Code
Display text
Description
Solution
E.04.11
VPS
VPS Gas Valve proving failed
Gas leakage control fault:
Bad connection: check the wiring and connec
tors
Gas leakage control VPS faulty: Replace the
GPS
Gas valve unit faulty: Replace the gas valve
unit
E.04.12
False flame
False flame detected before burner
start
False flame signal:
The burner remains very hot: Set the O
2
Ionisation current measured but no flame
should be present: check the ionisation/ignition
electrode
Faulty gas valve: replace the gas valve
Faulty ignition transformer: replace the ignition
transformer
E.04.13
Fan
Fan speed has exceeded normal op
erating range
Fan fault:
Bad connection: check the wiring and connec
tors.
Fan operates when it should not be operating:
check for excessive chimney draught
Faulty fan: replace the fan
E.04.15
FlueGas Pipe Blocked
The flue gas pipe is blocked
Flue gas outlet is blocked:
Check that the flue gas outlet is not blocked
Restart the boiler
E.04.17
GasValve Driver Err.
The driver for the gas valve is bro
ken
Gas valve unit fault:
Bad connection: check the wiring and connec
tors
Faulty gas valve unit: Replace the gas valve
unit
E.04.23
Internal Error
Gas Valve Control internal locking
Restart the boiler
Replace the CU-GH
E.04.250
Internal error
Gas valve relay error detected
-
E.04.254
Unknown
Unknown
-
10.2 Error history
The control panel includes an error memory in which is stored a history of
the last 32 errors. Details of the boiler when the error occurred can be
read out. For example;
status
sub-status
flow temperature
return temperature
These details and others can contribute to the error solution.