Tab.55 Factory settings at installer level
Code
Display text Description
Adjustment range
Subme
nu
285
355
430
500
575
650
AP001
BL function BL input function selection 1 = Full blocking
2 = Partial blocking
3 = User reset lock
ing
4 = Backup re
lieved
5 = Generator re
lieved
6 = Gen.&Backup
relieved
7 = High, Low Tariff
8 = Photovoltaic
HP Only
9 = PV HP And
backup
10 = Smart Grid
ready
11 = Heating Cool
ing
Gas
fired ap
pliance
1
1
1
1
1
1
AP006
Min. water
pressure
Appliance will report low
water pressure below this
value
0 - 6 bar
Gas
fired ap
pliance
0.8
0.8
0.8
0.8
0.8
0.8
AP008
Release
wait time
Waiting time after closing
the release contact to start
the heat generator.
0 - 255 Sec
Gas
fired ap
pliance
0
0
0
0
0
0
AP009
Service
hours
Number of heat generator
operating hours for raising
a service notification
100 - 25500 Hours Gas
fired ap
pliance
2550
0
2550
0
2550
0
2550
0
2550
0
2550
0
AP010
Service noti
fication
Select the type of service
notification
0 = None
1 = Custom notifi
cation
2 = ABC notifica
tion
Gas
fired ap
pliance
0
0
0
0
0
0
AP011
Service
hours mains
Hours powered to raise a
service notification
100 - 25500 Hours Gas
fired ap
pliance
8750 8750 8750 8750 8750 8750
AP056
Outdoor
sensor
Enable outdoor sensor
0 = No outside sen
sor
1 = AF60
2 = QAC34
Outdoor
tempera
ture
0
0
0
0
0
0
AP063
Max CH
flow setpoint
Maximum central heating
flow temperature setpoint
20 - 90 °C
Produc
er Ge
neric
Gas
fired ap
pliance
90
90
90
90
90
90
AP073
Summer
Winter
Outdoor temperature: up
per limit for heating
15 - 30.5 °C
Outdoor
tempera
ture
22
22
22
22
22
22
AP079
Building In
ertia
Inertia of the building used
for heat up speed
0 - 10
Outdoor
tempera
ture
3
3
3
3
3
3
AP080
Frost min
out temp
Outside temperature be
low which the antifreeze
protection is activated
-30 - 20 °C
Outdoor
tempera
ture
-10
-10
-10
-10
-10
-10
8 Settings
7734324 - v.03 - 29092020
55