background image

12.4  Technical data

Tab.60 General

Quinta Ace

 

 

135

160

Nominal output (P

n

) for central heating operation (80/60°C)

min - max

 

(1)

kW

31.5 - 128.1

128.1

31.5 - 152.1

152.1

Nominal output (P

nc

) for central heating operation (50/30°C)

min - max

 

(1)

kW

34.7 - 136.1

136.1

34.7 - 161.6

161.6

Nominal input (Q

nh

) central heating operation (H

i

) G20 (H gas) min - max

 

(1)

kW

32.0 - 131.0

131.0

32.0 - 156.0

156.0

Nominal input (Q

nh

) central heating operation (H

i

) G31 (Pro­

pane)

min - max

kW

40.0 - 131.0

40.0 - 156.0

Nominal input (Q

nh

) central heating operation (H

s

) G20 (H 

gas)

min - max

 

(1)

kW

35.6 - 145.5

145.5

35.6 - 173.3

173.3

Nominal input (Q

nh

) central heating operation (H

s

) G31 (Pro­

pane)

min - max

kW

43.4 - 142.0

43.4 - 169.6

Reduced input (Q

Y20h

) central heating operation (H

i

) G20 (H 

gas)

min - max

 

(1)

kW

29.8 - 121.8

121.8

29.8 - 145.1

145.1

Reduced input (Q

Y20h

) central heating operation (H

s

) G20 (H 

gas)

min - max

 

(1)

kW

33.1 - 135.3

135.3

33.1 - 161.2

161.2

Full load central heating efficiency (Hi) (80/60 °C) (92/42/EEC)  

%

97.8

97.5

Full load central heating efficiency (Hi) (50°C/30°C) 

(EN15502)

 

%

103.9

103.6

Minimum load central heating efficiency (Hi) (return tempera­

ture 60°C)

 

%

98.4

98.4

Part load central heating efficiency (92/42/EEC) (return tem­

perature 30°C)

 

%

108.8

108.5

(1) Factory setting.

Tab.61 Gas and flue gas data

Quinta Ace

 

 

135

160

Gas test pressure G20 (H gas)

min - max

mbar

17 - 25

17 - 25

Gas test pressure G31 (propane)

min - max

mbar

37 - 50

37 - 50

Gas consumption G20 (H gas)

(1)

min - max

m

3

/h

3.4 - 13.9

3.4 - 16.5

Gas consumption G31 (propane)

(1)

min - max

m

3

/h

1.4 - 5.3

1.4 - 6.3

BREEAM NO

X

 annual emissions G20 (H gas) (EN 15502)

H

s

mg/kWh

24

22

BREEAM NO

X

 annual emissions G31 (propane) (EN 15502)

H

s

mg/kWh

23

23

BREEAM

 

Credits

2

2

Flue gas mass flow rate

min - max

kg/h

g/s

57 - 233

16 - 65

57 - 277

16 - 77

Flue gas temperature

min - max

°C

32 - 63

32 - 66

Maximum counter pressure

 

Pa

200

200

(1) Gas consumption based on lower heating value under standard conditions: T=288.15 K, p=1013.25 mbar. G20=34.02; G25.3=29.92; 

G25=29.25; G31=88.00MJ/m

3

Tab.62 Central heating circuit data

Quinta Ace

 

 

135

160

Water content

 

l

17

17

Water operating pressure

min

bar

0.8

0.8

Water operating pressure (PMS)

max

bar

4.0

4.0

Water temperature

max

°C

110

110

12 Technical specifications

7701838 - v.09 - 10122021

71

Содержание Quinta Ace 135

Страница 1: ...United Kingdom en Installation and User Manual High efficiency wall hung gas boiler Quinta Ace 135 160 HMI T control...

Страница 2: ...sing the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer...

Страница 3: ...n 14 4 3 3 Flushing the system 14 4 4 Requirements for the gas connection 15 4 5 Requirements on the flue gas discharge system 15 4 5 1 Classification 15 4 5 2 Material 16 4 5 3 Dimensions of flue gas...

Страница 4: ...57 11 3 Home screen 57 11 4 Activating holiday programs for all zones 58 11 5 Heating circuit configuration 58 11 6 Changing the room temperature of a zone 59 11 6 1 Definition of zone 59 11 6 2 Chang...

Страница 5: ...68 12 1 4 Factory test 68 12 2 Electrical diagram 68 12 3 Dimensions and connections 70 12 4 Technical data 71 13 Appendix 73 13 1 ErP information 73 13 1 1 Product fiche 73 13 2 EC Declaration of con...

Страница 6: ...ting motor lift etc 2 Shut off the gas supply 3 Open the windows 4 Report any leaks immediately 5 Evacuate the property 6 Contact a qualified installer Danger If you smell flue gases 1 Switch the boil...

