Tab.59 Factory settings at basic installer level
Code
Display text Description
Adjustment range
Subme
nu
570
710
860
1000 1150 1300
AP016
CH function
on
Enable central heating
heat demand processing
0 = Off
1 = On
Gas
fired ap
pliance
1
1
1
1
1
1
AP017
DHW func
tion on
Enable domestic hot water
heat demand processing
0 = Off
1 = On
Gas
fired ap
pliance
1
1
1
1
1
1
AP074
Force sum
mer mode
The heating is stopped.
Hot water is maintained.
Force Summer Mode
0 = Off
1 = On
Outdoor
tempera
ture
0
0
0
0
0
0
CP000
MaxZoneT
FlowSet
point
Maximum Flow Tempera
ture setpoint zone
7 - 100 °C
Direct
zone
80
80
80
80
80
80
CP010
Tflow set
point zone
Zone flow temperature
setpoint, used when the
zone is set to a fixed flow
setpoint.
7 - 100 °C
Direct
zone
90
90
90
90
90
90
CP080
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP081
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP082
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP083
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP084
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP085
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP200
Manu Zo
neRoom
TempSet
Manually setting the room
temperature setpoint of
the zone
5 - 30 °C
Direct
zone
20
20
20
20
20
20
CP320
Operating
ZoneMode
Operating mode of the
zone
0 = Scheduling
1 = Manual
2 = Antifrost
3 = Temporary
Direct
zone
0
0
0
0
0
0
CP510
Temporary
Room Setp
Temporary room setpoint
per zone
5 - 30 °C
Direct
zone
20
20
20
20
20
20
CP550
Zone, fire
place
Fire Place mode is active
0 = Off
1 = On
Direct
zone
0
0
0
0
0
0
CP570
ZoneTime
Prog Select
Time Program of the zone
selected by the user
0 = Schedule 1
1 = Schedule 2
2 = Schedule 3
3 = Cooling
Direct
zone
0
0
0
0
0
0
8 Settings
60