Minimum clearances
The following illustrations indicate the minimum
clearances for trouble-free operation of the equip-
ment.
The protective zones serve to provide unhindered
air intake and outlet, as well as providing sufficient
room for performing maintenance and repairs and
preventing the unit from being damaged.
An infringement of the minimum clearances can
result in unit operation being impaired.
A
B
C
D
E
Fig. 16: Minimum clearances
Minimum clearances (all measurements in mm)
KWE
290-640
Eco
KWE
730-800
Eco
KWE
970-3150
Eco
A
1500
1500
1500
B
1500
1500
1500
C
1500
1500
1500
D
1500
1000
1500
E
2500
2500
2500
Set-up
The hermetically closed system of the refrigeration
circuit contains a flammable refrigerant of safety
class A2L.
Warning of inflammable substances!
When installing the unit, the local safety regula-
tions must be checked and observed by the spe-
cialist company carrying out the work. If necessary,
additional safety precautions must be taken in
accordance with the applicable regulations (e.g.
DIN EN 378).