Unit data KWE 1240-1480 Eco
Series
KWE
1240 Eco
KWE
1320 Eco
KWE
1400 Eco
KWE
1480 Eco
Operating mode
Air-cooled chiller for external installation in high-effi-
ciency design for cooling
Nominal cooling output
1)
kW
123.9
132.6
140.5
148.3
SEER
4.8
4.9
5.0
4.9
Annual room cooling efficiency
ŋ
S,C
%
182
188
192
187
Adjustment range - return temperature
cooling
°C
+5 to +18
Operating range, cooling
°C
+5 to +48 / -15 to +48
3)
Cooling circuits, number
2
Refrigerant
R452B
GWP value
676
Refrigerant filling quantity
kg
13.5
14.0
14.5
CO
2
equivalent
t
9.1
9.5
9.8
Compressor, number
4
Nominal flow rate
m
3
/h
39,000
Number of fans
2
Sound pressure level
2)
dB (A)
58.1
58.8
Sound power level
dB (A)
90.0
90.7
Power supply
V/Ph/Hz
400/3~N / 50
Enclosure class
IP
X4
Electrical current consumption, max.
A
146.3
153.5
Electrical rated power consumption,
cooling
kW
42.0
43.0
44.0
48.1
Electrical rated current consumption,
cooling
A
75.8
77.6
79.5
86.8
Operating medium
Water; max. 35% ethylene glycol, max. 35% propy-
lene glycol
Operating pressure, medium, max.
kPa
800
Nominal flow rate, cooling
m
3
/h
21.3
22.8
24.2
25.5
Minimum flow volume, medium
m
3
/h
12.8
13.7
14.5
15.3
Maximum flow volume, medium
m
3
/h
34.1
36.5
38.7
40.8
Pressure loss, indoor
kPa
55.5
52.4
45.1
49.6
13
Содержание KWE 1060 Eco
Страница 61: ...V Valves for hydronic balancing 45 54 W Warranty 5 61...
Страница 62: ...REMKO KWE Eco series 62...
Страница 63: ......