Страница 7: ...al doing otherwise may result in dangerous situations and or bodily injury Warning Removal and disposal of the boiler must be carried out by a qualified installer in accordance with local and national...

Страница 8: ...allation and initial commissioning of the appliance The installer must observe the following instructions Read and follow the instructions given in the manuals provided with the appliance Install the...

Страница 9: ...lower importance but they can help you navigate or give useful information See Reference to other manuals or pages in this manual Helpful information or extra guidance Direct menu navigation confirma...

Страница 10: ...Smart controls platform The Quinta Ace boiler is equipped with the e Smart controls platform This is a modular system and offers compatibility and connectivity between all products that make use of th...

Страница 11: ...n Function FSB WHB HE 150 300 2 1 Control unit CU GH06c The CU GH06c control unit handles all basic functionality of the Quinta Ace boiler MK3 1 85 Control panel HMI T control The HMI T control is the...

Страница 12: ...ger It is forbidden to store even temporarily combustible products and substances in the boiler or near the boiler Caution Mount the boiler on a strong and solid wall at least half brick brickwork wit...

Страница 13: ...ng straps and remove 2 Remove the cardboard box 3 Take the 2 floor stands out of the packaging and place them on the floor in front of the bottom of the boiler 4 With 2 people place the boiler upright...

Страница 14: ...m per metre the maximum horizontal length is 5 metres Do not make a fixed connection in order to prevent an overpressure in the siphon 4 3 3 Flushing the system The installation must be cleaned and fl...

Страница 15: ...AD 3000924 01 Room ventilated version Without down draught diverter Flue gas discharge via the roof Air from the installation area The air supply opening of the boiler must stay open The installation...

Страница 16: ...oof terminal Muelink Grol 1 The material must also satisfy the material property requirements from the relevant chapter 4 5 2 Material Use the string on the flue gas outlet material to check whether i...

Страница 17: ...s outlet pipe Warning The pipes connected to the flue gas adapter must satisfy the following dimension requirements d1 External dimensions of flue gas outlet pipe D1 External dimensions of air supply...

Страница 18: ...L Diameter 1 90 mm 100 mm 110 mm 130 mm 150 mm Quinta Ace 135 8 m 12 m 23 m 40 m 1 40 m 1 Quinta Ace 160 5 m 8 m 15 m 37 m 40 m 1 1 With retention of the maximum flue length it is possible to apply a...

Страница 19: ...1 5 m 90 bend 2 0 m 3 0 m 3 0 m Tab 16 Pipe reduction for each bend radius 1D parallel Diameter 100 mm 110 mm 130 mm 150 mm 45 bend 1 m 1 2 m 90 bend 1 8 m 2 1 m 4 5 5 Additional guidelines Installati...

Страница 20: ...boiler is completely pre wired Never change the internal connections of the control panel Always connect the boiler to a well earthed installation The wiring must comply with the instructions in the...

Страница 21: ...ket at the level of the arrows on the side of the boiler Warning The weight of the boiler exceeds the maximum lift weight for one person Observe the applicable regulations We recommend the use of a li...

Страница 22: ...pre charge 2 Fit the expansion vessel on the central heating return pipe 5 2 3 Connecting the condensate drain pipe The siphon is supplied separately with the boiler as standard including a flexible p...

Страница 23: ...pipes turn off the main gas tap Before installing check that the gas meter has sufficient capacity Take into account the consumption of all appliances Notify the local energy company if the gas meter...

Страница 24: ...lectrical connection for gas combination block 230 RAC Electrical connection of fan The majority of components in the control unit Ignition transformer Power supply cable connection Various connection...

Страница 25: ...ble in the box with connector X021 must be slid onto the connector pin 5 pins 24 V of the PCB B Battery There is also a back up battery on the PCB for the internal clock Check the battery voltage if t...

Страница 26: ...connection cable X033 with the connector in the connection box 9 Connect the connection cable X017 with the connector in the connection box 10 Now connect the desired external controllers to the other...

Страница 27: ...NTC 1000 25 C When an on off thermostat is also connected the boiler will control the temperature with the set point from the internal heating curve OpenTherm controllers can also use the outdoor tem...

Страница 28: ...ng the parameter EP014 0 10 Volt analogue temperature regulation C The appliance can be controlled by a 0 10 Volt input signal When configured to temperature based the 0 10 V signal controls the boile...

Страница 29: ...boiler frost protection pump starts when the temperature of the heat exchanger is 6 C and the burner starts when the temperature of the heat exchanger is 3 C Lock out no frost protection with outdoor...

Страница 30: ...n contact No Normally opened contact Contact will close when status occurs Select the desired status notification setting using parameter EP018 and EP019 Connecting 0 10 V output The 0 10 contact can...

