Code
Display text
Description
Adjustment range
Submenu
135
160
AP074
Force summer
mode
The heating is stopped. Hot water
is maintained. Force Summer
Mode
0 = Off
1 = On
Outdoor
tempera
ture
0
0
AP079
Building Inertia
Inertia of the building used for heat
up speed
0 - 255
Outdoor
tempera
ture
0
0
AP080
Frost min out
temp
Outside temperature below which
the antifreeze protection is activa
ted
-32 - 32 °C
Outdoor
tempera
ture
0
0
AP102
Boiler Pump
function
Configuration of the boiler pump
as zone pump or system pump
(feed lowloss header)
0 = No
1 = Yes
Commercial
boiler
0
0
AP110
2nd return sen
sor
Parameter to activate the 2nd re
turn sensor
0 = Inactive
1 = Active
Commercial
boiler
0
0
CP000
MaxZoneT
FlowSetpoint
Maximum Flow Temperature set
point zone
0 - 90 °C
CH
90
90
CP010
Tflow setpoint
zone
Zone flow temperature setpoint,
used when the zone is set to a
fixed flow setpoint.
0 - 90 °C
CH
90
90
CP020
Zone Function
Functionality of the zone
0 = Disable
1 = Direct
CH
1
1
CP060
RoomT. Holiday Wished room zone temperature on
holiday period
5 - 20 °C
CH
6
6
CP070
MaxReduce
dRoomT.Lim
Max Room Temperature limit of
the circuit in reduced mode, that
allows switching to comfort mode
5 - 30 °C
CH
15
15
CP210
Zone HCZP
Comfort
Comfort footpoint of the tempera
ture of heat curve of the circuit
15 - 90 °C
CH
15
15
CP220
Zone HCZP Re
duced
Reduced footpoint of the tempera
ture of heat curve of the circuit
15 - 90 °C
CH
15
15
CP230
Zone Heating
Curve
Heating curve temperature gradi
ent of the zone
0 - 4
CH
2.5
2.5
CP340
TypeReduced
NightMode
Type of reduced night mode, stop
or maintain heating of circuit
0 = Stop heat demand
1 = Continue heat de
mand
CH
0
0
CP470
Zone screed
drying
Setting of the screed drying pro
gram of the zone
0 - 30 Days
CH
0
0
CP480
ScreedStart
Temp
Setting of the start temperature of
the screed drying program of the
zone
20 - 50 °C
CH
20
20
CP490
ScreedStop
Temp
Setting of the stop temperature of
the screed drying program of the
zone
20 - 50 °C
CH
20
20
CP750
MaxZone Pre
heat time
Maximum zone preheat time
0 - 65000 Min
CH
0
0
CP780
Control strategy Selection of the control strategy for
the zone
0 = Automatic
1 = Room Temp. based
2 = Outdoor Temp. based
3 = Outdoor & room
based
CH
1
1
DP003
Abs. max fan
DHW
Maximum fan speed on Domestic
Hot Water
1000 - 8500 Rpm
Commercial
boiler
5700
6700
DP010
Hysteresis DHW Temperature hysteresis for the
heat generator to start on domestic
hot water production
0 - 60 °C
Commercial
boiler
7
7
DP011
Stop offset
DHW
Temperature offset to stop heat
generator on domestic hot water
production
0 - 60 °C
Commercial
boiler
5
5
8 Settings
7701838 - v.09 - 10122021
43