit
!
(with dot) appears in the
‘code’
-display.
- Press the ‘
s
’-key until the digit
#
(with dot) appears in the
‘code’
-display.
- Set the required value, using the [
+
] and [
-
]-keys.
- Press the ‘
e
’-key to store the new value (value will flash twice).
- Press the ‘
reset’
-key to return to operating mode.
REMARK:
there are further adjustments available on service level. Please refer to
your service engineer or contractor
(see Par. 6.6.7).
6.5.4 Boiler control setting (
A
)
The boiler is factory set to option
11
(HTG modulating or on/off with DHW on)
To change the control option:
- Press the ‘
m
’ -key until the digit
!
(with dot) appears in the
‘code’
-display.
- Press the ‘
s
’-key until the digit
A
(with dot) appears in the
‘code’
-display.
- Set the required X and Y values as listed below in using the [
+
] and [
-
]-keys.
- Press the ‘
e
’-key to store the new value (value will flash twice).
- Press the ‘
reset’
-key to return to operating mode