Страница 31: ...rds The interface connector will now be released 5 Pull the interface connector from the connector The interface connector is disconnected 6 Preparation of commissioning 6 1 Checklist before commissio...

Страница 32: ...en fully vented 6 Check all connections for gas tightness The test pressure may be a maximum of 60 mbar 6 2 Control panel description 6 2 1 Control panel components 1 Rotary knob to select a tile menu...

Страница 33: ...or the user Description Icon Enable installer access System Settings Version Information Tab 20 Available menus for the installer Description Icon Disable installer access Installation Setup Commissio...

Страница 34: ...ct the boiler and installation from freezing in winter Service notification service needed Installer contact details are displayed or can be filled in Tab 22 Icons On off Icon Description Icon Descrip...

Страница 35: ...008 Fan RPM Min Minimum fan speed during Central Heating Domestic Hot Water mode 900 8500 Rpm 1900 1900 GP009 Fan RPM Start Fan speed at appliance start 900 5000 Rpm 2200 2200 Before operating with a...

Страница 36: ...Tab 29 Adjustment for BREEAM with gas type G30 G31 butane propane Code Display text Description Range 135 160 DP003 Abs max fan DHW Maximum fan speed on Domestic Hot Wa ter 1000 8500 Rpm 5800 6850 GP...

Страница 37: ...t of the screen 3 Check the load test settings and adjust if necessary Only the parameters shown in bold can be changed Checking setting values for O2 at full load 1 Measure the percentage of O2 in th...

Страница 38: ...as finished select the tile to restart the chimney sweep menu A Change load test mode B Low power 3 Select the Low power test in the menu Change load test mode The low load test starts The selected lo...

Страница 39: ...re only applicable when the fan speeds have been set for BREEAM Caution The O2 values at part load must be higher than the O2 values at full load 3 If the measured value is outside of the values given...

Страница 40: ...s When you have saved the commissioning settings the option Revert commissioning settings becomes available in the Advanced Service Menu 8 Settings 8 1 Introduction to parameter codes The controls pla...

Страница 41: ...ndicate any character within the search field The list of datapoints appears in the display Only the first 30 results are shown when searching 5 Select the desired datapoint 8 3 List of parameters 8 3...

Страница 42: ...h Installer Installation Setup FSB WHB HE 150 300 Submenu 1 Parameters counters signals Parameters General 1 See the column Submenu in the following table for the correct navigation The parameters are...

Страница 43: ...e HCZP Comfort Comfort footpoint of the tempera ture of heat curve of the circuit 15 90 C CH 15 15 CP220 Zone HCZP Re duced Reduced footpoint of the tempera ture of heat curve of the circuit 15 90 C C...

Страница 44: ...n time after heat gener ator start for central heating 5 180 Sec Commercial boiler 30 30 PP015 CH Pump post run time Central heating pump post run time 1 99 Min Commercial boiler 1 1 PP016 Max CH pump...

Страница 45: ...l boiler 120 120 GP048 Fan PWM Min Minimum Pulse Width Modulation for the fan controller 0 100 GVC Pneu matic 10 10 GP050 Power Min Minimum power in kilo Watt for RT2012 calculation 0 300 kW Commercia...

Страница 46: ...required at the appropriate time Use the automatic maintenance message for preventive maintenance to keep faults to a minimum The service messages show which service kit must be used These service kit...

Страница 47: ...l operation will resume when the cause of the blocking has been rectified A blocking can become a lock out E 00 00 1 Lock out The controls will stop normal operation The cause of the lock out must be...

Страница 48: ...low check the water pres sure A 02 18 OBD Error Object Dictionary Error Configuration error Reset CN1 and CN2 See The data plate for the CN1 and CN2 values A 02 37 Uncritic device lost Uncritical dev...

Страница 49: ...elta TH TF Maximum difference between heat exchanger temperature and flow temperature Maximum difference between heat exchanger and flow temperature exceeded No flow or insufficient flow Check the cir...

Страница 50: ...e water pressure Check that the sensors are operating correctly Check that the sensor has been fitted properly Check the cleanliness of the heat exchanger Check that the central heating system has bee...

Страница 51: ...Bad connection with BUS check the wiring No PCB reconnect PCB or retrieve from mem ory using auto detect H 02 48 Funct Gr Conf Fault Function Group Configuration Fault SCB not found Carry out an auto...

Страница 52: ...connection check the wiring and connec tors Incorrectly fitted sensor check that the sensor has been correctly fitted Faulty sensor replace the sensor E 00 08 THeat Ex Open Heat exchanger temperature...

Страница 53: ...the wiring and connec tors Water circulation in wrong direction check the circulation direction pump valves Incorrectly fitted sensor check that the sensor has been correctly fitted Malfunctioning se...

