10. Fill in the following data on the sticker included, and attach it next to
the data plate on the appliance.
The gas type, if adapted to another gas;
The gas supply pressure;
The flue type, if set to overpressure application;
The parameters modified for the changes mentioned above;
Any fan speed parameters modified for other purposes.
11. Optimise the settings as required for the system and user
preferences.
See
For more information; Settings, page 40 and User instructions,
12. Save the commissioning settings on the control panel, so they can be
restored after a reset.
13. Instruct the user in the operation of the system, boiler and controller.
14. Inform the user of the maintenance to be performed.
15. Hand over all manuals to the user.
7.3.1
Saving the commissioning settings
You can save all current settings on the control panel. These settings can
be restored if necessary, for example after replacement of the control unit.
> Advanced Service Menu > Save as commissioning settings
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select Advanced Service Menu.
3. Select Save as commissioning settings.
4. Select Confirm to save the settings.
When you have saved the commissioning settings, the option Revert
commissioning settings becomes available in the Advanced Service Menu.
8 Settings
8.1
Introduction to parameter codes
The controls platform makes use of an advanced system to categorise
parameters, measurements and counters. Knowing the logic behind these
codes, makes it easier to identify them. The code consists of two letters
and three numbers.
The first letter is the category the code relates to.
A
Appliance: Appliance
C
Circuit: Zone
D
Domestic hot water: Domestic hot water
E
External: External options
G
Gas fired: Gas-fired heat engine
P
Producer: Central heating
Category D codes are appliance controlled only. When the domestic hot
water is controlled by an SCB, it is handled like a circuit, with C-category
codes.
Fig.50
Example filled-in sticker
AD-3001124-01
Adjusted for
/ Réglée pour /
Ingesteld op / Eingestellt auf
/ Regolato per / Ajustado
para / Ρυθμισμένο για /
Nastawiony na / настроен
для / Reglat pentru /
настроен за / ayarlanmıştır /
Nastavljen za / beállítva/
Nastaveno pro / Asetettu
kaasulle / Justert for/
indstillet til/ ضبط ل :
C
(10)3(X)
Gas
C
(12)3(X)
mbar
Parameters
/ Paramètres /
Parameter / Parametri /
Parámetros / Παράμετροι /
Parametry / Параметры /
Parametrii / Параметри /
Parametreler / Paraméterek
/ Parametrit / Parametere /
Parametre / المعلمات :
G20
20
DP003 - 3300
GP007 - 3300
GP008 - 2150
GP009 -
Fig.51
Code on a HMI T-control
AD-3001373-02
00:12
......
......
........ .......
........ .......
....................
..... ... ....... .... .. ..... ....... .... ..... .......
..... ... ....... .... .. ..... ....
.........
..... ... ....... ....
..... ... ....... ....
....... .... .. ..... ....
.......
....... ...........
......
.....
...
CP010
CP010
Fig.52
First letter
AD-3001375-01
C
P010
8 Settings
40
7701838 - v.09 - 10122021
Содержание Quinta Ace 135
Страница 74: ...13 Appendix 74 7701838 v 09 10122021...