Code
Display text
Description
Adjustment range
Submenu
135
160
EP014
SCB func. 10V
PWMin
Smart Control Board function 10
Volt PWM input
0 = Off
1 = Temperature control
2 = Power control
0-10 volt in
put
0
0
GP007
Fan RPM Max
CH
Maximum fan speed during Cen
tral Heating mode
1000 - 8500 Rpm
Commercial
boiler
5700
6700
GP008
Fan RPM Min
Minimum fan speed during Central
H Domestic Hot Water
mode
900 - 8500 Rpm
Commercial
boiler
GVC Pneu
matic
1900
1900
GP009
Fan RPM Start
Fan speed at appliance start
900 - 5000 Rpm
Commercial
boiler
GVC Pneu
matic
2200
2200
GP010
GPS Check
Gas Pressure Switch check on/off 0 = No
1 = Yes
Commercial
boiler
0
0
GP021
Temp diff Modu
lating
Modulate back when delta temper
ature is larger than this threshold
5 - 25 or 40 °C
Commercial
boiler
40
25
GP022
Tfa Filter Tau
Tau factor for average flow tem
perature calculation
0 - 255
Commercial
boiler
1
1
GP024
VPS Check
Valve Proofing System check on /
off
0 = No
1 = Yes
Commercial
boiler
GVC Pneu
matic
0
0
PP007
Min anti-cycle
time
Minimum heat generator holding
time that can be reached after a
stop
0 - 20 Min
Commercial
boiler
3
3
PP012
Stabilization
time
Stabilization time after heat gener
ator start for central heating
5 - 180 Sec
Commercial
boiler
30
30
PP015
CH Pump post
run time
Central heating pump post run
time
1 - 99 Min
Commercial
boiler
1
1
PP016
Max. CH pump
speed
Maximum central heating pump
speed (%)
20 - 100 %
Commercial
boiler
100
100
PP018
Min CH pump
speed
Minimum central heating pump
speed (%)
20 - 100 %
Commercial
boiler
20
20
PP023
CH Hysteresis
Temperature hysteresis for the
generator to start on central heat
ing
1 - 25 °C
Commercial
boiler
10
10
Tab.42 Navigation for advanced installer level
Level
Menu path
Advanced installer
> Installation Setup > FSB-WHB-HE-150-300 > Submenu
> Parameters, counters, signals >
Parameters > Advanced
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Tab.43 Factory settings at advanced installer level
Code
Display text
Description
Adjustment range
Submenu
135
160
AP002
Manual Heat
Demand
Enable manual heat demand func
tion
0 = Off
1 = With setpoint
2 = TOutdoor Control
Commercial
boiler
0
0
AP026
Setpoint manual
HD
Flow temperature setpoint for
manual heat demand
7 - 90 °C
Commercial
boiler
40
40
AP056
Outdoor sensor Enable outdoor sensor
0 = No outside sensor
1 = AF60
Outdoor
tempera
ture
1
1
AP089
Installer name
Name of the installer
Mandatory
bus master
8 Settings
44
7701838 - v.09 - 10122021