Страница 54: ...ing and connec tors Incorrectly fitted sensor check that the sensor has been correctly fitted Faulty sensor replace the sensor E 04 05 TFlue Open Flue temperature sensor is either re moved or measurin...

Страница 55: ...ion check the wiring and connec tors Gas leakage control VPS faulty Replace the valve proving system VPS Gas valve unit faulty Replace the gas valve unit E 04 12 False flame False flame detected befor...

Страница 56: ...to navigate Use the button to confirm your selection 1 Press the button 2 Select Error History Enable installer access if Error History is not available 2 1 Select Enable installer access 2 2 Use code...

Страница 57: ...edit read only datapoint will appear in the display if a setting cannot be changed Tab 48 Selectable tiles for the user Tile Menu Function Information menu Read out various current values Error indica...

Страница 58: ...enu available Select the heating circuit you want to configure by selecting the tile or Tab 49 Menu to configure domestic hot water Menu Function Set heating temperatures Set the temperatures for the...

Страница 59: ...access enabled Select zone Zone friendly Name or Icon display zone Use the rotary knob to navigate Use the button to confirm your selection 1 Select the tile of the zone you want to change 2 Select Zo...

Страница 60: ...1 6 4 Timer program to control the room temperature Creating a timer program A timer program allows you to vary the room temperature per hour and per day The room temperature is linked to the activity...

Страница 61: ...y The last activity of the day is valid until the first activity of the next day Fig 67 Activities of a timer program AD 3001403 01 0 15 20 25 T 0 00 2 00 4 00 6 00 8 00 10 00 12 00 h 14 00 16 00 18 0...

Страница 62: ...otary knob to navigate Use the button to confirm your selection 1 Select the tile of the zone you want to change 2 Select Set heating temperatures A list of 6 activities and their temperatures is show...

Страница 63: ...rating mode You can change the operating mode for hot water production You can choose from 5 operating modes Operating mode Use the rotary knob to navigate Use the button to confirm your selection 1 S...

Страница 64: ...scheduled activities 5 3 Copy to other day to copy the scheduled activities of the weekday to other days 5 4 Set activity temperatures to change the temperature Activating a DHW timer program In orde...

Страница 65: ...an outdoor sensor is connected to the installation it s also possible to use the summer mode function for switching the central heating on or off CH function on Use the rotary knob to navigate Use th...

Страница 66: ...Language Select your country and language Daylight Saving Time Enable or disable daylight saving time When enabled daylight saving time will update the systems internal time to correspond with summer...

Страница 67: ...ature is lower than 4 C the boiler switches on If the water temperature is higher than 10 the burner shuts down and the pump continues to run for a short time To prevent the system and radiators freez...

Страница 68: ...2 X2 1 3 2 Pump N L X3 1 3 2 4 5 6 7 8 9 10 11 12 On off OT PWM 0 0 10 0 Tout BL RL X4 1 7 6 3 AT F1 X019 X039 X036 X5 1 7 X6 1 15 CB 01 X018 X017 X035 X033 X020 230VAC X038 Bus X037 Bus CU GH06 X12 1...

Страница 69: ...Flow sensor 12 Heat exchanger sensor 13 Return sensor 14 Hydraulic pressure sensor 15 Air pressure differential switch 16 Flue gas sensor 17 Fan control 18 Gas valve 1 19 Gas valve 2 20 Standard PCB 2...

Страница 70: ...425 80 226 602 600 143 1045 Flue gas outlet connection 100 mm Air supply connection 150 mm Siphon connection CH flow connection 1 inch male thread CH return connection 1 inch male thread Gas connecti...

Страница 71: ...i 50 C 30 C EN15502 103 9 103 6 Minimum load central heating efficiency Hi return tempera ture 60 C 98 4 98 4 Part load central heating efficiency 92 42 EEC return tem perature 30 C 108 8 108 5 1 Fact...

Страница 72: ...heat output and high tempera ture operation 2 P4 kW 128 1 152 1 Useful heat output at 30 of rated heat output and low tem perature regime 1 P1 kW 42 8 50 8 Seasonal space heating energy efficiency s...

Страница 73: ...energy consumption GJ Sound power level LWA indoors dB 68 68 See For specific precautions in relation to assembly installation and maintenance Safety page 6 13 2 EC Declaration of conformity This appl...

Страница 74: ...13 Appendix 74 7701838 v 09 10122021...

Страница 75: ...al and technological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior...

Страница 76: ...Remeha Commercial UK Brooks House Coventry Road Warwick CV34 4LL T 44 0 330 678 0140 E technical remeha co uk W www remeha co uk 7701838 v 09 10122021 7701838...

Отзывы: